Product Details

Center Break Isolator and double Break Isolator

 

These disconnectors are , no load switching devices
which physically isolate the lines. They are designed for
horizontal outdoor application and can also be designed
for vertical installation. For earthing and closing of
switchyard portions of the installation, the earthing
switches are provided on disconnector. If required.

The following documents were referred to during the preparation of this specification. In case of conflict, the provisions of this specification shall take precedence.
IEC 129:1975: Alternating Current Disconnectors (Isolators) and Earthing Switches
IEC 60694:2002: Common Specifications for High Voltage Switchgear and Controlgear
BS 729: Hot dip galvanized coating on iron and steel articles
IEC62271-102
Isolator (Disconnector) – a mechanical switching device which provides, in the open position, an isolating distance in accordance with Electrical Safety requirements.

SERVICE CONDITIONS
The isolator shall be suitable for continuous operation outdoors in tropical areas at altitudes of up to 2200m above sea level, humidities of up to 90%, average ambient temperature of +30ºC with a minimum of -1ºC and a maximum of +40ºC and heavy saline conditions along the coast.

4.2. DESIGN AND CONSTRUCTION
4.2.1 The Isolator, Solid Link shall be designed and constructed in accordance with IEC 129 and IEC 60694.
4.2.2 The isolating link shall be of the vertical opening, designed for single phase manual operation. It shall be easily removed and replaced by using a portable operating rod.
4.2.3 The isolating link shall incorporate double porcelain insulators to suit voltage requirements and mounted on hot dipped galvanised steel under base suitable for vertical mounting.
4.2.4 The isolating link shall be arranged so that each unit is mounted independently on an angle bracket. It shall be supplied complete with the angle bracket and accessories suitable for mounting on ‘U’ type steel channel. The drawings to be submitted shall indicate all the applicable mounting positions.
4.2.5 The isolator shall be designed such that in fully open position, it shall provide adequate electrical isolation between the contacts on each phase. It shall conform to the requirement as single point isolation for safety.
4.2.6 All steel parts shall be hot dip galvanized to BS 729. The minimum coating of galvanizing required is 80 microns.
4.2.7 The solid link shall be removable from the mounting by use of operating rod.
4.2.8 All current carrying parts of the isolator shall be made of high conductivity material.
4.2.9 The isolator shall be fitted with clamp connectors for Aluminium (ACSR) conductor of Aluminium (ACSR)conductor of up to 18.2mm diameter.

The rating of the complete isolator shall be as follows: –
Rated voltage
36 kV
Rated frequency
50 Hz
Rated lightning impulse withstand voltage
200 kV
Rated power frequency withstand voltage, dry
95 kV
Rated normal current
400 Amps
Rated short time withstand current for 3 sec, min.
18.0 kA
Minimum creepage distance of insulators
900 mm
 

 SOLID LINKS 11KV
 
 
 
 
 

N/O DETAIL   DATA
1 Description   Solid link assembly complete with link
rated at 200A and mounting bracket to PIESA 002. (See Figure 1  to Figure 12 below)
2 System conditions of service
 
 
 
a) nominal Voltage (Un) r.m.s
 
 
 
 
kV
 
 
 
 
11
b) maximum system voltage (Um) r.m.s KV 12
c) earthing   Effective & non effective
d) Frequency Hz 50
3 Site conditions of service
a) altitude
 
m
 
1400
b) Operating Ambient temperature °C 1 to 40
c) Humidity % 85
4 Rating    
a) Nominal voltage kV 11
b) Rated current Solid link  
A
 
200
 
Cut out base
 
A
 
200
5 Electrical components    
a) Insulator material specification   Porcelain
Dielectric strength    
Lightning  impulse withstand (1.2/50) kV 95
Power frequency wet withstand voltage
r.m.s
kV 28
6 Specific creepage distance mm/kV 25

 

 
 

7 General information to be provided
with bid:
Drawings and brochures showing outline and general arrangement
 
 
 
 
Yes/No
 
 
 
 
Yes
  b) Detailed drawings of all items
showing critical tolerances to be provided with bid
Yes/No Yes
8 Previous Type test report/certificate on
complete solid link assembly to be provided with bid
 
Yes/No
 
Yes
10 Routine tests (acceptance tests on
sample
Product) to be provided on delivery
Yes/No Yes
11 Applicable standard   PIESA 002
12 Other applicable standards   NRS 035
SABS IEC 602822
SABS IEC 60186
BS 137 part 2

 

 
 

TRILINKS
 
 
 
Lot 3(a) 11kV with interrupters
 
 
 

N/O DETAIL   DATA
1 TYPE   11kV pre-assembled gang
operated overhead line load break switch complete with expulsion interrupters
2 Mounting configuration   Horizontal
3 Mode of operation   Manually operated pole
mounted linking rod and handle with locking facilities
  a) nominal Voltage (Un) r.m.s kV 11
b) maximum voltage (Um) r.m.s KV 12
c) earthing   Effective & non effective
d) Frequency Hz 50
e) rated current Amp 400
f) Fault closing capacity kA 12.5
4 Site conditions of service
a) altitude
 
metres
 
1400
b) Operating Ambient temperature  
°C
 
1 to +40
c) Relative humidity % 85
5 Electrical components    
a) Insulator material specification   High Temperature Vulcanised
Silicon rubber
b) Cross arm and operating controls materials   Hot dip galvanized steel to
SAN760
Dielectric strength    
Lightning  impulse withstand (1.2/50) kV 95

 

 
 

  Power frequency wet withstand voltage r.m.s KV 28
  Short time current rating 1sec kA 12.5
6 creepage distance mm/kV 25
7 General information to be provided with bid:
Drawings and brochures showing
Outline and general arrangement
 
 
 
Yes/No
 
 
 
Yes
8 Previous Type test report/certificate on complete
assembly to be provided with bid
Yes/No Yes.
9 Routine tests (acceptance tests on sample
 
Product) to be provided on delivery.
Yes/No Yes
10 Applicable standards   IEC62271

 

 
 
FURTHER REQUIREMENTS:
 
Water shall not be able to accumulate on any part of the equipment nor shall any feature introduce moisture into any component.
The design shall incorporate all reasonable precautions and provisions for the safety of personnel concerned with the operation and maintenance of the same.
The current path shall be such that load current shall only flow through high conductive materials such as copper and its alloys. Load current shall not be permitted to flow through ferrous components, springs, or springloaded mechanisms.
All load current paths shall be so designed that the relevant parts of the switch are capable of carrying the specified rated current without exceeding the permitted temperature rise.
 
 
 
SUPPLIMENTARY NOTES
 
Suppliers should give sufficient information including drawings (which must be brief, clear and to the point) on how their switch designs addresses these requirements. Further, Suppliers may offer better alternatives that are of cost benefits to customer, It is therefore imperative that schedule "B" is completed by the tenderer. Any deviations/modifications/alternatives specification must be listed in schedule "C.
 
 

 

 
 
 
 
33kV with interrupters
 
 
 

N/O DETAIL   DATA
1 TYPE   33kV pre-assembled gang
operated overhead line load break switch complete with expulsion interrupters
2 Mounting configuration   Horizontal
3 Mode of operation   Manually operated pole
mounted linking rod and handle with locking facilities
  a) nominal Voltage (Un) r.m.s kV 33
b) maximum voltage (Um) r.m.s KV 36
c) earthing   Effective & non effective
d) Frequency Hz 50
e) rated current Amp 200
f) Fault closing capacity kA 12.5
4 Site conditions of service
a) altitude
 
metres
 
1400
b) Operating Ambient temperature  
°C
 
1 to +40
c) Relative humidity % 85
5 Electrical components    
a) Insulator material specification   High Temperature Vulcanised
Silicon rubber
b) Cross arm and operating controls materials   Hot dip galvanized steel to
SAN760
Dielectric strength    
Lightning  impulse withstand (1.2/50) kV 170
Power frequency wet withstand voltage r.m.s KV 70
  Short time current rating 1sec kA 12.5
6 creepage distance mm/kV 25
7 General information to be provided with bid:    

 

 
 

  Drawings and brochures showing
Outline and general arrangement
 
Yes/No
 
Yes
8 Previous Type test report/certificate on complete
assembly to be provided with bid
Yes/No Yes
9 Routine tests (acceptance tests on sample
 
Product) to be provided on delivery
Yes/No Yes
10 Applicable standards   IEC62271

 

 
 
FURTHER REQUIREMENTS:
 
Water shall not be able to accumulate on any part of the equipment nor shall any feature introduce moisture into any component.
The design shall incorporate all reasonable precautions and provisions for the safety of personnel concerned with the operation and maintenance of the same.
The current path shall be such that load current shall only flow through high conductive materials such as copper and its alloys. Load current shall not be permitted to flow through ferrous components, springs, or springloaded mechanisms.
All load current paths shall be so designed that the relevant parts of the switch are capable of carrying the specified rated current without exceeding the permitted temperature rise.
 
 
 
SUPPLIMENTARY NOTES
 
Suppliers should give sufficient information including drawings (which must be brief, clear and to the point) on how their switch designs addresses these requirements. Further, Suppliers may offer better alternatives that are of cost benefits to custoemr.
 
 
 

 

 
 
 
 
11kV without interrupters
 
 
 
 

N/O DETAIL   DATA
1 TYPE   11kV pre-assembled gang
operated overhead line switch without expulsion interrupters (nonload break switch)
2 Mounting configuration   Horizontal
3 Mode of operation   Manually operated pole
mounted linking rod and handle with locking facilities
  a) nominal Voltage (Un) r.m.s kV 11
b) maximum voltage (Um) r.m.s KV 12
c) earthing   Effective & non effective
d) Frequency Hz 50
e) rated current Amp 400
4 Site conditions of service
a) altitude
 
metres
 
1400
b) Operating Ambient temperature  
°C
 
1 to +40
c) Relative humidity % 85
5 Electrical components    
a) Insulator material specification   High Temperature Vulcanised
Silicon rubber
b) Cross arm and operating controls materials   Hot dip galvanized steel to
SAN760
Dielectric strength    
Lightning  impulse withstand (1.2/50) kV 95
Power frequency wet withstand voltage r.m.s KV 28
  Short time current rating 1sec kA 12.5
6 creepage distance mm/kV 25
7 General information to be provided with bid:    

 

 
 

  Drawing and brochures showing
Outline and general arrangement
 
Yes/No
 
Yes
8 Previous Type test report/certificate on complete
assembly to be provided with bid
Yes/No Yes
9 Routine tests (acceptance tests on sample
 
Product) to be provided on delivery
Yes/No Yes
10 Applicable standards   IEC62271

 

 
 
FURTHER REQUIREMENTS:
 
Water shall not be able to accumulate on any part of the equipment nor shall any feature introduce moisture into any component.
The design shall incorporate all reasonable precautions and provisions for the safety of personnel concerned with the operation and maintenance of the same.
The current path shall be such that load current shall only flow through high conductive materials such as copper and its alloys. Load current shall not be permitted to flow through ferrous components, springs, or springloaded mechanisms.
All load current paths shall be so designed that the relevant parts of the switch are capable of carrying the specified rated current without exceeding the permitted temperature rise.
 
 
 
SUPPLIMENTARY NOTES
 
Suppliers should give sufficient information including drawings (which must be brief, clear and to the point) on how their switch designs addresses these requirements. Further, Suppliers may offer better alternatives that are of cost benefits to
 

 

 
 
 
 
 
33kV without interrupters
 
 

N/O DETAIL   DATA
1 TYPE   33kV pre-assembled gang
operated overhead line switch without expulsion interrupters (nonload break switch)
2 Mounting configuration   Horizontal
3 Mode of operation   Manually operated pole
mounted linking rod and handle with locking facilities
  a) nominal Voltage (Un) r.m.s kV 33
b) maximum voltage (Um) r.m.s KV 36
c) earthing   Effective & non effective
d) Frequency Hz 50
e) rated current Amp 200
4 Site conditions of service
a) altitude
 
metres
 
1400
b) Operating Ambient temperature  
°C
 
1 to +40
c) Relative humidity % 85
5 Electrical components    
a) Insulator material specification   High Temperature Vulcanised
Silicon rubber
b) Cross arm and operating controls materials   Hot dip galvanized steel to
SAN760
Dielectric strength    
Lightning  impulse withstand (1.2/50) kV 170
Power frequency wet withstand voltage r.m.s KV 70
  Short time current rating 1sec kA 12.5
6 creepage distance mm/kV 25
7 General information to be provided with bid:    

 

 
 

  Drawing and brochures showing
Outline and general arrangement
 
Yes/No
 
Yes
8 Previous Type test report/certificate on complete
assembly to be provided with bid
Yes/No Yes
9 Routine tests (acceptance tests on sample
 
Product) to be provided on delivery
Yes/No Yes
10 Applicable standards   IEC62271

 
 
FURTHER REQUIREMENTS:
 
Water shall not be able to accumulate on any part of the equipment nor shall any feature introduce moisture into any component.
The design shall incorporate all reasonable precautions and provisions for the safety of personnel concerned with the operation and maintenance of the same.
The current path shall be such that load current shall only flow through high conductive materials such as copper and its alloys. Load current shall not be permitted to flow through ferrous components, springs, or springloaded mechanisms.
All load current paths shall be so designed that the relevant parts of the switch are capable of carrying the specified rated current without exceeding the permitted temperature rise.
 
 
 
SUPPLIMENTARY NOTES
 
Suppliers should give sufficient information including drawings (which must be brief, clear and to the point) on how their switch designs addresses these requirements. Further, Suppliers may offer better alternatives that are of cost benefits to.
  load-break disconnector switches
are designed for low-load breaking
overhead MV electrical lines. Equipped
with an air-break technology system
combined with an isolating switch in
series, this device provides visible opening
and great safety in operation.switches are suitable for overhead
distribution networks up to 36 kV, and
especially those requiring a high level of
insulation: • No maintenance required •
Easy pole top mounting • Line works can
be carried in safe conditions thanks to the
visible opening and high level of
insulation • A manual control mechanism
is available with a rod assembly and
padlockable lever • Whip breaking system
• The ISAR-A switch control mechanisms
are equipped with a tumbler spring
system which directly operates the mobile
shaft. The operating speed is not
dependent on the operator • Height of the
pole from 11 to 14 m • Porcelain
insulators as per standard CEI 60273  Technical Characteristics Rated voltage: 24 kV / 36 kV Rated current: 200 A / 400 A Breaking capacity: 80 A Rated peak closing
capacity: 25 kA This equipment is fully compliant with international standard (IEC
62271-103).

We are China Switch Disconnector Manual Operations, Load-Break Disconnector Switches manufacture and supplier,You can get more details with Email,you will get cheap price or factory price.

Get Latest Price Request a quote

Popular Disconnector Switch Products

Outdoor High Voltage 12kv Disconnect Switch Gw9-10W

Insulator 11kv Pin

High-Voltage Disconnector Switch 24kv

24kv Outdoor Pole Mounted Load Disconnector Switch

Hv Removable Isolating Links

Disconnect Switch 33 Kv, 17.5 Ka, 800 - 1250 a Wit, 17.5 Ka, 800 - 1250 a Without Grounding Blade Double Break

Popular Isolator Switch Products

(Fuse Type) Gwr-12/36 Outdoor AC High Voltage Disconnect Switch

High Voltage 33kv Isolator Current 2000A with Earth Switch

High -Voltage Isolate Switch 15kv 400A

Load Break Switch 33kv

High -Voltage Isolate Switch 10kv 200A

12kv Gw4 Outdoor Disconnector Switches

Popular jgtrade1 Products

5/8 "Long Straight Shackle Crillete Recto 5/8

M20 X 450 Eyebolt Nut

Polymer Fuse Cutout, Drop out Fuses 12 Kv 200A

High -Voltage Isolate Switch 10kv 400A

Cut Resistance Gloves, Nitrile Sandy Finishhppe + Dyneemablack 7-11

Polymer Fuse Cutout, Drop out Fuses 15 Kv 200A

Popular Switch Disconnect Products

Switch Disconnect 1 Pole, 15kv, 630A, 50 (60) Hz

Tags: , , ,

FAST AND RELIABLE SERVICE FOR YOUR PROJECT

Contact our trained experts today to find your perfect power solution.

ASK A QUESTION