Indoor AC Load Switch11kv for Breaking Load Current and Closing Short-Circuit Current
Indoor AC Load Switch11kv for Breaking Load Current and Closing Short-Circuit Current image
Get Latest Price Request a quote
Basic Info.
Product Description
General:
FN5-12 series indoor AC HV load switch is suitable for AC 50Hz, 10kV network to break load current and close
short-circuit current. The load switch with fuse can break short-circuit current as protection switch. This series is
fitted with specialized CS manual operating mechanism or CS6-1 manual operating mechanism.
Characteristics:
1. Small dimension, light weight, simple structure, convenient maintenance, small operating force.
2. Reliable mechanical interlock prevents mal-operation
3. Clearly visible opening
4. Applied self-energy gas-generation arc-extinguishing has stable performance. It is both safe and reliable.
5. Composite equipments have open-phase protection function.
Techncial parameters:
Name | Unit | Data |
Rated voltage | kV | 10 |
Maximum working voltage | kV | 12 |
Rated frequency | Hz | 50 |
Rated current | A | 400 630 |
Rated short-time withstand current (thermal stable current) | kA/s | 12.5/4 20/2 |
Rated peak withstand current (dynamic stable current) | kA | 31.5 50 |
Rated closed-loop breaking current | A | 400 630 |
Rated active load breaking current | A | 400 630 |
5% rated active load breaking current | A | 20 31.5 |
Rated breaking current of cable charging | A | 10 |
Rated breaking current of no-load transformer | 1250kVA no-load current of transformer | |
Rated short-circuit closing current | kA | 31.5 50 |
Load current breaking times | load/times | 100%/20 30%/75 60%/35 5%/80 |
1min power frequency withstand voltage (effective) to earth, inter-phase, isolation opening | kV | 42/48 |
Power frequency withstand voltage between isolation openings | kV | 53 |
Lightning impulse withstand voltage(peak)to earth, inter-phase, isolation opening | kV | 75/85 |
Closing and breaking operating torque(force) | N. m | 90(180) 100(200) |
Remark: The earthing part of FN5-10D load switch also has short-circuit closing capability
Technical parameter table of FN5-10 load switch_ fuse combined power equipment
Name | Unit | Data |
Rated voltage | kV | 10 |
Maximum working voltage | kV | 12 |
Rated frequency | Hz | 50 |
Rated current | A | 100 |
Rated short-circuit breaking current(anticipated effective value) | kA | 40 |
Rated short-circuit closing current(anticipated effective value) | kA | 100 |
Rated transfer current | A | 1400 |
1min power frequency withstand voltage (effective) to earth, inter-phase, isolation opening | kV | 42/48 |
Lightning impulse withstand voltage (peak) to earth, inter-phase, isolation opening | kV | 75/85 |
Fuse-link striking output energy | J | 2-5 |
Our Services
1. | Pre sale service |
a. | make technical solution |
b. | send quotation, technical data sheet and drawing |
c. | prepare power transmission plan, testing plan and shipment plan |
2. | In sale service |
a. | supervise the manufacturing schedule totally in accordance with the plan |
b. | send photos to customer during every manufacturing process(hold point) |
c. | inform the customer one week before testing. |
3. | After sale service |
a. | installation and commissioning, training the workers |
b. | quick response within 12 hours any time |
c. | provide 12 months guarantee period normally. |
FAQ
1. Q: | What is your delivery time ? |
A: | Depend on the type of transformer. |
2. Q: | What is your payment term? |
A: | 30% advance by T/T , 70% before delivery by T/T or L/C or we can discuss about it. |
3. Q: | What kind of standard you follow? |
A: | IEC, ANSI, CS*A, GB, etc |
4. Q: | What kind of supporting documentation you can provide normally |
A: | Quotation, outline drawing, manufacturing plan, quality control plan testing plan, financial report, type test report(KEMA, CESI),reference list, etc |
5. Q: | What is your normal warranty period? |
A: | 12 months after transformer operation. |
6. Q: | Can u do installation and commission in user’s site? |
A: | Yes, we can send our installation team to user’s country for service. |
7. Q: | Do you have any experience in this kind of transformer? |
A: | Yes, we can provide reference list for check. |
Our advantages:
Quality Assurance
–From the very beginning, VILLE ensures quality in every step to achieve the best quality.
Experience Sharing
–With more than 30 years’ experience in power industry, VILLE brings you an optimized solution.
Global Service
–Wherever you are, VILLE global network will support and provide you with value.
Quick Response
–In response to your needs without delay, VILLE knows the value of your time.
Thanks for choosing VILLE as your reliable partner and
please trust both of us will create a brilliant future!
/* January 22, 2024 19:08:37 */!function(){function s(e,r){var a,o={};try{e&&e.split(“,”).forEach(function(e,t){e&&(a=e.match(/(.*?):(.*)$/))&&1
We are China Indoor AC Load Switch11kv for Breaking Load Current and Closing Short-Circuit Current manufacture and supplier,You can get more details with Email,you will get cheap price or factory price.
Get Latest Price Request a quote
Popular cnville Products
Rod Post Insulators RTV Post Insulator
Conductive Arm for Electric Arc Furnace Graphite Electrode Conductive Arm
Dbf4q Dbf Series of Fan for Transformer
33kv 40000kVA Power Distribution Transformer
Popular Indoor AC Load Switch11kv for Breaking Load Current and Closing Short-Circuit Current Products
Popular Load Switch Products
Fn12-12 Series Indoor Use High Voltage Air Breaker Switch
(Fuse Type) Gwr-12/36 Outdoor AC High Voltage Disconnect Switch
Fn5-12 Series Indoor AC Hv Load Switch-Fuse Combination Apparatus
24kv High Voltage Air Load Switch for Switchgear
Indoor Use Vacuum Load Switch with Fuse Holder
Fn7 Series Fuse Combination Indoor Load Break Switch for Switchgear
Popular Vacuum Load Switch Products
Fzrw32-24/630-200 Load Switch 24kv Isolating Vacuum Load Switch for Transformer
Fnl6a-12 Series 12kv Load Switch
Indoor High Voltage 12kv Fuse Combination Vacuum Load Switch Protection Device
Tags: cnville, Indoor AC Load Switch11kv for Breaking Load Current and Closing Short-Circuit Current, Load Switch, Vacuum Load Switch