Overhead Transmission Aluminium Cable Duplex Service Drop ABC Cable
Overhead Transmission Aluminium Cable Duplex Service Drop ABC Cable image
Get Latest Price Request a quote
Quick Details
Product Details
Construction:
Conductors are concentric stranded or compressed conductors of aluminum 1350-H19 covered for weather proofing with polyethylene, High Density polyethylene (HDPE) or Cross-linked polyethylene (XLPE) insulation, concentric stranded AAC,ACSR or 6210 AAAC alloy neutral messenger.
Applications:
Duplex Service Drop is to supply 120V or 240V and below aerial service for temporary service at construction sites, outdoor or street lighting, for service at 600V or below at a conductor temperature of 70ºC maximum for polyethylene insulation , or 90ºC maximum for cross-linked polyethylene insulation.
Standards:
Duplex service drop cable meets or exceeds the following ASTM specifications:
ASTM B-230 Aluminum Wire, 1350-H19 for Electrical Purposes.
ASTM B-231 Aluminum Conductors, Concentric-Lay-Stranded.
ASTM B-232 Aluminum Conductors, Concentric-Lay-Stranded, Coated Steel Reinforced (ACSR).
ASTM B-399 Concentric-Lay-Stranded Aluminum Alloy Conductors 6201-T81.
Service drop conductor meets or exceeds all applicable requirement of ANSI/ ICEA-S-76-474:
Ampacity rating base on 75ºC conductor temperature; 25ºC ambient temperature. Emissivity 0.91 and coefficient of absorbtion of 0.95.
Code Word | Phase Conductor | Bare Neutral Messenger | Weight Per 1000 ft. (lbs.) | Allowable Ampacity+ | |||||||
Size (AWG or kcmil) | Stranding | Insul. Thick. (mils) | Size (AWG) | Strand- ing | Insul. Thick. (mils) | Rated Strength (lbs.) | XLP | POLY | XLP | POLY | |
6201 ALLOY NEUTRAL-MESSENGER | |||||||||||
Chihuahua | 6 | 1 | 45 | 6 | 30.58 | 7 | 1110 | 65 | 65 | 85 | 70 |
Vizsla | 6 | 7 | 45 | 6 | 30.58 | 7 | 1110 | 68 | 68 | 85 | 70 |
Harrier | 4 | 1 | 45 | 4 | 48.69 | 7 | 1760 | 99 | 99 | 115 | 90 |
Whippet | 4 | 7 | 45 | 4 | 48.69 | 7 | 1760 | 103 | 103 | 115 | 90 |
Schnauzer | 2 | 7 | 45 | 2 | 77.47 | 7 | 2800 | 157 | 157 | 150 | 120 |
Heeler | 1/0 | 9 | 60 | 1/0 | 123.3 | 7 | 4460 | 250 | 250 | 205 | 160 |
* Code words for XLP insulated products are formed by adding "/XLP" to the conventional code words above (e.g.-Chihuahua/XLP).+ Conductor temperature of 90°C for XLP, 75°C for Poly; ambient temperature of 40°C; emissivity 0.9; 2 ft./sec. wind in sun.++ Designated sizes are: ACSR 6/1 diameter equivalent and AAC with equivalent resistivity per ASTM B-399 for 6201. |
Code Word | Phase Conductor | Bare Neutral Messenger | Weight Per 1000 ft. (lbs.) | Allowable Ampacity+ | ||||||
Size (AWG or kcmil) | Stranding | Insul. Thick. (mils) | Size (AWG) | Strand- ing | Rated Strength (lbs.) | XLP | POLY | XLP | POLY | |
AAC NEURAL-MESSENGER | ||||||||||
Pekingese | 6 | 1 | 45 | 6 | 7 | 563 | 61 | 61 | 85 | 70 |
Collie | 6 | 7 | 45 | 6 | 7 | 563 | 64 | 64 | 85 | 70 |
DachShund | 4 | 1 | 45 | 4 | 7 | 881 | 92 | 92 | 115 | 90 |
Spaniel | 4 | 7 | 45 | 4 | 7 | 881 | 96 | 96 | 115 | 90 |
Doberman | 2 | 7 | 45 | 2 | 7 | 1350 | 147 | 147 | 150 | 120 |
Bull | 1/0 | 9 | 60 | 1/0 | 7 | 1990 | 234 | 234 | 205 | 160 |
* Code Words For XLP Insulated Products Are Formed By Adding "/XLP" to the Conventional Code Words Above (e.g.-Chihuahua/XLP).+ Conductor Temperature of 90°C For XLP, 75°C For Poly; Ambient Temperature of 40°C; Emissivity 0.9; 2 ft./sec. Wind In Sun. |
Code Word | Phase Conductor | Bare Neutral Messenger | Weight Per 1000 ft. (lbs.) | Allowable Ampacity+ | ||||||
Size (AWG or kcmil) | Stranding | Insul. Thick. (mils) | Size (AWG) | Strand- ing | Rated Strength (lbs.) | XLP | POLY | XLP | POLY | |
ACSR NEUTRAL-MESSENGER | ||||||||||
Setter | 6 | 1 | 45 | 6 | 6/1 | 1190 | 72 | 72 | 85 | 70 |
Shepherd | 6 | 7 | 45 | 6 | 6/1 | 1190 | 75 | 75 | 85 | 70 |
Eskimo | 4 | 1 | 45 | 4 | 6/1 | 1860 | 110 | 110 | 115 | 90 |
Terrier | 4 | 7 | 45 | 4 | 6/1 | 1860 | 115 | 115 | 150 | 120 |
Chow | 2 | 7 | 45 | 2 | 6/1 | 2850 | 176 | 176 | 150 | 120 |
Bull | 1/0 | 9 | 60 | 1/0 | 6/1 | 4380 | 280 | 280 | 205 | 160 |
* Code words for XLP insulated products are formed by adding "/XLP" to the conventional code words above (e.g.-Chihuahua/XLP).+ Conductor temperature of 90°C for XLP, 75°C for Poly; ambient temperature of 40°C; emissivity 0.9; 2 ft./sec. wind in sun. |
We are China Overhead Transmission Aluminium Cable Duplex Service Drop ABC Cable manufacture and supplier,You can get more details with Email,you will get cheap price or factory price.
Get Latest Price Request a quote
Popular ABC Cables Products
ABC Cables Overhead Aerial Bundle Cable
NFC 33-209 Aerial Bundled Cables 3X70+54.6+1X16 ABC Cable
Overhead Transmission Line ABC Aerial Bunched Cables
Rhvs Aluminium 12/20 Kv XLPE Insulated Overhead A2xs2yt Cable
Caai-S Cables Autoportantes Multi-Conductores ABC Cable
Shepherd Core XLPE Insulated Overhead ABC Cable
Popular Aerial Bundled Cable Products
Overhead XLPE/PE/PVC Insualted Aluminium Conductor Cable
Low Voltage Twisted 4X16mm2 NF2X Service Cable for Overhead Line
XLPE Insulated Aluminium Overhead Cable
0.6/1 Kv LV Aerial Bundled Cable 1 Core Phase 16mm2 AAC 16mm2 Bare
0.6/1kv Al XLPE/Aerial Bundled/ABC Cable for Aluminum
0.6/1kv XLPE Insulation Aerial Bundled Cable ABC Cable
Popular jytopcable Products
500V 6mm Twin and Earth Cable, Twin & Earth Cable
600V Ttu Cable 8 AWG Cable Ttu
Mv Copper Conductor XLPE Insulated Power Cable for Single Core
Low Voltage Aerial Bundled Cable Triplex ABC Cable for Overhead Transmission
PVC/XLPE Insulated Power Cable Professional Supplier
0.6/1kv PVC Insulated and Sheath Power Cable with 4+1 Core
Popular Overhead Cable Products
Quadruplex Service Drop, Aluminum Wire, ABC Cable
11kv ABC Aluminium Overhead Cable by Manumfactory of Henan Jinshui
Jlha1 Jlha2 Jlha3 Jlha4 AAAC Various Voltage Levels All Aluminum Alloy Conductor Aerial Bundle Cable
XLPE Cable Bare Overhead Aluminum AAC Conductor
Low Voltage Aluminium Conductor AAC/ABC Cable Aerial Bundle Cable Overhead Cable
Overhead Aluminum Triplex Service Drop Cable
Tags: ABC Cables, Aerial Bundled Cable, jytopcable, Overhead Cable