Oil-Immersed Power Transformer 11kv 33kv
Oil-Immersed Power Transformer 11kv 33kv image
Get Latest Price Request a quote
Quick Details
Product Details
Suzhou Silverstone Electric Co., Ltd
1. General
(1) Application:
>> 12, 24,36KV~220kv class transformers
are widely used in power transmission and distribution stations,
industry plants, Generation Setup Unit (GSU).
>> They have the characteristic of high efficiency, low loss and maintenance free.
(2) Type and Rating
**Capacity range :50-50000KVA.
**Secondary voltage: 415V ,400V etc.
**Frequency :50Hz ,60Hz.
**Type: Single phase, three phase.
**No-load tap changer and on-load tap changer.
**ONAN and ONAF.
**Set-up and set-down type.
(3) Standard: IEC60076-1, IEC60076-2, IEC60076-5, IEC60317, ANSI, IEEE, AS, etc.
2. Conditions of service
(1) Altitude: Up to 1,000m above sea level.
(2) Ambient temperature:
**Max: +40ºC.
**Average (daily, Max.): +30ºC.
**Average (yearly, Max.): +20ºC.
**Min: -45ºC.
(3) Environment: Outdoor.
(4) Special conditions:
It may be consulted between manufacturer and customer.
3. Structural Features
(1) Iron core
The iron core is made of cold rolled grain oriented silicon steel sheet. Laminations are cut to length
on GEORG cut to- length line with step lap cut and automatic stacking functions.
The multistep lamination structure can reduce the loss and noise.
The steel sheet in the core limbs and yokes are clamped together by glass-epoxy bonds.
(2) Winding
High quality enameled or paper covered copper is used as conductor, the winding was made as
drum type, spiral type, improved spiral type, continuous type and interleaved type to ensure the insulation strength. Standard tapings are ±2*2.5%of the HV winding.
(3) Tank
The tank, cover and the conservator are made by corrugated steel plate. For the small transformers,
we use a deep tank and a cover, but for larger transformers, we manufacture bell type. The corrugated construction is a effective way for oil cooling.
(4) Insulation oil
The tanks are filled with high quality grade mineral oil as per IEC296 and it is PCB and PCT free.
The oil is used to help cooling the transformer. It is also used provide part of the electrical insulation between internal live parts.
(5) Tap changer
Tap changers are used to regulate the output voltage of the transformers to required levels. We
achieve this by changing the ratios of the transformer on the system by altering the number of turns in the HV winding. Tap changers can be on load (OLTC) or off load(OCTC).
(6) Assembly
The core and the windings assembled together from the active part of the transformer. The active
body assembled with multi-windings and identical pressure dry method adopted, effectively improved
the electrical strength and the ability to short circuit withstanding.
4. Test equipment
Strict test should be done according to IEC standard, by high technical equipment to ensure the
quality and the reliable of every transformer.
5. Technical Data of Typical Products
>S9, S10 series 10KV three phase off -load tap changer distribution transformer
| Type | Rating KVA |
On-load loss (w) |
Load loss (w) |
I (%) |
UK (%) |
Dimension (mm) | Weight (kg) |
||
| a | b | c | |||||||
| S9-M-50/11 | 50 | 170 | 870 | 2.0 | 4.0 | 1215 | 660 | 1170 | 430 |
| S9-M-250/11 | 250 | 560 | 3050 | 1.2 | 4.0 | 1190 | 815 | 1370 | 1115 |
| S9-M-400/11 | 400 | 800 | 4300 | 1.0 | 4.0 | 1515 | 770 | 1580 | 1380 |
| S9-M-500/11 | 500 | 960 | 5050 | 1.0 | 4.0 | 1635 | 840 | 1610 | 1600 |
| S9-M-1000/11 | 1000 | 1700 | 10300 | 0.7 | 4.5 | 1960 | 1095 | 1960 | 2860 |
| S9-M-2500/11 | 2500 | 3300 | 23000 | 0.55 | 5.5 | 2230 | 2305 | 2445 | 5660 |
| S10-M-30/10 | 30 | 110 | 600 | 1.8 | 4.0 | 870 | 645 | 1025 | 310 |
| S10-M-50/10 | 50 | 140 | 870 | 1.7 | 4.0 | 1090 | 650 | 1080 | 395 |
| S10-M-80/10 | 80 | 200 | 1250 | 1.6 | 4.0 | 1140 | 675 | 1110 | 490 |
| S10-M-100/10 | 100 | 240 | 1500 | 1.5 | 4.0 | 1185 | 690 | 1130 | 560 |
| S10-M-125/10 | 125 | 280 | 1800 | 1.4 | 4.0 | 1205 | 710 | 1180 | 670 |
| S10-M-160/10 | 160 | 340 | 2200 | 1.3 | 4.0 | 1255 | 720 | 1200 | 780 |
| S10-M-200/10 | 200 | 400 | 2600 | 1.2 | 4.0 | 1295 | 740 | 1215 | 875 |
| S10-M-250/10 | 250 | 470 | 3050 | 1.1 | 4.0 | 1340 | 755 | 1260 | 1115 |
| S10-M-315/10 | 315 | 560 | 3650 | 1.0 | 4.0 | 1400 | 770 | 1320 | 1280 |
| S10-M-400/10 | 400 | 680 | 4300 | 0.9 | 4.0 | 1500 | 860 | 1400 | 1490 |
| S10-M-500/10 | 500 | 810 | 5150 | 0.9 | 4.0 | 1575 | 895 | 1430 | 1740 |
| S10-M-630/10 | 630 | 1020 | 6200 | 0.8 | 4.5 | 1660 | 930 | 1545 | 2110 |
| S10-M-800/10 | 800 | 1190 | 7500 | 0.7 | 4.5 | 1830 | 1070 | 1590 | 2625 |
| S10-M-1000/10 | 1000 | 1450 | 10300 | 0.6 | 4.5 | 1935 | 1175 | 1685 | 2860 |
| S10-M-1250/10 | 1250 | 1650 | 12000 | 0.6 | 4.5 | 1960 | 1170 | 1730 | 3330 |
| S10-M-1600/10 | 1600 | 2040 | 14500 | 0.5 | 4.5 | 2325 | 1220 | 2120 | 3765 |
| S10-M-2000/10 | 2000 | 2140 | 17820 | 0.5 | 4.5 | 2395 | 1260 | 2225 | 4530 |
>>S11 series 20KV three phase off -load tap changer distribution transformer
| TYPE | Voltage ratio(kV) | Connection | No load Loss (W) |
Load loss (W) |
Io (%) |
UK (%) |
Dimensions (mm) | Weight (Kg) | |||||
| a | b | c | d | e | f | ||||||||
| S11-M-30/20 | 20(10) ±5%/0.4 |
Yyn0 Dyn11 |
100 | 690/ 660 |
2.1 | 5.5 |
1100 | 700 | 1240 | 14 | 400 | 400 | 640 |
| S11-M-50/20 | 130 | 1010/ 960 |
2.0 | 1130 | 710 | 1260 | 14 | 400 | 450 | 710 | |||
| S11-M-63/20 | 150 | 1200/1150 | 1.9 | 1160 | 740 | 1270 | 14 | 400 | 450 | 780 | |||
| S11-M-80/20 | 180 | 1440/1370 | 1.8 | 1200 | 770 | 1280 | 14 | 400 | 450 | 860 | |||
| S11-M-100/20 | 200 | 1730/ 1650 |
1.6 | 1220 | 800 | 1300 | 14 | 400 | 450 | 900 | |||
| S11-M-125/20 | 240 | 2080/ 1980 |
1.5 | 1270 | 840 | 1330 | 19 | 550 | 450 | 970 | |||
| S11-M-160/20 | 290 | 2540/ 2420 |
1.4 | 1320 | 870 | 1350 | 19 | 550 | 550 | 1100 | |||
| S11-M-200/20 | 340 | 3000/ 2860 |
1.3 | 1360 | 900 | 1380 | 19 | 550 | 550 | 1240 | |||
| S11-M-250/20 | 400 | 3520/ 3350 |
1.2 | 1430 | 910 | 1430 | 19 | 550 | 650 | 1420 | |||
| S11-M-315/20 | 480 | 4210/ 4010 |
1.1 | 1460 | 920 | 1450 | 19 | 550 | 650 | 1570 | |||
| S11-M-400/20 | 570 | 4970/ 4730 |
1.0 | 1490 | 940 | 1470 | 19 | 660 | 750 | 1740 | |||
| S11-M-500/20 | 680 | 5940/ 5660 |
1.0 | 1570 | 970 | 1540 | 19 | 660 | 750 | 1950 | |||
| S11-M-630/20 | 810 | 6820 | 0.9 | 6.0 |
1650 | 1000 | 1580 | 19 | 660 | 850 | 2290 | ||
| S11-M-800/20 | 980 | 8250 | 0.8 | 1750 | 1070 | 1650 | 19 | 820 | 850 | 2690 | |||
| S11-M-1000/20 | 1150 | 11330 | 0.7 | 1830 | 1170 | 1690 | 19 | 820 | 850 | 2880 | |||
| S11-M-1250/20 | 1380 | 13200 | 0.7 | 1900 | 1200 | 1790 | 19 | 820 | 850 | 3400 | |||
| S11-M-1600/20 | 1660 | 15950 | 0.6 | 1950 | 1250 | 1850 | 19 | 820 | 900 | 4100 | |||
>>>>S9 series 35kV three phase Off-load tap changer power transformer
| Capacity KVA |
Voltage and tap range | Connection | No-load loss (kW) |
Load loss (KW) |
NO-load current (%) |
Impedance (%) |
Dimensions (mm) LxWxH |
||
| HV (kV) | MV (kV) | LV (kV) | |||||||
| 50 | 35 | ± 5 | 0.4 | Dyn11 Yyn0 |
0.21 | 1.27/1.21 | 2.00 | 6.5 | 1100x845x1715 |
| 100 | 0.29 | 2.12/2.02 | 1.80 | 1190x915x1780 | |||||
| 125 | 0.34 | 2.50/2.38 | 1.70 | 1220x1040x1780 | |||||
| 160 | 0.36 | 2.97/2.83 | 1.60 | 1240x1070x1810 | |||||
| 200 | 0.43 | 3.50/3.33 | 1.50 | 1380x780x1875 | |||||
| 250 | 0.51 | 4.16/3.96 | 1.40 | 1540x880x1820 | |||||
| 315 | 0.61 | 5.01/4.77 | 1.40 | 1440x800x1975 | |||||
| 400 | 0.73 | 6.05/5.76 | 1.30 | 1660x825x1995 | |||||
| 500 | 0.86 | 7.28/6.93 | 1.20 | 1710x865x2030 | |||||
| 630 | 1.04 | 8.28 | 1.10 | 1630x1235x2070 | |||||
| 800 | 1.23 | 9.90 | 1.00 | 1655x1415x2120 | |||||
| 1000 | 1.44 | 12.15 | 1.00 | 1860x1435x2220 | |||||
| 1250 | 1.76 | 14.67 | 0.90 | 1890x1640x2260 | |||||
| 1600 | 2.12 | 17.55 | 0.80 | 2050x1720x2390 | |||||
| 630 | 3.15 6.3 10.5 |
Yd11 | 1.04 | 8.28 | 1.10 | 1630x1235x2070 | |||
| 800 | 1.23 | 9.90 | 1.00 | 1655x1415x2120 | |||||
| 1000 | 1.44 | 12.15 | 1.00 | 1860x1435x2220 | |||||
| 1250 | 1.76 | 14.67 | 0.90 | 1890x1640x2260 | |||||
| 1600 | 2.12 | 17.55 | 0.80 | 2050x1720x2390 | |||||
| 2000 | 2.72 | 19.35 | 0.70 | 2400x1900x2410 | |||||
| 2500 | 3.20 | 20.70 | 0.60 | 2500x1930x2700 | |||||
| 3150 | 35~ 38.5 |
± 5 | 3.15 6.3 10.5 |
3.80 | 24.30 | 0.56 | 7.0 | 2600x2100x2800 | |
| 4000 | 4.52 | 28.80 | 0.56 | 2830 x2350x2855 | |||||
| 5000 | 5.40 | 33.03 | 0.48 | 2930x2480x2930 | |||||
| 6300 | 6.56 | 36.90 | 0.48 | 7.5 | 3150x2330x3220 | ||||
| 8000 | ± 2 x 2.5 | 3.15 3.3 6.3 6.6 10.5 11 |
YNd11 | 9.00 | 40.50 | 0.42 | 3295x3110x3345 | ||
| 10000 | 10.88 | 47.70 | 0.42 | 3450x3210x3440 | |||||
| 12500 | 12.60 | 56.70 | 0.40 | 8.0 | 3620x3255x3500 | ||||
| 16000 | 15.20 | 69.30 | 0.40 | 3980x3420x3650 | |||||
| 20000 | 18.00 | 83.70 | 0.40 | 4030x3470x3690 | |||||
| 25000 | 21.28 | 99.00 | 0.32 | 5050x4640x3930 | |||||
| 31500 | 25.28 | 118.8 | 0.32 | 5120x4800x4030 | |||||
>>>>S9 series 35kV three phase on-load tap changer power transformer
| Type | Voltage compose and Tapping range (kV) | Connection |
No-load Loss (kW) |
Load loss (kW) |
No- load current (I%) |
Impedance voltage (%) | Transport weight (t) | Gross weight (t) | Dimensions L×W×H (mm) |
|
| HV | LV | |||||||||
| SZ9-2000/35 | 35 ±3×2.5% |
6.3 10.5 |
Yd11 | 2.88 | 18.7 | 1.00 | 6.5 | 4.93 | 5.97 | 3010×2070×2540 |
| SZ9-2500/35 | 3.40 | 21.7 | 1.00 | 6.5 | 5.68 | 6.95 | 3040×2270×2610 | |||
| SZ9-3150/35 | 4.04 | 26.0 | 0.90 | 7.0 | 6.08 | 7.90 | 3160×2300×2640 | |||
| SZ9-4000/35 | 35 38.5 ±3×2.5% |
6.3 10.5 |
4.84 | 30.7 | 0.90 | 7.0 | 7.10 | 9.11 | 3300×2330×2890 | |
| SZ9-5000/35 | 5.80 | 36.0 | 0.85 | 7.0 | 8.47 | 10.86 | 3350×2520×3000 | |||
| SZ9-6300/35 | 7.04 | 38.7 | 0.85 | 7.5 | 9.87 | 12.30 | 3680×2650×3050 | |||
| SZ9-8000/35 | 9.84 | 42.8 | 0.75 | 7.5 | 12.55 | 15.30 | 4190×2930×3280 | |||
| SZ9-10000/35 | 35 38.5 ±3×2.5% |
6.3 6.6 10.5 11 |
Ynd11 |
11.6 | 50.6 | 0.75 | 7.5 | 14.70 | 17.86 | 4620×3160×3400 |
| SZ9-12500/35 | 13.7 | 60.0 | 0.70 | 8.0 | 17.35 | 20.05 | 4740×3200×3540 | |||
| SZ9-16000/35 | 16.0 | 73.0 | 0.70 | 8.0 | 19.45 | 23.74 | 4810×3360×3790 | |||
| SZ9-20000/35 | 18.9 | 88.3 | 0.70 | 8.0 | 27.50 | 34.95 | 4880×3540×4150 | |||
| SZ9-25000/35 | 22.4 | 104.4 | 0.65 | 8.0 | 32.51 | 40.22 | 4920×3920×4200 | |||
| SZ9-31500/35 | 26.6 | 125.3 | 0.65 | 8.0 | 37.73 | 45.53 | 5010×4270×4460 | |||
We are China Oil-Immersed Power Transformer 11kv 33kv manufacture and supplier,You can get more details with Email,you will get cheap price or factory price.
Get Latest Price Request a quote
Popular Oil Transformet Products
33kv Medium Voltage Dry Type Distribution Transformers
11kv S11-M Sealed Transformer Factory
Sczb10-250~2500kVA 11kv on-Load Tap-Changing Distribution Transformer
330kv Three Phase off-Circuit Tap Changing Power Transformers
11kv Step Voltage Regulator Voltage Stabilizer
11kv Single Phase Overhead Conventional Pole Mounted Distribution Transformer
Popular Power Transformer Products
Sz11 Type 33kv on-Load Tap Changing Transformers
230kv 132kv 126kv Oil-Immersed Power Transformer IEC Standard
Oil Immersed Distribution Transformer 24kv
Step Voltage Regulator Oil Immersed
132kv Furnace Transformer with Tap Changing Oltc
20kv 24kv 50-3150kVA Distribution Transformer
Popular Rectifier Transformer Products
220kv 230kvlow Loss Oil-Immersed Power Transformer
33kv 38kv Oil-Immersed Power Transformer IEC Standard
Amorphous Alloy Oil-Immersed Power Distribution Transformer
132kv and Above Rectifier Special Transformer IEC Standard
210kVA DC185V Cast Resin Insulation Dry Type Excitation Rectifier Transformer
Vacuum Resin Cast Dry-Type Transformer Power Transmission
Popular silverstone-electric Products
66kv and 69kv Rectifier Special Transformer IEC Standard
33kv Dry Type on-Load Tap Changer Power Transformers
Three Phase Pad Mount Mobile Power Distribution Transformers 11kv
Vintage Grey Ceramic 160kn Normal Disc Insulator ANSI
High Voltage Cap and Pin Type Suspension Insulator
11kv Single Phase Overhead Conventional Pole Mounted Distribution Transformer
Tags: Oil Transformet, Power Transformer, Rectifier Transformer, silverstone-electric