NYY-J 0.6/1kV ELECTRIC CABLE PVC Insulated and Sheath Power Cable to DIN/VDE standard
1. Operating Characteristics
Rated voltage: 0.6/1(1.2)kV
Max. Permissible continuous operating temperature of conductor: 70° C
Max. Temperature of conductor during short-circuit (5s max. Duration) shall not exceed:
Nominal cross section of conductor ≤ 300mm2: 160° C;
Nominal cross section of conductor >300mm2: 140° C
The ambient temperature under installation should not be lower than: 0 ° C
The bending radius of cable is recommended as following:
For single core cable: Not less than 20 times of the diameter of cable
For multi-core cable: Not less than 15 times of the diameter of cable
2. Application
The cable is used for fixed installations such as electric power distribution networks or industrial installations, which is laid indoors, in tunnel, in cable trench or in conduit, unable to bear external mechanical force.
3. Manufacturing Standards
IEC 60502-1 & Chinese national standard GB/T 12706-2008 We can produce above cables according to popular international standards such as ASTM, BS, DIN, NF &AS/NZ also.
NOTE:
If you want to know more details about this kind of products, please visit our website(homepage) because we have no ways to show so much information on this platform. Thank you.
Note: RE= round conductor RM = stranded conductor SM=sectional conductor
| Cable size |
Conductor type |
Nominal thickness of PVC insulation(mm) | Nominal thickness of PVC sheath(mm) | Approx. cable overall diameter (mm) | Max. D.C resistance @ 20 0 C (Ω/km) | |||
| Phase core |
Earth core |
Phase core |
Earth core |
Phase core |
Earth core |
|||
| 3×2.5+1.5mm 2 | RE | RE | 0.8 | 0.8 | 1.8 | 11.7 | 7.41 | 12.1 |
| 3×4+2.5mm 2 | RE | RE | 1.0 | 0.8 | 1.8 | 13.5 | 4.61 | 7.41 |
| 3×6+4mm 2 | RE | RE | 1.0 | 1.0 | 1.8 | 15.0 | 3.08 | 4.61 |
| 3×10+6mm 2 | RM | RE | 1.0 | 1.0 | 1.8 | 17.6 | 1.83 | 3.08 |
| 3×16+10mm 2 | RM | RM | 1.0 | 1.0 | 1.8 | 20.3 | 1.15 | 1.83 |
| 3×25+16mm 2 | SM | RM | 1.2 | 1.0 | 1.8 | 21.4 | 0.727 | 1.15 |
| 3×35+16mm 2 | SM | RM | 1.2 | 1.0 | 1.8 | 23.1 | 0.524 | 1.15 |
| 3×50+25mm 2 | SM | SM | 1.4 | 1.2 | 1.9 | 26.3 | 0.387 | 0.727 |
| 3×70+35mm 2 | SM | SM | 1.4 | 1.2 | 2.0 | 30.0 | 0.268 | 0.524 |
| 3×95+50mm 2 | SM | SM | 1.6 | 1.4 | 2.2 | 34.3 | 0.193 | 0.387 |
| 3×120+70mm 2 | SM | SM | 1.6 | 1.4 | 2.3 | 37.6 | 0.153 | 0.268 |
| 3×150+70mm 2 | SM | SM | 1.8 | 1.4 | 2.4 | 40.8 | 0.124 | 0.268 |
| 3×185+95mm 2 | SM | SM | 2.0 | 1.6 | 2.6 | 45.7 | 0.0991 | 0.193 |
| 3×240+120mm 2 | SM | SM | 2.2 | 1.6 | 2.8 | 51.3 | 0.0754 | 0.153 |
| 3×300+150mm 2 | SM | SM | 2.4 | 1.8 | 2.9 | 56.6 | 0.0601 | 0.124 |
| 0.6/1kv XLPE/PVC POWER CABLE(unarmored) YJV,YJLV | |||||||||||||||||||||
| sectional Area of Conductor (mm²) |
Thickness Insulation (mm) |
Non-metallic sheath unarmored cable | |||||||||||||||||||
| Thickness of sheath | approx overall diameter | approx cable weight(kg/km) | |||||||||||||||||||
| mm | mm | Cu | Al | ||||||||||||||||||
| 1c | 2c | 3c | 4c | 5c | 1c | 2c | 3c | 4c | 5c | 1c | 2c | 3c | 4c | 5c | 1c | 2c | 3c | 4c | 5c | ||
| 1.5 | 0.7 | 1.4 | 1.8 | 1.8 | 1.8 | 1.8 | 5.6 | 10 | 10.4 | 11.1 | 11.9 | 45 | 122 | 139 | 167 | 195 | 35 | 103 | 111 | 506 | 148 |
| 2.5 | 0.7 | 1.4 | 1.8 | 1.8 | 1.8 | 1.8 | 6 | 10.8 | 11.2 | 12.1 | 13 | 57 | 148 | 175 | 215 | 253 | 42 | 117 | 129 | 641 | 175 |
| 4 | 0.7 | 1.4 | 1.8 | 1.8 | 1.8 | 1.8 | 6.5 | 11.7 | 12.3 | 13.2 | 14.3 | 75 | 185 | 228 | 285 | 337 | 50 | 135 | 153 | 833 | 212 |
| 6 | 0.7 | 1.4 | 1.8 | 1.8 | 1.8 | 1.8 | 7 | 12.7 | 13.4 | 14.4 | 15.6 | 97 | 239 | 295 | 373 | 445 | 60 | 165 | 183 | 1086 | 258 |
| 10 | 0.7 | 1.4 | 1.8 | 1.8 | 1.8 | 1.8 | 8.1 | 15 | 15.8 | 17.2 | 18.7 | 143 | 346 | 445 | 568 | 681 | 80 | 220 | 256 | 1629 | 366 |
| 16 | 0.7 | 1.4 | 1.8 | 1.8 | 1.8 | 1.8 | 9.2 | 17.2 | 18.2 | 19.8 | 21.7 | 206 | 494 | 660 | 835 | 1008 | 106 | 292 | 358 | 2377 | 505 |
| 25 | 0.9 | 1.4 | 1.8 | 1.8 | 1.8 | 1.8 | 10.6 | 20 | 21.2 | 23.2 | 25.5 | 303 | 711 | 951 | 1217 | 1483 | 146 | 396 | 479 | 3457 | 696 |
| 35 | 0.9 | 1.4 | 1.8 | 1.8 | 1.8 | 1.8 | 11.8 | 22.4 | 23.8 | 26.1 | 28.7 | 403 | 919 | 1267 | 1598 | 1959 | 185 | 478 | 606 | 4528 | 858 |
| 50 | 1 | 1.4 | 1.8 | 1.8 | 1.9 | 2 | 13.2 | 25.2 | 26.8 | 29.7 | 32.9 | 554 | 1188 | 1675 | 2209 | 2733 | 241 | 558 | 731 | 6190 | 1160 |
| 70 | 1.1 | 1.4 | 1.9 | 1.9 | 2 | 2.1 | 15 | 22.2 | 25.7 | 30 | 36.2 | 755 | 1564 | 2260 | 2987 | 3735 | 317 | 683 | 939 | 8348 | 1533 |
| 95 | 1.1 | 1.5 | 2 | 2 | 2.1 | 2.3 | 16.9 | 25.2 | 29.1 | 34.2 | 40.3 | 1004 | 2069 | 3003 | 3977 | 4975 | 409 | 874 | 1210 | 11091 | 1987 |
| 120 | 1.2 | 1.5 | 2.1 | 2.1 | 2.3 | 2.4 | 18.5 | 28.2 | 32.4 | 37.2 | 44.7 | 1250 | 2592 | 3763 | 4983 | 6228 | 498 | 1082 | 1498 | 13880 | 2453 |
| 150 | 1.4 | 1.6 | 2.2 | 2.3 | 2.4 | 2.6 | 20.6 | 31 | 36.2 | 41.2 | 50.3 | 1558 | 3214 | 4700 | 6202 | 7777 | 619 | 1327 | 1869 | 17280 | 3059 |
| 185 | 1.6 | 1.6 | 2.3 | 2.4 | 2.6 | 2.8 | 22.7 | 36.8 | 40.4 | 46.2 | 58.6 | 1908 | 3978 | 5779 | 7655 | 9623 | 750 | 1650 | 2287 | 21355 | 3803 |
| 240 | 1.7 | 1.7 | 2.5 | 2.6 | 2.8 | 3 | 25.3 | 41.6 | 47.4 | 53.3 | 63.1 | 2450 | 5104 | 7456 | 9859 | 12326 | 947 | 2084 | 2926 | 27399 | 4776 |
| 300 | 1.8 | 1.8 | 2.7 | 2.8 | 3 | 3.2 | 27.9 | 46.4 | 50.1 | 59.4 | 68.2 | 3053 | 6328 | 9234 | 12260 | 15291 | 1163 | 2541 | 3554 | 33997 | 5824 |
| 400 | 2 | 1.9 | 3.1 | 3.3 | 3.6 | 31.6 | 57.2 | 68.4 | 83.1 | 4021 | 12224 | 16240 | 20305 | 1514 | 4651 | 36685 | 7683 | ||||
| 500 | 2.2 | 2 | 3.3 | 3.3 | 35 | 74.2 | 82.2 | 5002 | 15136 | 20176 | 1869 | 5849 | 7554 | ||||||||
| 630 | 2.4 | 2.2 | 39.3 | 6290 | 2342 | ||||||||||||||||
| 800 | 2.6 | 2.3 | 44.8 | 7957 | 2943 | ||||||||||||||||
| 1000 | 2.8 | 2.4 | 49.9 | 9897 | 3629 | ||||||||||||||||
| 0.6/1kv XLPE/PVC POWER CABLE(unarmored) YJV,YJLV | |||||||||||||||
| sectional Area of Conductor (mm²) | Thickness of insulation (mm) | Non-metallic sheath unarmored cable | |||||||||||||
| thickness of sheath | approx overall diameter | cable weight | |||||||||||||
| mm | mm | Cu | Al | ||||||||||||
| phase line | zero line | phase line | zero line | 3+1c | 3+2c | 4+1c | 3+1c | 3+2c | 4+1c | 3+1c | 3+2c | 4+1c | 3+1c | 3+2c | 4+1c |
| 2.5 | 1.5 | 0.7 | 0.7 | 1.8 | 1.8 | 1.8 | 11.9 | 12.6 | 12.8 | 206 | 229 | 253 | |||
| 4 | 2.5 | 0.7 | 0.7 | 1.8 | 1.8 | 1.8 | 12.9 | 13.7 | 14 | 268 | 302 | 323 | 178 | 196 | 197 |
| 6 | 4 | 0.7 | 0.7 | 1.8 | 1.8 | 1.8 | 14.2 | 15.1 | 15.4 | 352 | 402 | 428 | 215 | 240 | 237 |
| 10 | 6 | 0.7 | 0.7 | 1.8 | 1.8 | 1.8 | 16.5 | 17.5 | 18.1 | 517 | 584 | 645 | 290 | 321 | 328 |
| 16 | 10 | 0.7 | 0.7 | 1.8 | 1.8 | 1.8 | 19.2 | 20.5 | 21.1 | 761 | 865 | 955 | 396 | 437 | 444 |
| 25 | 16 | 0.9 | 0.7 | 1.8 | 1.8 | 1.8 | 22.4 | 23.9 | 24.7 | 1110 | 1278 | 1406 | 538 | 605 | 606 |
| 35 | 16 | 0.9 | 0.7 | 1.8 | 1.8 | 1.8 | 24.6 | 25.9 | 27.3 | 1402 | 1558 | 1805 | 647 | 709 | 731 |
| 50 | 25 | 1 | 0.9 | 1.8 | 1.9 | 1.9 | 28 | 29.9 | 31.3 | 1943 | 2243 | 2531 | 842 | 984 | 975 |
| 70 | 35 | 1.1 | 0.9 | 1.9 | 2 | 2.1 | 29.5 | 33.2 | 34.4 | 2645 | 3038 | 3412 | 1101 | 1273 | 1234 |
| 95 | 50 | 1.1 | 1 | 2.1 | 2.2 | 2.2 | 33.2 | 37.8 | 38.7 | 3554 | 4105 | 4551 | 1443 | 1679 | 1579 |
| 120 | 70 | 1.2 | 1.1 | 2.2 | 2.3 | 2.4 | 36.3 | 41.6 | 43.6 | 4504 | 5265 | 5791 | 1793 | 2112 | 1993 |
| 150 | 70 | 1.4 | 1.1 | 2.3 | 2.4 | 2.5 | 39.7 | 45.9 | 47.9 | 5425 | 6200 | 7018 | 2147 | 2480 | 2380 |
| 185 | 95 | 1.6 | 1.1 | 2.5 | 2.6 | 2.7 | 45.4 | 51.4 | 53.3 | 6781 | 7792 | 8720 | 2683 | 3095 | 2946 |
| 240 | 120 | 1.7 | 1.2 | 2.7 | 2.8 | 2.9 | 53 | 58.6 | 60.1 | 8708 | 9960 | 11172 | 3412 | 3907 | 3701 |
| 300 | 150 | 1.8 | 1.4 | 2.9 | 3 | 3.1 | 58.3 | 65.4 | 62.9 | 10818 | 12394 | 13827 | 4192 | 4823 | 4480 |
| 400 | 185 | 2 | 1.6 | 3.1 | 3.3 | 3.4 | 67.5 | 74. 2 | 67.8 | 14163 | 16132 | 18093 | 5423 | 6225 | 5725 |
| 1.8/3(3.6)kv XLPE/PVC single core (unarmored)YJV,YJLV | |||||||||
| conductor | thickness of insulation (mm) | copper tape screened (mm) | thickness of sheath(mm) | approx overall diameter (mm) | copper core cable weight (kg/km) | aluminum core cable weight (kg/km) | insulation resistance 20ºC(Min.) (MΩ/km) | ||
| sectional area(mm²) | structure | overall diameter (mm) | |||||||
| 10 | C.C. | 3.9 | 2 | 0.12 | 1.4 | 12.9 | 252 | 189 | 500 |
| 16 | C.C. | 5 | 2 | 0.12 | 1.4 | 14 | 326 | 226 | 500 |
| 25 | C.C. | 6 | 2 | 0.12 | 1.4 | 15 | 426 | 269 | 500 |
| 35 | C.C. | 7.2 | 2 | 0.12 | 1.4 | 16.2 | 538 | 319 | 500 |
| 50 | C.C. | 8.4 | 2 | 0.12 | 1.5 | 17.6 | 702 | 390 | 500 |
| 70 | C.C. | 10 | 2 | 0.12 | 1.5 | 19.2 | 914 | 475 | 500 |
| 95 | C.C. | 11.7 | 2 | 0.12 | 1.6 | 21.1 | 1181 | 586 | 500 |
| 120 | C.C. | 13.1 | 2 | 0.12 | 1.6 | 22.5 | 1433 | 681 | 500 |
| 150 | C.C. | 14.6 | 2 | 0.12 | 1.7 | 24.2 | 1743 | 803 | 500 |
| 185 | C.C. | 16.3 | 2 | 0.12 | 1.7 | 25.9 | 2091 | 933 | 500 |
| 240 | C.C. | 18.5 | 2 | 0.12 | 1.8 | 28.3 | 2643 | 1140 | 500 |
| 300 | C.C. | 20.7 | 2 | 0.12 | 1.9 | 30.7 | 3244 | 1364 | 500 |
| 400 | C.C. | 23.8 | 2 | 0.12 | 2 | 34 | 4225 | 1718 | 500 |
| 500 | C.C. | 26.6 | 2.2 | 0.12 | 2.1 | 37.4 | 5227 | 2093 | 500 |
| 630 | C.C. | 30.1 | 2.4 | 0.12 | 2.2 | 41.5 | 6523 | 2574 | 500 |
| 800 | C.C. | 35 | 2.6 | 0.12 | 2.3 | 47 | 8221 | 3207 | 500 |
| 1000 | S.S | 39.5 | 2.8 | 0.12 | 2.5 | 52.3 | 10371 | 4104 | 500 |
Note:
C.C.: circular compacted
S.S.: shaped stranded conductor
| 1.8/3(3.6)KV XLPE/PVC single core (unarmored)YJV,YJLV | |||||||||
| conductor | thickness insulation (mm) | copper tape screened (mm) | thickness of sheath(mm) | approx overall diameter (mm) | copper core cable weight (kg/km) | aluminum core cable weight (kg/km) | insulation resistance 20ºC(Min.) (MΩ/km) | ||
| sectional area(mm²) | structure | overall diameter (mm) | |||||||
| 10 | C.C. | 3.9 | 2 | 0.1 | 1.8 | 22.8 | 700 | 511 | 500 |
| 16 | C.C. | 5 | 2 | 0.1 | 1.8 | 25.2 | 964 | 662 | 500 |
| 25 | C.C. | 6 | 2 | 0.1 | 1.8 | 27.3 | 1255 | 783 | 500 |
| 35 | C.C. | 7.2 | 2 | 0.1 | 1.9 | 30.1 | 1623 | 962 | 500 |
| 50 | C.C. | 8.4 | 2 | 0.1 | 2 | 32.9 | 2016 | 1072 | 500 |
| 70 | C.C. | 10 | 2 | 0.1 | 2.1 | 36.6 | 2660 | 1336 | 500 |
| 95 | C.C. | 11.7 | 2 | 0.1 | 2.2 | 40.4 | 3444 | 1647 | 500 |
| 120 | C.C. | 13.1 | 2 | 0.1 | 2.3 | 43.6 | 4216 | 1946 | 500 |
| 150 | C.C. | 14.6 | 2 | 0.1 | 2.4 | 47.1 | 5141 | 2304 | 500 |
| 185 | C.C. | 16.3 | 2 | 0.1 | 2.5 | 50.9 | 6207 | 2707 | 500 |
| 240 | C.C. | 18.5 | 2 | 0.1 | 2.7 | 56.1 | 7874 | 3335 | 500 |
| 300 | C.C. | 20.7 | 2 | 0.1 | 2.8 | 61 | 9666 | 3986 | 500 |
| 400 | C.C. | 23.8 | 2 | 0.1 | 3.1 | 68.3 | 12659 | 5086 | 500 |
| 500 | C.C. | 26.6 | 2.2 | 0.1 | 3.3 | 75.6 | 15695 | 6228 | 500 |
Note:
We are China Nycy 0.6/1kv PVC Power Cable to DIN/VDE Standard manufacture and supplier,You can get more details with Email,you will get cheap price or factory price.
Get Latest Price Request a quote
Popular 1kv Electric Cable Products
Nayy-J 0.6/1kv PVC Power Cable to DIN/VDE Standard
Nayy 0.6/1kv PVC Power Cable to DIN/VDE Standard
N2X Ry-O/N2X Ry-J Cu/PVC Power Cable to DIN/VDE0276
N2xcy/N2xcwy/Na2xcwy Cu/PVC Power Cable to DIN/VDE 0276
Nyry-O/Nyry-J 0.6/1kv Power Cable to DIN/VDE Standard
1kv PVC Insulation and Sheath Cable with Single Core
Popular Cable Nycy Products
Popular jytopcable Products
Single Core Overhead XLPE Insulated Aluminium Covered Line Wire and Cable
Aerial Twisted Aluminum ABC Cable for Overhead Line
Low Voltage Aerial Bundle Cable ABC
Bare Conductor AAC for Overhead Transmission 185mm2
Middle Voltage XLPE Insulated Power Cable with Copper Conductor
Thhn Electric Wire with Nylon Jacket
Popular Nycy Power Cable Products
3 Core 25mm2 Unarmoured or Armoured Copper Core Nycy XLPE PVC Power Cable Price
Tags: 1kv Electric Cable, Cable Nycy, jytopcable, Nycy Power Cable