ISO 9001 Certification XLPE Power Cable Cu (AL) /Xlp/Cts/Swa (STA) /PVC (PE)
ISO 9001 Certification XLPE Power Cable Cu (AL) /Xlp/Cts/Swa (STA) /PVC (PE) image
Get Latest Price Request a quote
- Overview
- Product Description
- Specification
- Company Profile
- Exhibition
- Packaging & Shipping
- FAQ
Basic Info.
Packaging & Delivery
Product Description
It is used to transmit and distribute power in power transmission and distribution system of 37kV or lower. It is generally applied to the fields including power, construction, mines, metallurgy, petrochemical indusry and communication in complete replace of oil immersed paper insulated power cable and in partial replace of PVC insulated power cable.
1. Rated voltage: Uo/U: 26/35kV, 21/35kV, 12/20 kV (24 kV), 8.7/10kV, 8.7/15kV, 6/6kV, 6/10kV.
2. No. of core: Single-core, Three-core.
3. The highest allowed operating temperature of conductor for long-term working is 90ºC. In short-circuit (Max. Long-term is no more than 5 seconds). The highest temperature for conductor is no more than 250ºC.
4. D.C Resistance of the conductor complies with the stipulations of GB/T3956-1997.
5. The environment temperature should be no lower than 0ºC when lay. Otherwise it should be preheated.
6. The cable is laid without horizontal drop limit. The Min. Bending radius of three-core cable should be no smaller than 12 times of cable outer diameter.
7. Working Frequency Voltage Test:.
For cable with Uo of 3.6kV or lower: 2.5Uo+2kV/5min without puncture.
For cable with Uo of 3.6Kv~18kV: 3.5Uo/5min without puncture.
For cable with Uo of 21kV and 26 kV: 2.5Uo/30min without puncture.
8. Partial Discharge Test: The discharge volume should be no more than 10pC under 1.73Uo for the cable.
| Type | Type | Name | No. of Cores | Nominal Cross-Section of Conductor(mm2) |
| Cu Core | Al Core | 1 | 1.5–1000 | |
| YJV (YJY) |
YJLV (YJLY) |
XLPE Insulated,PVC(PE) Sheathed Power Cable | 1 | 1.5–1000 |
| YJV22 (YJV23) |
YJLV22 (YJLY23) |
XLPE Insulated,Steel Tape Armoured,PVC(PE) Sheathed Power Cable | 2/3/4/5 | 1.5–400 |
| YJV32 (YJLV33) |
YJLV32 (YJLY33) |
XLPE Insulated,Fine Steel Wire Armoured,PVC(PE) Sheathed Power Cable | 2/3/4/5 | 1.5–400 |
| YJV42 (YJLV43) |
YJLV42 (YJLY43) |
XLPE Insulated,Thick Steel Wire Armoured,PVC(PE) Sheathed Power Cable | 2/3/4/5 | 1.5–400 |
| ZR-YJV (ZR-YJY) |
ZR-YJLV (ZR-YJLY) |
XLPE Insulated,PVC(PE) Sheathed Flame-retardant Power Cable | 2/3/4/5 | 1.5–400 |
| ZR-YJV22 (ZR-YJY23) |
ZR-YJLV22 (ZR-YJLY23) |
XLPE Insulated,Steel Tape Armoured,PVC(PE) Sheathed Flame-retardant Power Cable |
2/3/4/5 |
1.5–400 |
| ZR-YJV32 (ZR-YJY33) |
ZR-YJLV32 (ZR-YJLY33) |
XLPE Insulated,Fine Steel Wire Armoured,PVC(PE) Sheathed Flame-retardant Power Cable | 3+1/ 4+1/ 3+2 | 2.5–400 |
| ZR-YJV42 (ZR-YJY43) |
ZR-YJLV42 (ZR-YJLY43) |
XLPE Insulated,Thick Steel Wire Armoured,PVC(PE) Sheathed Flame-retardant Power Cable | 3+1/ 4+1/ 3+2 | 2.5–400 |
Specification
| 1)3.6/6(7.2)kV,3.6/6.6(7.2)kV,Three Cores,Al or Cu/XLPE/CTS/STA/PVC Armoured Power Cable | |||||||||
| No.X Nominal Cross Section of Conductor | Nominal Diameter of Conductor | Nominal Thickness of Insulation | Nominal Thickness of Copper Tape Screen | Nominal Thickness of Inner Sheath | Nominal Thickness of Steel Tape Armouring | Nominal Thickness of PVC Sheath | Approx. Overall Diameter | Approx. Weight | |
| Al Conductor | Cu Conductor | ||||||||
| No. X mm 2 | mm | mm | mm | mm | mm | mm | mm | kg/m | kg/m |
| 3 X 25 | 6 | 2.5 | 0.1 | 1.2 | 0.2 | 1.9 | 37.9 | 1.87 | 2.32 |
| 3 X 35 | 6.9 | 2.5 | 0.1 | 1.3 | 0.5 | 2 | 41.5 | 2.1 | 2.73 |
| 3 X50 | 8.2 | 2.5 | 0.1 | 1.3 | 0.5 | 2 | 44.3 | 2.37 | 3.22 |
| 3 X 70 | 9.7 | 2.5 | 0.1 | 1.4 | 0.5 | 2.1 | 47.9 | 2.77 | 4 |
| 3 X 95 | 11.3 | 2.5 | 0.1 | 1.4 | 0.5 | 2.2 | 51.6 | 3.21 | 4.91 |
| 3 X 120 | 12.8 | 2.5 | 0.1 | 1.5 | 0.5 | 2.4 | 55.4 | 3.69 | 5.84 |
| 3 X 150 | 14.2 | 2.5 | 0.1 | 1.5 | 0.5 | 2.5 | 58.6 | 4.15 | 6.85 |
| 3 X 185 | 15.9 | 2.5 | 0.1 | 1.5 | 0.5 | 2.6 | 62.5 | 4.73 | 8.11 |
| 3 X 240 | 18.3 | 2.6 | 0.1 | 1.6 | 0.5 | 2.7 | 68.5 | 5.62 | 10.05 |
| 3 X 300 | 20.4 | 2.8 | 0.1 | 1.7 | 0.5 | 2.9 | 74.5 | 6.55 | 12.11 |
| 3 X 400 | 23.2 | 3 | 0.1 | 1.9 | 0.8 | 3.2 | 83.6 | 8.78 | 15.86 |
| 3 X 500 | 26.4 | 3.2 | 0.1 | 2.1 | 0.8 | 3.4 | 93 | 10.52 | 18.85 |
| 2)6/10(12)kV,6.35/11(12)kV,,Three Cores,Al or Cu/XLPE/CTS/STA/PVC Armoured Power Cable | |||||||||
| No.X Nominal Cross Section of Conductor | Nominal Diameter of Conductor | Nominal Thickness of Insulation | Nominal Thickness of Copper Tape Screen | Nominal Thickness of Inner Sheath | Nominal Thickness of Steel Tape Armouring | Nominal Thickness of PVC Sheath | Approx. Overall Diameter | Approx. Weight | |
| Al Conductor | Cu Conductor | ||||||||
| No. X mm 2 | mm | mm | mm | mm | mm | mm | mm | kg/m | kg/m |
| 3 X 25 | 6 | 3.4 | 0.1 | 1.3 | 0.5 | 2 | 43.4 | 2.16 | 2.61 |
| 3 X 35 | 6.9 | 3.4 | 0.1 | 1.3 | 0.5 | 2 | 45.4 | 2.36 | 2.99 |
| 3 X50 | 8.2 | 3.4 | 0.1 | 1.4 | 0.5 | 2.2 | 48.8 | 2.69 | 3.54 |
| 3 X 70 | 9.7 | 3.4 | 0.1 | 1.5 | 0.5 | 2.3 | 52.4 | 3.1 | 4.33 |
| 3 X 95 | 11.3 | 3.4 | 0.1 | 1.5 | 0.5 | 2.4 | 56.1 | 3.56 | 5.26 |
| 3 X 120 | 12.8 | 3.4 | 0.1 | 1.5 | 0.5 | 2.5 | 59.5 | 4.04 | 6.19 |
| 3 X 150 | 14.2 | 3.4 | 0.1 | 1.5 | 0.5 | 2.6 | 62.7 | 4.49 | 7.19 |
| 3 X 185 | 15.9 | 3.4 | 0.1 | 1.6 | 0.5 | 2.6 | 66.6 | 5.12 | 8.49 |
| 3 X 240 | 18.3 | 3.4 | 0.1 | 1.7 | 0.5 | 2.8 | 72.4 | 5.99 | 10.42 |
| 3 X 300 | 20.4 | 3.4 | 0.1 | 1.8 | 0.5 | 3 | 77.5 | 6.86 | 12.42 |
| 3 X 400 | 23.2 | 3.4 | 0.1 | 1.9 | 0.8 | 3.2 | 85.4 | 8.97 | 16.05 |
| 3 X 500 | 26.4 | 3.4 | 0.1 | 2 | 0.8 | 3.4 | 93.7 | 10.65 | 19.5 |
| 3)8.7/10(15)kV,Three Cores,Al or Cu/XLPE/CTS/STA/PVC Armoured Power Cable | |||||||||
| No.X Nominal Cross Section of Conductor | Nominal Diameter of Conductor | Nominal Thickness of Insulation | Nominal Thickness of Copper Tape Screen | Nominal Thickness of Inner Sheath | Nominal Thickness of Steel Tape Armouring | Nominal Thickness of PVC Sheath | Approx. Overall Diameter | Approx. Weight | |
| Al Conductor | Cu Conductor | ||||||||
| No. X mm 2 | mm | mm | mm | mm | mm | mm | mm | kg/m | kg/m |
| 3 X 25 | 6 | 4.5 | 0.1 | 1.4 | 0.5 | 2.1 | 48.6 | 2.53 | 2.98 |
| 3 X 35 | 6.9 | 4.5 | 0.1 | 1.4 | 0.5 | 2.2 | 50.7 | 2.76 | 3.39 |
| 3 X50 | 8.2 | 4.5 | 0.1 | 1.5 | 0.5 | 2.3 | 53.9 | 3.1 | 3.95 |
| 3 X 70 | 9.7 | 4.5 | 0.1 | 1.5 | 0.5 | 2.4 | 57.4 | 3.51 | 4.74 |
| 3 X 95 | 11.3 | 4.5 | 0.1 | 1.5 | 0.5 | 2.6 | 61.2 | 4.05 | 5.75 |
| 3 X 120 | 12.8 | 4.5 | 0.1 | 1.6 | 0.5 | 2.6 | 64.7 | 4.56 | 6.72 |
| 3 X 150 | 14.2 | 4.5 | 0.1 | 1.6 | 0.5 | 2.7 | 67.9 | 5.04 | 7.74 |
| 3 X 185 | 15.9 | 4.5 | 0.1 | 1.7 | 0.5 | 2.8 | 71.9 | 5.66 | 9.04 |
| 3 X 240 | 18.3 | 4.5 | 0.1 | 1.8 | 0.5 | 3 | 77.7 | 6.56 | 11 |
| 3 X 300 | 20.4 | 4.5 | 0.1 | 1.9 | 0.8 | 3.2 | 84.1 | 8.39 | 13.96 |
| 3 X 400 | 23.2 | 4.5 | 0.1 | 2 | 0.8 | 3.3 | 90.5 | 9.71 | 16.79 |
| 3 X 500 | 26.4 | 4.5 | 0.1 | 2.1 | 0.8 | 3.5 | 98.8 | 11.45 | 20.57 |
| 4)12/20(24)kV, 12.7/22(24)kV,Three Cores,Al or Cu/XLPE/CTS/STA/PVC Armoured Power Cable | |||||||||
| No.X Nominal Cross Section of Conductor | Nominal Diameter of Conductor | Nominal Thickness of Insulation | Nominal Thickness of Copper Tape Screen | Nominal Thickness of Inner Sheath | Nominal Thickness of Steel Tape Armouring | Nominal Thickness of PVC Sheath | Approx. Overall Diameter | Approx. Weight | |
| Al Conductor | Cu Conductor | ||||||||
| No. X mm 2 | mm | mm | mm | mm | mm | mm | mm | kg/m | kg/m |
| 3 X 25 | |||||||||
| 3 X 35 | 6.9 | 5.5 | 0.1 | 1.5 | 0.5 | 2.4 | 55.6 | 3.14 | 3.77 |
| 3 X50 | 8.2 | 5.5 | 0.1 | 1.5 | 0.5 | 2.5 | 58.6 | 3.49 | 4.34 |
| 3 X 70 | 9.7 | 5.5 | 0.1 | 1.5 | 0.5 | 2.6 | 62.1 | 3.93 | 5.16 |
| 3 X 95 | 11.3 | 5.5 | 0.1 | 1.6 | 0.5 | 2.6 | 65.7 | 4.46 | 6.16 |
| 3 X 120 | 12.8 | 5.5 | 0.1 | 1.7 | 0.5 | 2.7 | 69.4 | 5 | 7.15 |
| 3 X 150 | 14.2 | 5.5 | 0.1 | 1.7 | 0.5 | 2.8 | 72.6 | 5.49 | 8.19 |
| 3 X 185 | 15.9 | 5.5 | 0.1 | 1.8 | 0.5 | 3 | 76.9 | 6.16 | 9.53 |
| 3 X 240 | 18.3 | 5.5 | 0.1 | 1.9 | 0.8 | 3.2 | 83.9 | 7.87 | 12.31 |
| 3 X 300 | 20.4 | 5.5 | 0.1 | 2 | 0.8 | 3.2 | 88.6 | 8.96 | 14.52 |
| 3 X 400 | 23.2 | 5.5 | 0.1 | 2.1 | 0.8 | 3.5 | 95.4 | 10.35 | 17.43 |
| 3 X 500 | 26.4 | 5.5 | 0.1 | 2.2 | 0.8 | 3.7 | 103.7 | 12.45 | 20.23 |
| 5)18/30(36)kV,19/33(36)kV,Three Cores,Al or Cu/XLPE/CTS/STA/PVC Armoured Power Cable | |||||||||
| No.X Nominal Cross Section of Conductor | Nominal Diameter of Conductor | Nominal Thickness of Insulation | Nominal Thickness of Copper Tape Screen | Nominal Thickness of Inner Sheath | Nominal Thickness of Steel Tape Armouring | Nominal Thickness of PVC Sheath | Approx. Overall Diameter | Approx. Weight | |
| Al Conductor | Cu Conductor | ||||||||
| No. X mm 2 | mm | mm | mm | mm | mm | mm | mm | kg/m | kg/m |
| 3 X 25 | |||||||||
| 3 X 35 | |||||||||
| 3 X50 | 8.2 | 8 | 0.1 | 1.7 | 0.5 | 2.8 | 70.4 | 4.56 | 5.41 |
| 3 X 70 | 9.7 | 8 | 0.1 | 1.7 | 0.5 | 2.9 | 73.9 | 5.04 | 6.26 |
| 3 X 95 | 11.3 | 8 | 0.1 | 1.8 | 0.5 | 3 | 77.7 | 5.62 | 7.32 |
| 3 X 120 | 12.8 | 8 | 0.1 | 1.9 | 0.8 | 3.2 | 82.8 | 6.99 | 9.15 |
| 3 X 150 | 14.2 | 8 | 0.1 | 1.9 | 0.8 | 3.2 | 85.8 | 7.56 | 10.26 |
| 3 X 185 | 15.9 | 8 | 0.1 | 2 | 0.8 | 3.3 | 89.9 | 8.3 | 11.67 |
| 3 X 240 | 18.3 | 8 | 0.1 | 2.1 | 0.8 | 3.5 | 95.7 | 9.36 | 13.79 |
| 3 X 300 | 20.4 | 8 | 0.1 | 2.2 | 0.8 | 3.6 | 100.6 | 10.51 | 16.07 |
| 3 X 400 | 23.2 | 8 | 0.1 | 2.3 | 0.8 | 3.8 | 107.2 | 11.99 | 19.07 |
| 3 X 500 | 26.4 | 8 | 0.1 | 2.4 | 0.8 | 4 | 120.1 | 14.15 | 23.85 |
Zhengzhou Jinshui Industry & Commerce Co.,Ltd is a professional cable manufacturer and exporter with more than 20 years experience, located in Zhengzhou, China. Products mainly include bare conductor, aerial bundled cable(ABC), building wire, XLPE insulated Power Cable, coaxial cable, etc. With high-quality products and professional service, we have gained the trust from many customers and established long-term business relationship with them. Products have been exported to more than 30 countries.
2. How can we guarantee quality?
/* January 22, 2024 19:08:37 */!function(){function s(e,r){var a,o={};try{e&&e.split(“,”).forEach(function(e,t){e&&(a=e.match(/(.*?):(.*)$/))&&1
We are China ISO 9001 Certification XLPE Power Cable Cu (AL) /Xlp/Cts/Swa (STA) /PVC (PE) manufacture and supplier,You can get more details with Email,you will get cheap price or factory price.
Get Latest Price Request a quote
Popular ISO 9001 Certification XLPE Power Cable Cu (AL) /Xlp/Cts/Swa (STA) /PVC (PE) Products
Popular jsgroup Products
ACSR 17/3 ASTM Overhead Bare Conductor
1.5mm 2.5mm Solid or Stranded Copper PVC House Wiring Electrical Wire
450/750V Copper Conductor PVC Insulated Wire
General Rubber Sheath Cable with High Quality
Power Cable 12kv 20kv Copper/Aluminum Conductor Yjv72 Yjlsv
0.6/1kv ABC Cable Aluminum Conductor PE/XLPE for Overhead Line
Popular XLPE Cable Products
Good Quality Cu/XLPE/PVC-0.6/1kv 3X120+2X70mm2 XLPE Insulated Power Cable
Xhhw/Xhhw-2 CT, Building Wire, 600V, Cu/XLPE (UL 44/CSA C22.2/ICEA S-95-658/NEMA WC70)
25kv Underground Aluminum/Copper XLPE Insulated Power Cable
600V 3*2 3*4 3*6 AWG XLPE Insulation Concentric Cable
AAC, ACSR, AAAC Messenger XLPE Insulation Power ABC Cable
AS/NZS Cables Wire Screend Copper Cable Asnzs Wires
Popular XLPE Copper Cable Products
Cu/XLPE/PVC/SWA/PVC 4X120 Sqmm 600/1000V Low Voltage Cables
0.6/1kv 4X25 mm2 Aluminum Low Voltage Cable XLPE Insulated Armoured Cable
Copper Conductor Copper Tape Screen XLPE Insulated 11kV Power Cable
0.6 / 1kv PVC Free Sample Fire Resistant Cable Coaxial Cable Price
Tags: ISO 9001 Certification XLPE Power Cable Cu (AL) /Xlp/Cts/Swa (STA) /PVC (PE), jsgroup, XLPE Cable, XLPE Copper Cable