Mv Distribution Line Aerial Bundled Conductor ABC Overhead Cables

China 
                        Mv Distribution Line Aerial Bundled Conductor ABC Overhead Cables
                      manufacture and supplier

Mv Distribution Line Aerial Bundled Conductor ABC Overhead Cables image

Get Latest Price Request a quote

Quick Details

Mv Distribution Line Aerial Bundled Conductor ABC Overhead Cables

4x50Sqmm

Jytop

ISO9001, CE, CCC, VDE

Overhead

Round Wire

XLPE or PE or PVC

HDPE

Aluminum

Overhead

Stranded

Insulated

IEC, ASTM, Sans, AS/NZS, Icea…

Duplex, Triplex, Quadruplex, Multiplex

AAC ACSR AAAC

AAC

Coil, Wooden Drum, Customized

jytop

Packed in 500m Coils or in Wooden Reels

4x35mm2

Zhengzhou, China

8544492100

Product Details

Mv Distribution Line Aerial Bundled Conductor ABC Overhead Cables 

MV Aerial Bundled Conductor ABC Cables Standards:
IEC 60502 / AS/NZS 3599-1 standards
MV Aerial Bundled Conductor ABC Cables Constructions:

Conductor: Round, Aluminium Conductor
Conductor Screen: Extruded semi-conductive layer.
Insulation:  XLPE
insulation Screen: Extruded semi-conductive layer.
metallic Screen(optional): Copper wire screen or copper tape screen.
Separator: Semi-conductive swellable tape.
outer Sheath: HDPE.
Messager wire: Galvanized steel wires.
Assembly: Three XLPE insulated screened cores are bundled around the galvanized steel
wires in a right hand lay.
MV Aerial Bundled Conductor ABC Cables Application:
Aerial bundled cables are mainly used for secondary overhead lines on poles or as feeders
to residential premises.
The Function of messenger wire:
A) It acts as load bearing wire.    B) It acts as earth or neutral conductor
MV Aerial Bundled Conductor ABC Cables Specifications: 
AS/NZS 3599 Part 1 6.35/11 kV AL/XLPE /CWS/HDPE Screened Cables

Application
The cables are designed for aerial power lines with rated voltage Uo(Um) 10(12) kV ~35(40.5)kV.

Product properties and range 
* Rated voltage is 10kV and 35KV
* No. of cores :  1 ,  Nominal cross-section(mm2): 16~300
* Max.Continuous permissive working temperature of conductor:
XLPE insulation should be not more than 90ºC.
*Max. Temperature at short circuit (the longest continuous time is not more than 5S) XLPE insulation is 250ºC.
* Installation temperature of cable should be not less than -20ºC.
*  Permissive bending radius of cable should be not less than 20(D+d) mm.
D -the actual overall diameter of cable ,mm;
d-the actual overall diameter of conductor ,mm.
* Insulation resistance of common insulation construction of aerial cable should be not less than 1500MΩ km, and insulation 
resistance of thin XLPE insulated construction of light aerial cable should be not less than 1000mΩ km.

parameter of abc cable

Number of CoresxNominal Cross Section Phase Conductor Messenger Suspension Unit Continuous current rating at 30ºCambient temp
Stranding Nominal Sectional Area Maximum Conductor Resistance Stranding Nominal Sectional Area Breaking Load
No.×mm2 mm mm mm mm No.×mm mm2 KN
3×35 6.9 3.4 0.8 1.2 7/4.75 52.4 1370
3×50 8.1 3.4 0.8 1.2 7/4.75 54.6 1530
3×70 9.7 3.4 0.8 1.2 7/4.75 57.8 1790
3×95 11.4 3.4 0.8 1.2 7/4.75 61.3 2100
3×120 12.8 3.4 0.8 1.2 19/3.50 67.3 2540
3×150 14.2 3.4 0.8 1.2 19/3.50 70.1 2840
3×185 15.7 3.4 0.8 1.2 19/3.50 73.1 3190

AS/NZS 3599 Part 1 12.7/22 kV AL/XLPE /HDPE Non-screened Cables

Number of CoresxNominal Cross Section Diameter of Conductor Thickness of Insulation Thickness of Insulation Screen Thickness of Sheath Messenger Suspension Unit Stranding Nominal Sectional Area Breaking Load
No.×mm2 mm mm mm mm No.×mm mm2 KN
3×35 6.9 5.5 0.8 1.2 7/4.75 61 1780
3×50 8.1 5.5 0.8 1.2 7/4.75 63.3 1970
3×70 9.7 5.5 0.8 1.2 7/4.75 66.5 2260
3×95 11.4 5.5 0.8 1.2 7/4.75 69.9 2600
3×120 12.8 5.5 0.8 1.2 19/3.50 75.9 3070
3×150 14.2 5.5 0.8 1.2 19/3.50 78.7 3390
3×185 15.7 5.5 0.8 1.2 19/3.50 81.7 3760

AS/NZS 3599 Part 1 12.7/22 kV AL/XLPE /CWS/HDPE Screened Cables

Number of CoresxNominal Cross Section Diameter of Conductor Thickness of Insulation Thickness of Insulation Screen Copper Wire Screen Stranding Thickness of Sheath Galvanized Steel Wire Stranding Nominal Sectional Area Breaking Load
No.×mm2 mm mm mm No.×mm mm No.×mm mm2 KN
No.×mm2 mm mm mm No.×mm mm No.×mm mm2 KN
Light Duty Screen
3×35 6.9 5.5 0.8 25/0.85 1.8 7/2.00 62.7 2280
3×35 6.9 5.5 0.8 25/0.85 1.8 19/2.00 66.7 2580
3×50 8.1 5.5 0.8 25/0.85 1.8 19/2.00 69 2780
3×70 9.7 5.5 0.8 25/0.85 1.9 19/2.00 72.6 3110
3×95 11.4 5.5 0.8 25/0.85 1.9 19/2.00 76 3460
3×120 12.8 5.5 0.8 25/0.85 2 19/2.00 79.2 3810
3×150 14.2 5.5 1 25/0.85 2 19/2.00 82.8 4230
3×185 15.7 5.5 1 25/0.85 2.1 19/2.00 86.2 4650
Heavy Duty Screen
3×35 6.9 5.5 0.8 40/0.85 1.8 7/2.00 62.7 2510
3×35 6.9 5.5 0.8 40/0.85 1.8 19/2.00 66.7 2810
3×50 8.1 5.5 0.8 23/1.35 1.8 19/2.00 71 3300
3×70 9.7 5.5 0.8 32/1.35 1.9 19/2.00 74.6 3970
3×95 11.4 5.5 0.8 39/1.35 1.9 19/2.00 78 4600
3×120 12.8 5.5 0.8 39/1.35 2 19/2.00 81.2 4950
3×150 14.2 5.5 1 39/1.35 2 19/2.00 84.8 5360
3×185 15.7 5.5 1 39/1.35 2.1 19/2.00 88.2 5790

Other cross-sections can be offered upon request.

IEC 60502 6.35/11 kV ABC for Overhead Distribution Lines

Number of CoresxNominal Cross Section Phase Conductor Messenger Suspension Unit Continuous current rating at 30 ambient temp
Stranding Nominal Sectional Area Maximum Conductor Resistance Stranding Nominal Sectional Area Breaking Load
No.×mm2 No.×mm mm2 Ω/Km No.×mm mm2 KN A
3X50 + 1X25 19/1.78 50 0.641 7/3.0 50 60 116
3X70 + 1X50 19/.14 70 0.443 7/3.15 50 62 210
3X95+ 1X50 19/2.52 95 0.32 7/3.0 50 60 173
3X185+1X120 37/2.52 185 0.164 7/4.67 120 150 259
3X150 +1X50 37/2.25 150 0.206 7/3.15 50 62 365
3X240 +1X50 61/2.25 240 0.125 7/3.15 50 62 500

IEC 60502 19/33 kV ABC for Overhead Distribution Lines

Number of CoresxNominal Cross Section Phase Conductor Messenger Suspension Unit Continuous current rating at 30 ambient temp
Stranding Nominal Sectional Area Maximum Conductor Resistance Stranding Nominal Sectional Area Breaking Load
No.×mm2 No.×mm mm2 Ω/Km No.×mm mm2 KN A
3X50 + 1X50 19/1.78 50 0.641 7/3.0 50 60 165
3X150+ 1X50 37/2.25 150 0.206 7/3.0 50 60 315
3X185+1X70 37/2.52 185 0.164 7/3.57 70 91 355
3X70 +1X50 19/2.14 7 0.443 7/3.15 50 62 250
3X150 +1X50 37/2.25 150 0.206 7/3.15 50 62 370

Factroy and Products

We are China Mv Distribution Line Aerial Bundled Conductor ABC Overhead Cables manufacture and supplier,You can get more details with Email,you will get cheap price or factory price.

Get Latest Price Request a quote

Popular AAC Conductor ABC Cable Products

Aerial Bundeld Cable 4core 95mm2 for Myanmar Market

Duplex/Triplex/Quadruplex Service Drop XLPE Insulated ABC Aerial Bundle Cable

High Quality Overhead ASTM Standard AAC Conductor ABC Cable Duplex Triplex Quadruplex Aerial Bundled Cable

Mv Distribution Line Aerial Bundled Conductor ABC Overhead Cables

Overhead Insulated ABC Cable with Messenger Bare AAAC Conductor

2*6AWG+1*6AWG AAC Conductor Plum ABC Aerial Bundle Overhead Cable

Popular Aerial Bundled Conductor Products

LV 3X70+54.6+16 Aerial Bundled Conductor /ABC Cable with NFC Standard

Aerial Bundled Conductor XLPE Insulated/PE Insulation Aluminum Overhead Cable

Competitive Price of Aerial Bundled Conductor ABC Cable

Competitive Price of Aerial Bundled Cable ABC Cable

Aerial Bundled Conductor SIP1 SIP2 SIP3 SIP4 Cable ABC Cable

Mv Distribution Line Aerial Bundled Conductor ABC Overhead Cables

Popular IEC ABC Cable Products

High Quality ABC Cable with IEC Standard

Mv Distribution Line Aerial Bundled Conductor ABC Overhead Cables

Excellent Performance IEC Standard ABC Cable

Popular jytopcable Products

Middle Voltage Mv 15kv Aluminum Conductor XLPE Insulated Electric Cable

AAAC Conductor with ASTM, BS, DIN, and IEC Standards

LV PVC Insulated Electric Cable with CE ISO9001

Rvvp 300/300V PVC Insulated PVC Sheathed Screen Flexible Control Cable

Bare Conductor AAAC All Aluminum Alloy Conductor Almelec Conductor

Middle Voltage Mv 8.7/15kv Copper Conductor XLPE Insulated Power Cable

Tags: , , ,