Subway XLPE Insulated PVC Sheathed Copper Electric Wire Power Cable
Subway XLPE Insulated PVC Sheathed Copper Electric Wire Power Cable image
Get Latest Price Request a quote
Quick Details
Product Details
Tel: 0086 532 85611663 Phone: 0086 15192706553
__________________________________________________________________________________________
Product Description
Low Voltage Cable
1. Application
The cable is used in electric transmission and distribution system operating at AC rated voltage up to and including 1.8/3 KV
2. Operating Characteristic
1) The rated voltage U0/U of cable is 0.6/1KV.
2) The long time allowable working temperature of conductor is 70 °C FOR cable with PVC insulation, 90 °C for cable with XLPE insulation.
3) The cable laying temperature is not less than 0°C, and the allowable bending radius of a cable is not less 20 times than cable overall diameter for single core unarmored cable, 15 times of that for single core armored, 12 times of that for 3 cores armored cable.
2. Construction
3. Cores and Nominal Cross Section Area:
| Rated voltage 0.6/1kV Single core Basic parameter of Power Cable | |||||||||||
| Nominal cross section mm2 | Thickness of insulation mm | YJV,YJLV | Approximate weight of cable kg/km | Approximate weight of cable kg/km | |||||||
| Thickness of sheath mm | Approx. overall diameter of cable mm | YJV | YJLV | Inner covering mm | Thickness of steel tape mm | Thickness of sheath mm | Approx. overall diameter of cable mm | YJV62 | YJLV62 | ||
| 1.5 | 0.7 | 0.7 | 5.6 | 45 | 35 | ||||||
| 2.5 | 0.7 | 0.7 | 6.0 | 56 | 41 | ||||||
| 4 | 0.7 | 0.7 | 6.5 | 74 | 49 | ||||||
| 6 | 0.7 | 0.7 | 7.0 | 95 | 59 | ||||||
| 10 | 0.7 | 0.7 | 8.2 | 139 | 79 | ||||||
| 16 | 0.7 | 0.7 | 9.1 | 197 | 102 | ||||||
| 25 | 0.9 | 0.9 | 10.6 | 293 | 143 | 0.9 | 0.2 | 1.8 | 14.0 | 451 | 301 |
| 35 | 0.9 | 0.9 | 11.6 | 386 | 178 | 0.9 | 0.2 | 1.8 | 15.0 | 558 | 349 |
| 50 | 1.0 | 1.0 | 13.0 | 507 | 225 | 0.9 | 0.2 | 1.8 | 16.4 | 698 | 416 |
| 70 | 1.1 | 1.1 | 14.9 | 708 | 300 | 0.9 | 0.2 | 1.8 | 18.3 | 926 | 519 |
| 95 | 1.1 | 1.1 | 16.8 | 959 | 394 | 0.9 | 0.2 | 1.8 | 20.0 | 1194 | 628 |
| 120 | 1.2 | 1.2 | 18.5 | 1193 | 479 | 0.9 | 0.2 | 1.8 | 21.7 | 1450 | 737 |
| 150 | 1.4 | 1.4 | 20.6 | 1470 | 590 | 0.9 | 0.2 | 1.8 | 23.6 | 1745 | 865 |
| 185 | 1.6 | 1.6 | 22.8 | 1831 | 730 | 0.9 | 0.2 | 1.8 | 25.6 | 2122 | 1021 |
| 240 | 1.7 | 1.7 | 25.7 | 2380 | 933 | 0.9 | 0.2 | 1.9 | 28.5 | 2706 | 1259 |
| 300 | 1.8 | 1.8 | 28.3 | 2960 | 1144 | 0.9 | 0.2 | 1.9 | 30.9 | 3304 | 1488 |
| 400 | 2.0 | 2.0 | 31.3 | 3755 | 1433 | 1.2 | 0.5 | 2.1 | 35.9 | 4494 | 2173 |
| Rated voltage 0.6/1kV Two cores Basic parameter of Power Cable | |||||||||||
| Nominal cross section mm2 | Thickness of insulation mm | YJV,YJLV | Approximate weight of cable kg/km | Approximate weight of cable kg/km | |||||||
| Thickness of sheath mm | Approx. overall diameter of cable mm | YJV | YJLV | Inner covering mm | Thickness of steel tape mm | Thickness of sheath mm | Approx. overall diameter of cable mm | YJV62 | YJLV62 | ||
| 1.5 | 0.7 | 1.8 | 10.2 | 114 | 96 | 0.9 | 0.2 | 1.8 | 12.8 | 232 | 214 |
| 2.5 | 0.7 | 1.8 | 11.0 | 141 | 111 | 0.9 | 0.2 | 1.8 | 13.6 | 269 | 238 |
| 4 | 0.7 | 1.8 | 12.0 | 181 | 132 | 0.9 | 0.2 | 1.8 | 14.6 | 320 | 271 |
| 6 | 0.7 | 1.8 | 13.0 | 228 | 156 | 0.9 | 0.2 | 1.8 | 15.6 | 379 | 306 |
| 10 | 0.7 | 1.8 | 15.4 | 331 | 211 | 0.9 | 0.2 | 1.8 | 18.0 | 509 | 389 |
| 16 | 0.7 | 1.8 | 17.2 | 458 | 268 | 0.9 | 0.2 | 1.8 | 19.8 | 657 | 467 |
| 25 | 0.9 | 1.8 | 20.2 | 672 | 371 | 0.9 | 0.2 | 1.8 | 22.8 | 905 | 604 |
| 35 | 0.9 | 1.8 | 22.2 | 873 | 455 | 0.9 | 0.2 | 1.8 | 24.8 | 1130 | 712 |
| 50 | 1.0 | 1.8 | 25.0 | 1140 | 574 | 0.9 | 0.2 | 1.8 | 27.6 | 1428 | 863 |
| 70 | 1.1 | 1.9 | 29.0 | 1592 | 775 | 1.2 | 0.2 | 2.0 | 33.6 | 2262 | 1445 |
| 95 | 1.1 | 2.0 | 32.6 | 2134 | 1000 | 1.2 | 0.2 | 2.2 | 37.4 | 2899 | 1765 |
| 120 | 1.2 | 2.1 | 36.2 | 2660 | 1229 | 1.2 | 0.5 | 2.3 | 41.0 | 3504 | 2074 |
| 150 | 1.4 | 2.3 | 40.4 | 3287 | 1522 | 1.2 | 0.5 | 2.4 | 45.0 | 4202 | 2437 |
| 185 | 1.6 | 2.4 | 44.6 | 4073 | 1864 | 1.2 | 0.5 | 2.5 | 49.2 | 5079 | 2870 |
| 240 | 1.7 | 2.6 | 50.4 | 5287 | 2384 | 1.4 | 0.5 | 2.8 | 55.6 | 6457 | 3554 |
| 300 | 1.8 | 2.8 | 55.6 | 6567 | 2925 | 1.4 | 0.5 | 2.9 | 60.6 | 7822 | 4180 |
| 400 | 2.0 | 2.9 | 61.4 | 8279 | 3622 | 1.4 | 0.5 | 3.1 | 66.6 | 9692 | 5034 |
| Rated voltage 0.6/1kV Three cores Basic parameter of Power Cable | |||||||||||
| Nominal cross section mm2 | Thickness of insulation mm | YJV,YJLV | Approximate weight of cable kg/km | Approximate weight of cable kg/km | |||||||
| Thickness of sheath mm | Approx. overall diameter of cable mm | YJV | YJLV | Inner covering mm | Thickness of steel tape mm | Thickness of sheath mm | Approx. overall diameter of cable mm | YJV62 | YJLV62 | ||
| 1.5 | 0.7 | 1.8 | 10.7 | 135 | 107 | 0.9 | 0.2 | 1.8 | 13.3 | 259 | 231 |
| 2.5 | 0.7 | 1.8 | 11.5 | 171 | 125 | 0.9 | 0.2 | 1.8 | 14.1 | 304 | 259 |
| 4 | 0.7 | 1.8 | 12.6 | 225 | 152 | 0.9 | 0.2 | 1.8 | 15.2 | 370 | 297 |
| 6 | 0.7 | 1.8 | 13.7 | 291 | 182 | 0.9 | 0.2 | 1.8 | 16.3 | 449 | 341 |
| 10 | 0.7 | 1.8 | 16.3 | 429 | 250 | 0.9 | 0.2 | 1.8 | 18.9 | 618 | 438 |
| 16 | 0.7 | 1.8 | 18.2 | 609 | 324 | 0.9 | 0.2 | 1.8 | 20.8 | 820 | 534 |
| 25 | 0.9 | 1.8 | 21.4 | 907 | 455 | 0.9 | 0.2 | 1.8 | 24.0 | 1154 | 703 |
| 35 | 0.9 | 1.8 | 23.6 | 1194 | 567 | 0.9 | 0.2 | 1.8 | 26.2 | 1466 | 840 |
| 50 | 1.0 | 1.8 | 26.6 | 1570 | 722 | 0.9 | 0.2 | 1.9 | 29.4 | 1891 | 1042 |
| 70 | 1.1 | 1.9 | 30.9 | 2208 | 983 | 1.2 | 0.2 | 2.1 | 35.7 | 2936 | 1711 |
| 95 | 1.1 | 2.1 | 35.0 | 2995 | 1294 | 1.2 | 0.5 | 2.2 | 39.6 | 3794 | 2093 |
| 120 | 1.2 | 2.2 | 38.8 | 3741 | 1595 | 1.2 | 0.5 | 2.4 | 43.6 | 4642 | 2496 |
| 150 | 1.4 | 2.3 | 43.1 | 4601 | 1953 | 1.2 | 0.5 | 2.5 | 47.9 | 5598 | 2950 |
| 185 | 1.6 | 2.5 | 47.8 | 5738 | 2425 | 1.4 | 0.5 | 2.7 | 53.0 | 6851 | 3538 |
| 240 | 1.7 | 2.7 | 54.0 | 7462 | 3107 | 1.4 | 0.5 | 2.9 | 59.2 | 8711 | 4356 |
| 300 | 1.8 | 2.9 | 59.6 | 9283 | 3820 | 1.4 | 0.5 | 3.1 | 64.8 | 10655 | 5192 |
| 400 | 2.0 | 3.1 | 66.0 | 11771 | 4786 | 1.4 | 0.5 | 3.3 | 71.2 | 13284 | 6299 |
| Rated voltage 0.6/1kV Four cores Basic parameter of Power Cable | |||||||||||
| Nominal cross section mm2 | Thickness of insulation mm | YJV,YJLV | Approximate weight of cable kg/km | Approximate weight of cable kg/km | |||||||
| Thickness of sheath mm | Approx. overall diameter of cable mm | YJV | YJLV | Inner covering mm | Thickness of steel tape mm | Thickness of sheath mm | Approx. overall diameter of cable mm | YJV62 | YJLV62 | ||
| 1.5 | 0.7 | 1.8 | 11.4 | 160 | 123 | 0.9 | 0.2 | 1.8 | 14.0 | 292 | 255 |
| 2.5 | 0.7 | 1.8 | 12.4 | 207 | 147 | 0.9 | 0.2 | 1.8 | 15.0 | 351 | 290 |
| 4 | 0.7 | 1.8 | 13.6 | 277 | 179 | 0.9 | 0.2 | 1.8 | 16.2 | 434 | 337 |
| 6 | 0.7 | 1.8 | 14.8 | 362 | 217 | 0.9 | 0.2 | 1.8 | 17.4 | 533 | 389 |
| 10 | 0.7 | 1.8 | 17.7 | 542 | 302 | 0.9 | 0.2 | 1.8 | 20.3 | 746 | 507 |
| 16 | 0.7 | 1.8 | 19.8 | 777 | 396 | 0.9 | 0.2 | 1.8 | 22.4 | 1005 | 625 |
| 25 | 0.9 | 1.8 | 23.5 | 1169 | 566 | 0.9 | 0.2 | 1.8 | 26.1 | 1440 | 838 |
| 35 | 0.9 | 1.8 | 25.9 | 1546 | 710 | 0.9 | 0.2 | 1.9 | 28.7 | 1858 | 1022 |
| 50 | 1.0 | 1.9 | 29.5 | 2054 | 923 | 1.2 | 0.2 | 2.1 | 34.3 | 2751 | 1620 |
| 70 | 1.1 | 2.1 | 34.4 | 2909 | 1275 | 1.2 | 0.2 | 2.2 | 39.0 | 3695 | 2061 |
| 95 | 1.1 | 2.2 | 38.8 | 3930 | 1661 | 1.2 | 0.5 | 2.4 | 43.6 | 4831 | 2563 |
| 120 | 1.2 | 2.3 | 43.1 | 4913 | 2051 | 1.2 | 0.5 | 2.5 | 47.9 | 5909 | 3048 |
| 150 | 1.4 | 2.5 | 48.0 | 6067 | 2537 | 1.4 | 0.5 | 2.7 | 53.2 | 7184 | 3654 |
| 185 | 1.6 | 2.7 | 53.3 | 7566 | 3148 | 1.4 | 0.5 | 2.8 | 58.3 | 8772 | 4355 |
| 240 | 1.7 | 2.9 | 60.2 | 9839 | 4033 | 1.4 | 0.5 | 3.1 | 65.4 | 11225 | 5419 |
| 300 | 1.8 | 3.1 | 66.4 | 12242 | 4957 | 1.4 | 0.5 | 3.3 | 71.6 | 13764 | 6479 |
| 400 | 2.0 | 3.3 | 73.5 | 15526 | 6212 | 1.4 | 0.5 | 3.5 | 78.7 | 17205 | 7891 |
| Rated voltage 0.6/1kV Five cores Basic parameter of Power Cable | |||||||||||
| Nominal cross section mm2 | Thickness of insulation mm | YJV,YJLV | Approximate weight of cable kg/km | Approximate weight of cable kg/km | |||||||
| Thickness of sheath mm | Approx. overall diameter of cable mm | YJV | YJLV | Inner covering mm | Thickness of steel tape mm | Thickness of sheath mm | Approx. overall diameter of cable mm | YJV62 | YJLV62 | ||
| 1.5 | 0.7 | 1.8 | 12.2 | 186 | 140 | 0.9 | 0.2 | 1.8 | 14.8 | 328 | 281 |
| 2.5 | 0.7 | 1.8 | 13.3 | 244 | 168 | 0.9 | 0.2 | 1.8 | 15.9 | 398 | 322 |
| 4 | 0.7 | 1.8 | 14.6 | 329 | 207 | 0.9 | 0.2 | 1.8 | 17.2 | 498 | 376 |
| 6 | 0.7 | 1.8 | 16.0 | 434 | 254 | 0.9 | 0.2 | 1.8 | 18.6 | 619 | 439 |
| 10 | 0.7 | 1.8 | 19.2 | 655 | 356 | 0.9 | 0.2 | 1.8 | 21.8 | 877 | 578 |
| 16 | 0.7 | 1.8 | 21.7 | 948 | 472 | 0.9 | 0.2 | 1.8 | 24.3 | 1199 | 723 |
| 25 | 0.9 | 1.8 | 25.7 | 1432 | 679 | 0.9 | 0.2 | 1.9 | 28.5 | 1742 | 989 |
| 35 | 0.9 | 1.9 | 28.6 | 1914 | 869 | 0.9 | 0.2 | 2.0 | 31.4 | 2257 | 1213 |
| 50 | 1.0 | 2.0 | 32.6 | 2546 | 1131 | 1.2 | 0.2 | 2.2 | 37.4 | 3310 | 1896 |
| 70 | 1.1 | 2.2 | 38.1 | 3607 | 1565 | 1.2 | 0.5 | 2.3 | 42.7 | 4473 | 2431 |
| 95 | 1.1 | 2.3 | 42.9 | 4876 | 2040 | 1.2 | 0.5 | 2.5 | 47.7 | 5868 | 3032 |
| 120 | 1.2 | 2.5 | 47.9 | 6120 | 2543 | 1.4 | 0.5 | 2.7 | 53.1 | 7235 | 3658 |
| 150 | 1.4 | 2.7 | 53.4 | 7556 | 3143 | 1.4 | 0.5 | 2.8 | 58.4 | 8765 | 4352 |
| 185 | 1.6 | 2.9 | 59.2 | 9419 | 3897 | 1.4 | 0.5 | 3.0 | 64.2 | 10752 | 5230 |
| 240 | 1.7 | 3.1 | 66.9 | 12249 | 4992 | 1.4 | 0.5 | 3.3 | 72.1 | 13783 | 6525 |
| 300 | 1.8 | 3.4 | 74.0 | 15273 | 6168 | 1.4 | 0.5 | 3.5 | 79.0 | 16925 | 7820 |
| 400 | 2.0 | 3.6 | 82.0 | 19369 | 7726 | 1.4 | 0.5 | 3.8 | 88.4 | 22080 | 10437 |
| Rated voltage 0.6/1kV 3+1 cores Basic parameter of Power Cable | |||||||||||
| Nominal cross section mm2 | Thickness of insulation mm | YJV,YJLV | Approximate weight of cable kg/km | Approximate weight of cable kg/km | |||||||
| Thickness of sheath mm | Approx. overall diameter of cable mm | YJV | YJLV | Inner covering mm | Thickness of steel tape mm | Thickness of sheath mm | Approx. overall diameter of cable mm | YJV62 | YJLV62 | ||
| 2.5/1.5 | 0.7/0.7 | 1.8 | 12.4 | 198 | 143 | 0.9 | 0.2 | 1.8 | 15.0 | 342 | 287 |
| 4/2.5 | 0.7/0.7 | 1.8 | 13.6 | 262 | 174 | 0.9 | 0.2 | 1.8 | 16.2 | 420 | 332 |
| 6/4 | 0.7/0.7 | 1.8 | 14.8 | 343 | 211 | 0.9 | 0.2 | 1.8 | 17.4 | 515 | 382 |
| 10/6 | 0.7/0.7 | 1.8 | 17.7 | 506 | 290 | 0.9 | 0.2 | 1.8 | 20.3 | 710 | 495 |
| 16/10 | 0.7/0.7 | 1.8 | 19.8 | 724 | 378 | 0.9 | 0.2 | 1.8 | 22.4 | 953 | 607 |
| 25/16 | 0.9/0.7 | 1.8 | 23.5 | 1083 | 536 | 0.9 | 0.2 | 1.8 | 26.1 | 1354 | 807 |
| 35/16 | 0.9/0.7 | 1.8 | 25.3 | 1371 | 649 | 0.9 | 0.2 | 1.9 | 28.1 | 1676 | 954 |
| 50/25 | 1.0/0.9 | 1.9 | 28.8 | 1852 | 853 | 0.9 | 0.2 | 2.0 | 31.6 | 2198 | 1199 |
| 70/35 | 1.1/0.9 | 2.0 | 33.5 | 2593 | 1158 | 1.2 | 0.2 | 2.2 | 38.3 | 3378 | 1944 |
| 95/50 | 1.1/1.0 | 2.2 | 37.9 | 3506 | 1522 | 1.2 | 0.5 | 2.3 | 42.5 | 4367 | 2383 |
| 120/70 | 1.2/1.1 | 2.3 | 42.1 | 4452 | 1897 | 1.2 | 0.5 | 2.5 | 46.9 | 5425 | 2871 |
| 150/70 | 1.4/1.1 | 2.5 | 46.9 | 5361 | 2305 | 1.4 | 0.5 | 2.6 | 51.9 | 6430 | 3373 |
| 185/95 | 1.6/1.1 | 2.6 | 51.8 | 6732 | 2851 | 1.4 | 0.5 | 2.8 | 57.0 | 7933 | 4053 |
| 240/120 | 1.7/1.2 | 2.9 | 58.8 | 8740 | 3670 | 1.4 | 0.5 | 3.0 | 63.8 | 10065 | 4995 |
| 300/150 | 1.8/1.4 | 3.1 | 64.8 | 10850 | 4504 | 1.4 | 0.5 | 3.2 | 69.8 | 12304 | 5958 |
| 400/185 | 2.0/1.6 | 3.3 | 71.8 | 13718 | 5628 | 1.4 | 0.5 | 3.5 | 77.0 | 15359 | 7269 |
| Rated voltage 0.6/1kV 3+2 cores Basic parameter of Power Cable | |||||||||||
| Nominal cross section mm2 | Thickness of insulation mm | YJV,YJLV | Approximate weight of cable kg/km | Approximate weight of cable kg/km | |||||||
| Thickness of sheath mm | Approx. overall diameter of cable mm | YJV | YJLV | Inner covering mm | Thickness of steel tape mm | Thickness of sheath mm | Approx. overall diameter of cable mm | YJV62 | YJLV62 | ||
| 2.5/1.5 | 0.7/0.7 | 1.8 | 13.3 | 225 | 161 | 0.9 | 0.2 | 1.8 | 15.9 | 379 | 315 |
| 4/2.5 | 0.7/0.7 | 1.8 | 14.6 | 300 | 197 | 0.9 | 0.2 | 1.8 | 17.2 | 469 | 366 |
| 6/4 | 0.7/0.7 | 1.8 | 16.0 | 398 | 241 | 0.9 | 0.2 | 1.8 | 18.6 | 583 | 426 |
| 10/6 | 0.7/0.7 | 1.8 | 19.2 | 584 | 332 | 0.9 | 0.2 | 1.8 | 21.8 | 806 | 554 |
| 16/10 | 0.7/0.7 | 1.8 | 21.8 | 844 | 439 | 0.9 | 0.2 | 1.8 | 24.4 | 1096 | 691 |
| 25/16 | 0.9/0.7 | 1.8 | 25.7 | 1262 | 620 | 0.9 | 0.2 | 1.9 | 28.5 | 1572 | 930 |
| 35/16 | 0.9/0.7 | 1.8 | 27.5 | 1557 | 740 | 0.9 | 0.2 | 1.9 | 30.3 | 1889 | 1072 |
| 50/25 | 1.0/0.9 | 2.0 | 31.6 | 2148 | 998 | 1.2 | 0.2 | 2.1 | 36.2 | 2873 | 1724 |
| 70/35 | 1.1/0.9 | 2.1 | 36.7 | 2993 | 1350 | 1.2 | 0.2 | 2.3 | 41.5 | 3849 | 2206 |
| 95/50 | 1.1/1.0 | 2.3 | 41.5 | 4037 | 1770 | 1.2 | 0.5 | 2.4 | 46.1 | 4976 | 2709 |
| 120/70 | 1.2/1.1 | 2.4 | 46.1 | 5186 | 2223 | 1.4 | 0.5 | 2.6 | 51.3 | 6262 | 3299 |
| 150/70 | 1.4/1.1 | 2.6 | 51.5 | 6133 | 2669 | 1.4 | 0.5 | 2.8 | 56.7 | 7328 | 3863 |
| 185/95 | 1.6/1.1 | 2.8 | 57.1 | 7789 | 3341 | 1.4 | 0.5 | 3.0 | 62.3 | 9106 | 4658 |
| 240/120 | 1.7/1.2 | 3.0 | 64.5 | 10040 | 4255 | 1.4 | 0.5 | 3.2 | 69.7 | 11521 | 5736 |
| 300/150 | 1.8/1.4 | 3.3 | 71.3 | 12479 | 5251 | 1.4 | 0.5 | 3.4 | 76.3 | 14074 | 6845 |
| 400/185 | 2.0/1.6 | 3.5 | 79.0 | 15742 | 6547 | 1.4 | 0.5 | 3.7 | 85.4 | 18358 | 9163 |
| Rated voltage 0.6/1kV 4+1 cores Basic parameter of Power Cable | |||||||||||
| Nominal cross section mm2 | Thickness of insulation mm | YJV,YJLV | Approximate weight of cable kg/km | Approximate weight of cable kg/km | |||||||
| Thickness of sheath mm | Approx. overall diameter of cable mm | YJV | YJLV | Inner covering mm | Thickness of steel tape mm | Thickness of sheath mm | Approx. overall diameter of cable mm | YJV62 | YJLV62 | ||
| 2.5/1.5 | 0.7/0.7 | 1.8 | 13.3 | 235 | 165 | 0.9 | 0.2 | 1.8 | 15.9 | 389 | 319 |
| 4/2.5 | 0.7/0.7 | 1.8 | 14.6 | 315 | 202 | 0.9 | 0.2 | 1.8 | 17.2 | 483 | 371 |
| 6/4 | 0.7/0.7 | 1.8 | 16.0 | 416 | 247 | 0.9 | 0.2 | 1.8 | 18.6 | 601 | 432 |
| 10/6 | 0.7/0.7 | 1.8 | 19.2 | 620 | 344 | 0.9 | 0.2 | 1.8 | 21.8 | 842 | 566 |
| 16/10 | 0.7/0.7 | 1.8 | 21.7 | 896 | 455 | 0.9 | 0.2 | 1.8 | 24.3 | 1146 | 706 |
| 25/16 | 0.9/0.7 | 1.8 | 25.7 | 1347 | 650 | 0.9 | 0.2 | 1.9 | 28.5 | 1657 | 960 |
| 35/16 | 0.9/0.7 | 1.9 | 28.2 | 1742 | 811 | 0.9 | 0.2 | 1.9 | 30.8 | 2067 | 1136 |
| 50/25 | 1.0/0.9 | 2.0 | 32.1 | 2347 | 1065 | 1.2 | 0.2 | 2.1 | 36.7 | 3083 | 1802 |
| 70/35 | 1.1/0.9 | 2.2 | 37.5 | 3308 | 1466 | 1.2 | 0.5 | 2.3 | 42.1 | 4161 | 2318 |
| 95/50 | 1.1/1.0 | 2.3 | 42.2 | 4456 | 1905 | 1.2 | 0.5 | 2.5 | 47.0 | 5432 | 2881 |
| 120/70 | 1.2/1.1 | 2.5 | 47.1 | 5663 | 2394 | 1.4 | 0.5 | 2.6 | 52.1 | 6736 | 3466 |
| 150/70 | 1.4/1.1 | 2.7 | 52.6 | 6857 | 2918 | 1.4 | 0.5 | 2.8 | 57.6 | 8048 | 4109 |
| 185/95 | 1.6/1.1 | 2.8 | 58.1 | 8591 | 3606 | 1.4 | 0.5 | 3.0 | 63.3 | 9931 | 4946 |
| 240/120 | 1.7/1.2 | 3.1 | 65.8 | 11159 | 4638 | 1.4 | 0.5 | 3.3 | 71.0 | 12668 | 6146 |
| 300/150 | 1.8/1.4 | 3.3 | 72.6 | 13860 | 5693 | 1.4 | 0.5 | 3.5 | 77.8 | 15518 | 7351 |
| 400/185 | 2.0/1.6 | 3.6 | 80.6 | 17573 | 7154 | 1.4 | 0.5 | 3.8 | 87.0 | 20238 | 9819 |
4. Our Factory
5. Our Honor
6. Contact Details
Jessica Wang | Taifeng Cable Co., Ltd.
Add.: Heda Center, No.177 Tailiu Road, Shibei District, Qingdao, China
Factory Add.: No.1 Taifeng Road, Dacaozhuang Administrative Zone, Xingtai City, Hebei Province, China
Tel: 0086 532 85611663
Phone: 0086 15192706553
Website: taifengcable.en.
We are China Subway XLPE Insulated PVC Sheathed Copper Electric Wire Power Cable manufacture and supplier,You can get more details with Email,you will get cheap price or factory price.
Get Latest Price Request a quote
Popular Low Voltage Cable Products
Steel Wire Armoured Cable Cu/Al Conductor XLPE/PVC Insulation PVC Sheath 95mm Aluminium Cable Price
450V, 600V PVC Insulated Cable
BS 6346 Aluminum PVC Swa PVC Power Cable
Distribution Lines Cu (Al) Conductor Low Voltage PVC Insulated Steel Wire Armoured Cable
Copper PVC Cable LV (Low Voltage) Aluminium Cable
Popular PVC Sheathed Cable Products
XLPE Swa PVC Power Supply Cable Armoured 4 Core Power Cable
Copper Conductor XLPE Insulated PVC Sheathed Swa Armoured Power Cable
95mm 120mm XLPE Insulated 3 Core Low Voltage Power Cable
0.6/1kv PVC Insulated and Sheathed Copper/Aluminum Power Cable with IEC Standard
Low Voltage XLPE Insulated PVC Sheathed Swa Copper Electric Wire
Low Voltage XLPE Insulated PVC Sheathed Swa Copper Power Cable
Popular taifengcable Products
Hv Stranded Copper Conductor Sta/Swa Armored XLPE Insulated PVC Cable
Muti Core PVC Insulated Sheathed Flexible Copper Electric Control Cable
Security Fire Proof Resistance Flame Retardance Copper Electric Power Cable
0.6/1kv 3+1 Core Aluminum Conductor XLPE Insulated Overhead Aerial Bundled Cable
Aluminum Alloy Steel Reinforced Overhead Power Transmission Line ABC Cable
Low Voltage Chemical Plants Refinery Power Cable XLPE Insulation Steel Wire Armoured Flame Retardant
Popular XLPE Insulated Cable Products
Armoured Mine Cables Made in Jinshui
XLPE Epr Insulated 25kv Insulated Cable with High Quality
Re-2xy Sway XLPE Insulated Screened and Armoured Instrument Cables
Quadplex 4X185 XLPE Insulated Overhead Aerial Bundled Cable ABC Cable
11kv, 33kv, 66kv Middle Voltage Cable, CE Certificate
Cu/XLPE/Cts/PVC/Awa/PVC, Power Cable, 19/33 Kv, 1/C (BS 6622)