Medium Voltage, Copper/Aluminium Conductor, Cross Linked Polyethylene Insulated PVC Sheathed Power Cable Wire.
Medium Voltage, Copper/Aluminium Conductor, Cross Linked Polyethylene Insulated PVC Sheathed Power Cable Wire. image
Get Latest Price Request a quote
Quick Details
Product Details
Certificate: ISO 9001
Supply Ability: 3000km/Month
Packaging Details: Wood-metal Drum or Metal Drum.
Port: Qingdao / Tianjin/ Ningbo / Shanghai
Application
Media Voltage XLPE Insulated power cable is used to transmit and distribute power in power transmission and distribution system of 35kV or lower. It is generally applied to the fields including power, construction, mines, metallurgy, petrochemical industry and communication in complete replace of oil immersed paper insulated power cable.
Structure
Medium Voltage Power Cable consists of Aluminum or Copper Core, XLPE Insulation, Metal armor (Steel Tape, Steel wire) or no-armor, XLPE Sheath.
Standard
IEC60502,designing and manufacturing special power cable according to the other standards required by the customers.
1)3.6/6(7.2)kV,3.6/6.6(7.2)kV,Three Cores,Al or Cu/XLPE/CTS/STA/PVC Armoured Power Cable
No.X Nominal Cross Section of Conductor | Nominal Diameter of Conductor | Nominal Thickness of Insulation | Nominal Thickness of Copper Tape Screen | Nominal Thickness of Inner Sheath | Nominal Thickness of Steel Tape Armouring | Nominal Thickness of PVC Sheath | Approx. Overall Diameter | Approx. Weight | |
Al Conductor | Cu Conductor | ||||||||
No. X mm2 | mm | mm | mm | mm | mm | mm | mm | kg/m | kg/m |
3 X 25 | 6.0 | 2.5 | 0.1 | 1.2 | 0.2 | 1.9 | 37.9 | 1.87 | 2.32 |
3 X 35 | 6.9 | 2.5 | 0.1 | 1.3 | 0.5 | 2.0 | 41.5 | 2.10 | 2.73 |
3 X50 | 8.2 | 2.5 | 0.1 | 1.3 | 0.5 | 2.0 | 44.3 | 2.37 | 3.22 |
3 X 70 | 9.7 | 2.5 | 0.1 | 1.4 | 0.5 | 2.1 | 47.9 | 2.77 | 4.00 |
3 X 95 | 11.3 | 2.5 | 0.1 | 1.4 | 0.5 | 2.2 | 51.6 | 3.21 | 4.91 |
3 X 120 | 12.8 | 2.5 | 0.1 | 1.5 | 0.5 | 2.4 | 55.4 | 3.69 | 5.84 |
3 X 150 | 14.2 | 2.5 | 0.1 | 1.5 | 0.5 | 2.5 | 58.6 | 4.15 | 6.85 |
3 X 185 | 15.9 | 2.5 | 0.1 | 1.5 | 0.5 | 2.6 | 62.5 | 4.73 | 8.11 |
3 X 240 | 18.3 | 2.6 | 0.1 | 1.6 | 0.5 | 2.7 | 68.5 | 5.62 | 10.05 |
3 X 300 | 20.4 | 2.8 | 0.1 | 1.7 | 0.5 | 2.9 | 74.5 | 6.55 | 12.11 |
3 X 400 | 23.2 | 3.0 | 0.1 | 1.9 | 0.8 | 3.2 | 83.6 | 8.78 | 15.86 |
3 X 500 | 26.4 | 3.2 | 0.1 | 2.1 | 0.8 | 3.4 | 93.0 | 10.52 | 18.85 |
2)6/10(12)kV,6.35/11(12)kV,,Three Cores,Al or Cu/XLPE/CTS/STA/PVC Armoured Power Cable
No.X Nominal Cross Section of Conductor | Nominal Diameter of Conductor | Nominal Thickness of Insulation | Nominal Thickness of Copper Tape Screen | Nominal Thickness of Inner Sheath | Nominal Thickness of Steel Tape Armouring | Nominal Thickness of PVC Sheath | Approx. Overall Diameter | Approx. Weight | |
Al Conductor | Cu Conductor | ||||||||
No. X mm2 | mm | mm | mm | mm | mm | mm | mm | kg/m | kg/m |
3 X 25 | 6.0 | 3.4 | 0.1 | 1.3 | 0.5 | 2.0 | 43.4 | 2.16 | 2.61 |
3 X 35 | 6.9 | 3.4 | 0.1 | 1.3 | 0.5 | 2.0 | 45.4 | 2.36 | 2.99 |
3 X50 | 8.2 | 3.4 | 0.1 | 1.4 | 0.5 | 2.2 | 48.8 | 2.69 | 3.54 |
3 X 70 | 9.7 | 3.4 | 0.1 | 1.5 | 0.5 | 2.3 | 52.4 | 3.10 | 4.33 |
3 X 95 | 11.3 | 3.4 | 0.1 | 1.5 | 0.5 | 2.4 | 56.1 | 3.56 | 5.26 |
3 X 120 | 12.8 | 3.4 | 0.1 | 1.5 | 0.5 | 2.5 | 59.5 | 4.04 | 6.19 |
3 X 150 | 14.2 | 3.4 | 0.1 | 1.5 | 0.5 | 2.6 | 62.7 | 4.49 | 7.19 |
3 X 185 | 15.9 | 3.4 | 0.1 | 1.6 | 0.5 | 2.6 | 66.6 | 5.12 | 8.49 |
3 X 240 | 18.3 | 3.4 | 0.1 | 1.7 | 0.5 | 2.8 | 72.4 | 5.99 | 10.42 |
3 X 300 | 20.4 | 3.4 | 0.1 | 1.8 | 0.5 | 3.0 | 77.5 | 6.86 | 12.42 |
3 X 400 | 23.2 | 3.4 | 0.1 | 1.9 | 0.8 | 3.2 | 85.4 | 8.97 | 16.05 |
3 X 500 | 26.4 | 3.4 | 0.1 | 2.0 | 0.8 | 3.4 | 93.7 | 10.65 | 19.50 |
3)8.7/10(15)kV,Three Cores,Al or Cu/XLPE/CTS/STA/PVC Armoured Power Cable
No.X Nominal Cross Section of Conductor | Nominal Diameter of Conductor | Nominal Thickness of Insulation | Nominal Thickness of Copper Tape Screen | Nominal Thickness of Inner Sheath | Nominal Thickness of Steel Tape Armouring | Nominal Thickness of PVC Sheath | Approx. Overall Diameter | Approx. Weight | |
Al Conductor | Cu Conductor | ||||||||
No. X mm2 | mm | mm | mm | mm | mm | mm | mm | kg/m | kg/m |
3 X 25 | 6.0 | 4.5 | 0.1 | 1.4 | 0.5 | 2.1 | 48.6 | 2.53 | 2.98 |
3 X 35 | 6.9 | 4.5 | 0.1 | 1.4 | 0.5 | 2.2 | 50.7 | 2.76 | 3.39 |
3 X50 | 8.2 | 4.5 | 0.1 | 1.5 | 0.5 | 2.3 | 53.9 | 3.10 | 3.95 |
3 X 70 | 9.7 | 4.5 | 0.1 | 1.5 | 0.5 | 2.4 | 57.4 | 3.51 | 4.74 |
3 X 95 | 11.3 | 4.5 | 0.1 | 1.5 | 0.5 | 2.6 | 61.2 | 4.05 | 5.75 |
3 X 120 | 12.8 | 4.5 | 0.1 | 1.6 | 0.5 | 2.6 | 64.7 | 4.56 | 6.72 |
3 X 150 | 14.2 | 4.5 | 0.1 | 1.6 | 0.5 | 2.7 | 67.9 | 5.04 | 7.74 |
3 X 185 | 15.9 | 4.5 | 0.1 | 1.7 | 0.5 | 2.8 | 71.9 | 5.66 | 9.04 |
3 X 240 | 18.3 | 4.5 | 0.1 | 1.8 | 0.5 | 3.0 | 77.7 | 6.56 | 11.00 |
3 X 300 | 20.4 | 4.5 | 0.1 | 1.9 | 0.8 | 3.2 | 84.1 | 8.39 | 13.96 |
3 X 400 | 23.2 | 4.5 | 0.1 | 2.0 | 0.8 | 3.3 | 90.5 | 9.71 | 16.79 |
3 X 500 | 26.4 | 4.5 | 0.1 | 2.1 | 0.8 | 3.5 | 98.8 | 11.45 | 20.57 |
4)12/20(24)kV, 12.7/22(24)kV,Three Cores,Al or Cu/XLPE/CTS/STA/PVC Armoured Power Cable
No.X Nominal Cross Section of Conductor | Nominal Diameter of Conductor | Nominal Thickness of Insulation | Nominal Thickness of Copper Tape Screen | Nominal Thickness of Inner Sheath | Nominal Thickness of Steel Tape Armouring | Nominal Thickness of PVC Sheath | Approx. Overall Diameter | Approx. Weight | |
Al Conductor | Cu Conductor | ||||||||
No. X mm2 | mm | mm | mm | mm | mm | mm | mm | kg/m | kg/m |
3 X 25 | |||||||||
3 X 35 | 6.9 | 5.5 | 0.1 | 1.5 | 0.5 | 2.4 | 55.6 | 3.14 | 3.77 |
3 X50 | 8.2 | 5.5 | 0.1 | 1.5 | 0.5 | 2.5 | 58.6 | 3.49 | 4.34 |
3 X 70 | 9.7 | 5.5 | 0.1 | 1.5 | 0.5 | 2.6 | 62.1 | 3.93 | 5.16 |
3 X 95 | 11.3 | 5.5 | 0.1 | 1.6 | 0.5 | 2.6 | 65.7 | 4.46 | 6.16 |
3 X 120 | 12.8 | 5.5 | 0.1 | 1.7 | 0.5 | 2.7 | 69.4 | 5.00 | 7.15 |
3 X 150 | 14.2 | 5.5 | 0.1 | 1.7 | 0.5 | 2.8 | 72.6 | 5.49 | 8.19 |
3 X 185 | 15.9 | 5.5 | 0.1 | 1.8 | 0.5 | 3.0 | 76.9 | 6.16 | 9.53 |
3 X 240 | 18.3 | 5.5 | 0.1 | 1.9 | 0.8 | 3.2 | 83.9 | 7.87 | 12.31 |
3 X 300 | 20.4 | 5.5 | 0.1 | 2.0 | 0.8 | 3.2 | 88.6 | 8.96 | 14.52 |
3 X 400 | 23.2 | 5.5 | 0.1 | 2.1 | 0.8 | 3.5 | 95.4 | 10.35 | 17.43 |
3 X 500 | 26.4 | 5.5 | 0.1 | 2.2 | 0.8 | 3.7 | 103.7 | 12.45 | 20.23 |
5)18/30(36)kV,19/33(36)kV,Three Cores,Al or Cu/XLPE/CTS/STA/PVC Armoured Power Cable
No.X Nominal Cross Section of Conductor | Nominal Diameter of Conductor | Nominal Thickness of Insulation | Nominal Thickness of Copper Tape Screen | Nominal Thickness of Inner Sheath | Nominal Thickness of Steel Tape Armouring | Nominal Thickness of PVC Sheath | Approx. Overall Diameter | Approx. Weight | |
Al Conductor | Cu Conductor | ||||||||
No. X mm2 | mm | mm | mm | mm | mm | mm | mm | kg/m | kg/m |
3 X 25 | |||||||||
3 X 35 | |||||||||
3 X50 | 8.2 | 8.0 | 0.1 | 1.7 | 0.5 | 2.8 | 70.4 | 4.56 | 5.41 |
3 X 70 | 9.7 | 8.0 | 0.1 | 1.7 | 0.5 | 2.9 | 73.9 | 5.04 | 6.26 |
3 X 95 | 11.3 | 8.0 | 0.1 | 1.8 | 0.5 | 3.0 | 77.7 | 5.62 | 7.32 |
3 X 120 | 12.8 | 8.0 | 0.1 | 1.9 | 0.8 | 3.2 | 82.8 | 6.99 | 9.15 |
3 X 150 | 14.2 | 8.0 | 0.1 | 1.9 | 0.8 | 3.2 | 85.8 | 7.56 | 10.26 |
3 X 185 | 15.9 | 8.0 | 0.1 | 2.0 | 0.8 | 3.3 | 89.9 | 8.30 | 11.67 |
3 X 240 | 18.3 | 8.0 | 0.1 | 2.1 | 0.8 | 3.5 | 95.7 | 9.36 | 13.79 |
3 X 300 | 20.4 | 8.0 | 0.1 | 2.2 | 0.8 | 3.6 | 100.6 | 10.51 | 16.07 |
3 X 400 | 23.2 | 8.0 | 0.1 | 2.3 | 0.8 | 3.8 | 107.2 | 11.99 | 19.07 |
3 X 500 | 26.4 | 8.0 | 0.1 | 2.4 | 0.8 | 4.0 | 120.1 | 14.15 | 23.85 |
We are China Medium Voltage, Copper/Aluminium Conductor, Cross Linked Polyethylene Insulated PVC Sheathed Power Cable Wire. manufacture and supplier,You can get more details with Email,you will get cheap price or factory price.
Get Latest Price Request a quote
Popular huatongcable Products
Rubber Insulated Flexible Copper Welding Cable
UL Telephone Central Office Power Cable Sunlight Resistant
Aluminium Conductor Steel Supported Acss ASTM B856 for Overhead Distribution and Transmission Lines
ACSR Cable Bare Aluminium Stranded Conductor for Power Transmission
4 Core Cu/XLPE/Swa/PVC Underground Armoured Power Cable Size
Overhead Triplex Service Drop Fusus Aerial Bundled Cable for Transmission Line
Popular Power Cable Products
LV XLPE or PVC Power Cable 3X150+70sqmm
0.6/1kv Copper Conductor XLPE Insulated PVC Sheathed Power Cable
IEC BS Standard 0.6/1kv Cu/XLPE/PVC/Swa/PVC Power Cables
Low Voltage Aluminum Core Crosslinked Polyethylene Insulated PVC Sheathed Power Cable
PVC Sheath Copper Kvvr Control Cable
Yy PVC Control Cable, 300/500 V, Flexible Cu/PVC/PVC (BS 6500)
Popular Swa Products
3Cx185mm2 XLPE Insulated Copper Tape Screened Galvanized Steel Wire Armored Power Cable 33kV
3Cx300sq.mm 33kV CU/XLPE/SWA/PVC Copper Armoured MV Underground Power Cable for 33/11kV Substation
3Cx70sq.mm 11kV CU/XLPE/PVC Copper Insulated MV Underground Power Cable for 33/11kV Substation
IEC60502-2 XLPE Insualted Armoured Underground 6/10kv Copper Cable 3X35mm2
IEC60502-2 XLPE Insualted Armoured Underground 12/20kv Copper Cable 3X25mm2
Popular XLPE Insulation Products
Mv 6kv Copper Conductor XLPE Insulated Armoured Power Cable
5~46kv XLPE Insulated Power Cable Three Core XLPE Insulation Power Cable
35kv Shielded Powercable for Use in Thetransmission Anddistribution of Electricenergy
XLPE Insulation Steel Tape Armor Power Cable
10mm2 Service Cable Solid Aluminum Cable with Copper Pilot Wires
10kv Aluminum Conductor XLPE Insulation Aluminum Tape Screen ABC Cable
Tags: huatongcable, Power Cable, Swa, XLPE Insulation