Low Voltage ABC Aerial Bundled Cable (JKLYJ)

China 
                        Low Voltage ABC Aerial Bundled Cable (JKLYJ)
                      manufacture and supplier

Low Voltage ABC Aerial Bundled Cable (JKLYJ) image

Get Latest Price Request a quote

Quick Details

Low Voltage ABC Aerial Bundled Cable (JKLYJ)

JKLYJ

Henan Jiapu

ISO9001, CE, SABS

XLPE

PVC

Aluminum

Overhead

Stranded

Insulated

None

None

1-4 Cores

ASTM, BS, CSA, DIN

0.6/1kv,10kv

JIAPU

Wooden Drum

any one

Henan, China

4101962331

Product Details

Low Voltage ABC Aerial Bundled Cable (JKLYJ)

1. Features
RUS accepted.
Extruded ridges for easy Phase identification.

2. Standards
ICEA S-76-474
Neutral-Supported Power Cable Assemblies with Weather-Resistant Extruded Insulated rated 600V.

3. Application
For overhead distribution of electrical energy, such as a supply power, from pole-mounted transformer to the user’s service head where connection to the service entrance cable is made.
Also for temporary services and street light installations.

4. Specification
Maximum operating voltage: 600 volts, Maximum conductor operation temperatures:
Wet and dry locations:
Normal: 90° C
Emergency: 130° C
Short Circuit: 250° C

5. Engineering Information
Conductor: Aluminum alloy 1350-H19, solid conductor per ASTM B230, Compressed Class B stranding, or Class A stranding or unilay-compressed per ASTM B231, or combination unilay (19 wires)Per ASTM B786. Upon Request: Copper Conductors.
Separator: Suitable opaque tape as required.
Insulation: Black thermoset croos-linked polyethylene (XLPE). Upon request: PE insulated.
Neutral: Bare aluminum alloy 1350-H19 classes A stranding per ASTM B231 or ACSR stranding per ASTN B232, or ACSR/AW per ASTM B549. Upon request cover neutral.
Conductor Phase ID: Extruded ridges.
Duplex: Consist of one black phase insulated conductor twisted around a bare neutral conductor

Specification:

(1)Self-supporting

Phase Phase Phase Approx.Overall Diameter Max. D.C. Resistance of Conductor at 20ºC
AAC+UV-XLPE Compact Conductor UV-XLPE Insulation
No.X Normal Cross Section of Cores No.of Al Wires Overall Diameter Normal Thickness Min. Diameter
No. X mm2 mm mm mm mm mm ohm/km
1 X 10 7 4.05 1.0 0.8 6.05 6.05 3.08
1 X 16 7 4.8 1.2 0.98 7.2 7.20 1.91
1 X 25 7 6 1.2 0.98 8.4 8.40 1.20
1 X 35 7 7.0 1.4 1.16 9.8 9.80 0.868
1 X 50 7 8.3 1.4 1.16 11.1 11.10 0.641
1 X 70 19 9.8 1.4 1.16 12.6 12.60 0.443
1 X 95 19 11.6 1.6 1.34 14.8 14.80 0.320
1 X 120 19 13 1.6 1.34 16.2 16.20 0.253
1 X 150 19 14.6 1.8 1.52 18.2 18.20 0.206
1 X 185 36 16.2 2.0 1.70 20.2 20.20 0.164
1 X 240 36 18.4 2.2 1.88 22.8 22.80 0.125
2 X 10 7 4.05 1.0 0.8 6.05 12.10 3.08
2 X 16 7 4.8 1.2 0.98 7.2 14.40 1.91
2 X 25 7 6 1.2 0.98 8.4 16.80 1.20
2 X 35 7 7.0 1.4 1.16 9.8 19.60 0.868
2 X 50 7 8.3 1.4 1.16 11.1 22.20 0.641
2 X 70 19 9.8 1.4 1.16 12.6 25.20 0.443
2 X 95 19 11.6 1.6 1.34 14.8 29.60 0.320
2 X 120 19 13 1.6 1.34 16.2 32.40 0.253
2 X 150 19 14.6 1.8 1.52 18.2 36.40 0.206
2 X 185 36 16.2 2.0 1.70 20.2 40.40 0.164
2 X 240 36 18.4 2.2 1.88 22.8 45.60 0.125
3 X 10 7 4.05 1.0 0.8 6.05 13.07 3.08
3 X 16 7 4.8 1.2 0.98 7.2 15.55 1.91
3 X 25 7 6 1.2 0.98 8.4 18.14 1.20
3 X 35 7 7.0 1.4 1.16 9.8 21.17 0.868
3 X 50 7 8.3 1.4 1.16 11.1 23.98 0.641
3 X 70 19 9.8 1.4 1.16 12.6 27.22 0.443
3 X 95 19 11.6 1.6 1.34 14.8 31.97 0.320
3 X 120 19 13 1.6 1.34 16.2 34.99 0.253
3 X 150 19 14.6 1.8 1.52 18.2 39.31 0.206
3 X 185 36 16.2 2.0 1.70 20.2 43.63 0.164
3 X 240 36 18.4 2.2 1.88 22.8 49.25 0.125
4 X 10 7 4.05 1.0 0.8 6.05 14.64 3.08
4 X 16 7 4.8 1.2 0.98 7.2 17.42 1.91
4 X 25 7 6 1.2 0.98 8.4 20.33 1.20
4 X 35 7 7.0 1.4 1.16 9.8 23.72 0.868
4 X 50 7 8.3 1.4 1.16 11.1 26.86 0.641
4 X 70 19 9.8 1.4 1.16 12.6 30.49 0.443
4 X 95 19 11.6 1.6 1.34 14.8 35.82 0.320
4 X 120 19 13 1.6 1.34 16.2 39.20 0.253
4 X 150 19 14.6 1.8 1.52 18.2 44.04 0.206
4 X 185 36 16.2 2.0 1.70 20.2 48.88 0.164
4 X 240 36 18.4 2.2 1.88 22.8 55.18 0.125

(2) Phase + Neutral

Phase Neutral Phase Neutral Approx.Overall Diameter Max. D.C. Resistance of Conductor at 20ºC
AAC+UV-XLPE AAAC Compact Conductor UV-XLPE Insulation Conductor
Phase Neutral
No.X Normal Cross Section of Cores No.X Normal Cross Section of Cores No.of Al.Wire Overall Dia. Normal Thickness Min. No./Dia. of Al Alloy Wire
No. X mm2 No. X mm2 mm   mm Min. No./mm    mm ohm/km ohm/km
1 X 16 1 X 16 7 4.8 1.2 0.98 7/1.70 12.30 1.91 2.217
1 X 25 1 X 25 7 6 1.2 0.98 7/2.10 14.70 1.20 1.393
1 X 35 1 X 35 7 7.0 1.4 1.16 7/2.50 17.30 0.868 1.007
1 X 50 1 X 50 7 8.3 1.4 1.16 7/3.00 20.10 0.641 0.744
1 X 70 1 X 70 19 9.8 1.4 1.16 7/3.50 23.10 0.443 0.514
1 X 95 1 X 95 19 11.6 1.6 1.34 19/2.50 27.30 0.320 0.371
1 X 120 1 X 120 19 13 1.6 1.34 19/2.80 30.20 0.253 0.294
1 X 150 1 X 150 19 14.6 1.8 1.52 37/2.25 33.95 0.206 0.239
1 X 185 1 X 185 36 16.2 2.0 1.70 37/2.50 37.70 0.164 0.190
1 X 240 1 X 240 36 18.4 2.2 1.88 61/2.25 43.05 0.125 0.145
2 X 16 1 X 16 7 4.8 1.2 0.98 7/1.70 14.04 1.91 2.217
2 X 25 1 X 25 7 6 1.2 0.98 7/2.10 16.63 1.20 1.393
2 X 35 1 X 35 7 7.0 1.4 1.16 7/2.50 19.51 0.868 1.007
2 X 50 1 X 50 7 8.3 1.4 1.16 7/3.00 22.46 0.641 0.744
2 X 70 1 X 70 19 9.8 1.4 1.16 7/3.50 25.70 0.443 0.514
2 X 95 1 X 95 19 11.6 1.6 1.34 19/2.50 30.31 0.320 0.371
2 X 120 1 X 120 19 13 1.6 1.34 19/2.80 33.41 0.253 0.294
2 X 150 1 X 150 19 14.6 1.8 1.52 37/2.25 37.55 0.206 0.239
2 X 185 1 X 185 36 16.2 2.0 1.70 37/2.50 41.69 0.164 0.190
2 X 240 1 X 240 36 18.4 2.2 1.88 61/2.25 47.41 0.125 0.145
3 X 16 1 X 16 7 4.8 1.2 0.98 7/1.70 16.15 1.91 2.217
3 X 25 1 X 25 7 6 1.2 0.98 7/2.10 19.06 1.20 1.393
3 X 35 1 X 35 7 7.0 1.4 1.16 7/2.50 22.32 0.868 1.007
3 X 50 1 X 50 7 8.3 1.4 1.16 7/3.00 25.59 0.641 0.744
3 X 70 1 X 70 19 9.8 1.4 1.16 7/3.50 29.22 0.443 0.514
3 X 95 1 X 95 19 11.6 1.6 1.34 19/2.50 34.42 0.320 0.371
3 X 120 1 X 120 19 13 1.6 1.34 19/2.80 37.87 0.253 0.294
3 X 150 1 X 150 19 14.6 1.8 1.52 37/2.25 42.56 0.206 0.239
3 X 185 1 X 185 36 16.2 2.0 1.70 37/2.50 47.25 0.164 0.190
3 X 240 1 X 240 36 18.4 2.2 1.88 61/2.25 53.63 0.125 0.145

(3) Phase + Neutral + Service Connection

Phase Neutral Service Connection Phase Neutral   Service Connection Approx.Overall Diameter of Bundled Cable
AAC+UV-XLPE AAAC+UV-XLPE AAC+UV-XLPE Conductor UV-XLPE Conductor UV-XLPE Compact Conductor UV-XLPE
No.X Normal Cross Section of Cores No.X Normal Cross Section of Cores No.X Normal Cross Section of Cores No. of Al. Wire Overall Dia. Normal
Thickness
No./Dia. of Al. Wire Normal
Thickness
No. of Al. Wire Overall Dia. Normal
Thickness
No. X mm2 No. X mm2 No. X mm2 mm mm mm mm No./mm mm mm mm
3 X 16 1 X 50 1 X 16 7 4.8 1.2 7/3.0 1.4 7 4.8 1.2 26.2
3 X 25 1 X 50 1 X 16 7 6 1.2 7/3.0 1.4 7 4.8 1.2 28.6
3 X 35 1 X 50 1 X 16 7 7.0 1.4 7/3.0 1.4 7 4.8 1.2 31.4
3 X 50 1 X 50 1 X 16 7 8.3 1.4 7/3.0 1.4 7 4.8 1.2 34
3 X 70 1 X 50 1 X 16 19 9.8 1.4 7/3.0 1.4 7 4.8 1.2 37
3 X 95 1 X 50 1 X 16 19 11.6 1.6 7/3.0 1.4 7 4.8 1.2 41.4
3 X 120 1 X 50 1 X 16 19 13 1.6 7/3.0 1.4 7 4.8 1.2 44.2
3 X 16 1 X 50 2 X 16 7 4.8 1.2 7/3.0 1.4 7 4.8 1.2 26.2
3 X 25 1 X 50 2 X 16 7 6 1.2 7/3.0 1.4 7 4.8 1.2 28.6
3 X 35 1 X 50 2 X 16 7 7.0 1.4 7/3.0 1.4 7 4.8 1.2 31.4
3 X 50 1 X 50 2 X 16 7 8.3 1.4 7/3.0 1.4 7 4.8 1.2 34
3 X 70 1 X 50 2 X 16 19 9.8 1.4 7/3.0 1.4 7 4.8 1.2 37
3 X 95 1 X 50 2 X 16 19 11.6 1.6 7/3.0 1.4 7 4.8 1.2 41.4
3 X 120 1 X 50 2 X 16 19 13 1.6 7/3.0 1.4 7 4.8 1.2 44.2

We are China Low Voltage ABC Aerial Bundled Cable (JKLYJ) manufacture and supplier,You can get more details with Email,you will get cheap price or factory price.

Get Latest Price Request a quote

Popular ABC Cable Products

ABC Cable 2X2/0AWG+2/0AWG Bare AAAC Messenger Icea S76-474

Best Price ABC Cable XLPE Insulation 4*16 Cable

ABC Cable Alumium Boundled Cable for Power Supply

Medium Voltage ASTM Standard Overhead Cable Aluminum Conductor Aerial Bundle Cable

Triplex Service Drop ACSR Neutral Conductor Whelk

Factory Price Aluminium Conductor Duplex/Triplex/Quadruplex Service Drop ABC Cable

Popular Aerial Cable Products

Hot Selling Cable Aluminium Core XLPE Insulation ABC Cable

35kv Composite Conductor XLPE Insulation Power Cable

Low Voltage Caai with / Without XLPE Insulated Public Lighting and Al Alloy Messenger Overhead Aerial Cable

0.6/1kv ABC Cable Aluminum Wire

Aluminium Overhead Cable Duplex Service Drop

Aluminum Cable Used for Aerial

Popular jpcable99 Products

0.6/1kv Low Voltage Copper Conductor Power Cable PVC Cable

33kv Aluminium Conductor ABC Aerial Bundled Cable

Medium Voltage XLPE Insulated Steel Wire Armoured Power Cable.

ABC (Aerial Bundle Cable) with Duplex/Triplex/Quadruplex Service Drop- Aluminum Conductor.

High Quality 1/11kv XLPE Insulated Steel Wire Armoured Cable

Overhead Conductor

Popular Low Voltage Aerial Bundle Cable Products

Low Voltage ABC Aerial Bundled Power Cable

Low Voltage Aerial Bundle Cable (ABC kable) 2/3/4/5/6 Cores Aluminium

Tags: , , ,