Transformer Switch Conventional Oil Type on-Load Tap Changer CV
Transformer Switch Conventional Oil Type on-Load Tap Changer CV image
Get Latest Price Request a quote
Basic Info.
Product Description
General
The tap changer type CV is representing a selector switch of tubular design. The switching principle combines
operational features of a diverter switch and of a tap selector.
The tap changer will be fastened to the transformer tank cover by its tap changer head flange (which serves
also for connecting the tap changer to the drive shaft and oil compartment to the oil conservator.)
If required, the tap changer may be equipped with a change-over selector. (The design of the tap changer and
the nomenclature of its main parts can be seen from the installation drawings in the appendix.)
Tap changer models without change-over selector are available up to 14 and with change-over selector up to
27 operating positions.
These operating instructions contain all information to install and operate the following tap changer models
(without/ with change-over selector).
3-phase on-load tap changers for neutral point: CV350Y, S
3-phase on-load tap changers for any connection: CV 350 D, SV 500 D
Single-phase on-load tap changers: CV I 350, CV I 700.
Designation of the tap changer model
1. Highest voltage for equipment : 40.5kV, 72.5 kV.
2. Number of operating positions for tap changer:
Without change-over selector, the number of operating position can be up to 10,12,14 contacts respectively;
with change-over selector, it can be up to 19,23,27 contacts respectively.
3 There are two types of change-over selector, including reversing regulation reresented by W and coarse/fine
regulation represented by G, Mid position no. can be ‘0’ for without change-over selector, ‘1’ or ‘3’ for with
change-over selector.
4. Scope of application
The tap changer is used on power transformer, rectifier transformer and furnace transformer of rated voltage
of 110kV and below, rated current up to 500 A,frequency 50 to 60 Hz. The taps of the transformer can be
changed by the tap changer on load to regulate the output voltage,which is to ensure it is stablized in
the specified range. It is also used to increase or reduce output voltage according to the load requirement
for the purpose of regulation line voltage.
5. Rated application conditions and requirement
1)The tap changer is used in oil, the temperature of the oil must not be higher than 100°C or lower than -25°C.
2)The environmental air temperature of the tap changer must not be higher than 40°C or lower than -25°C
3)When installing the tap changer on the transformer the perpendicularity with the ground level must not be
bigger than 2%.
4)Any serious dust, explosive or corrosive gases must not be present at the installation site of the OLTC.
5)The storage place of the tap changer must be dry without moisture.
Technical data of Type CV On Load Tap Changer
INTRODUCTION OF ON-LOAD TAP CHANGER
OLTC can be divided into 5 big components: the tap changer head cover, the gear mechanism, main shaft, the
oil suction pipe and the oil compartment.
The tap changer head circular cover
The tap changer head cover is made of aluminium alloy by die casting. Gear actuating mechanism, inspection
window,oil and gas drain valves, explosive-proof cover are all on the cover. Oil-resisting sealing ring is used for
the connection between the cover and the flange.
Mechanical operation principle of the tap changer
Spring energy-accumulating mechanism
In the flange to the bottom of the head cover there are gear, grooved wheel, groove shift element and springs
combined up to form a separate mechanism. Its function is to actuate the movement from the motor drive into
the movement of the contacts on the main shaft.
Oil suction pipe
The oil suction pipe is located in the hollow center of main shaft, it can be seen when the gear mechanism is
taken off.It plays a role as oil suction pipe and to act as the positioning fixture of the main shaft.
Moving contact insert
The basic element is the 130 mm insulating tube. There are two groups of contact on the tube. Change over
contact group is at the top and the three identical moving contact groups are at the bottom.
Oil Compartment
There is a die casting aluminium alloy flange at the compartment head. The middle is the 395 insulating cylinder
and at the bottom is the bottom of the insulating cylinder. The oilresisting rubber as sealing ring are used for
the connections of these 3 parts. The function of the oil compartment is to support the fixed contacts of the tap
changer, as well as to separate the OLTC oil from the transformer oil.
Producing:
Our Services
| 1. | Pre sale service |
| a. | make technical solution |
| b. | send quotation, technical data sheet and drawing |
| c. | prepare power transmission plan, testing plan and shipment plan |
| 2. | In sale service |
| a. | supervise the manufacturing schedule totally in accordance with the plan |
| b. | send photos to customer during every manufacturing process(hold point) |
| c. | inform the customer one week before testing. |
| 3. | After sale service |
| a. | installation and commissioning, training the workers |
| b. | quick response within 12 hours any time |
| c. | provide 12 months guarantee period normally. |
FAQ
| 1. Q: | What is your delivery time ? |
| A: | Depend on the type of transformer. |
| 2. Q: | What is your payment term? |
| A: | 30% advance by T/T , 70% before delivery by T/T or L/C or we can discuss about it. |
| 3. Q: | What kind of standard you follow? |
| A: | IEC, ANSI, CSA, GB, etc |
| 4. Q: | What kind of supporting documentation you can provide normally |
| A: | Quotation, outline drawing, manufacturing plan, quality control plan testing plan, financial report, type test report(KEMA, CESI),reference list, etc |
| 5. Q: | What is your normal warranty period? |
| A: | 12 months after transformer operation. |
| 6. Q: | Can u do installation and commission in user’s site? |
| A: | Yes, we can send our installation team to user’s country for service. |
| 7. Q: | Do you have any experience in this kind of transformer? |
| A: | Yes, we can provide reference list for check. |
Our advantages:
Quality Assurance
–From the very beginning, VILLE ensures quality in every step to achieve the best quality.
Experience Sharing
–With more than 30 years’ experience in power industry, VILLE brings you an optimized solution.
Global Service
–Wherever you are, VILLE global network will support and provide you with value.
Quick Response
–In response to your needs without delay, VILLE knows the value of your time.
Thanks for choosing VILLE as your reliable partner and
please trust both of us will create a brilliant future!
/* January 22, 2024 19:08:37 */!function(){function s(e,r){var a,o={};try{e&&e.split(“,”).forEach(function(e,t){e&&(a=e.match(/(.*?):(.*)$/))&&1
We are China Transformer Switch Conventional Oil Type on-Load Tap Changer CV manufacture and supplier,You can get more details with Email,you will get cheap price or factory price.
Get Latest Price Request a quote
Popular cnville Products
Gw5 (GT10) -126D/1600-40 Outdoor AC Hv Disconnector Isolator Switch
Dh15-M-30/10 30kVA Dh Series 10kv/20kv Single Phase Pole Mounted Distribution Transformer
Rod Post Insulators RTV Post Insulator
Zw39-40.5 High Voltage Vacuum Circuit Breaker
Water Cooled Compensator for Transformer/Transformer Water Cooled
Popular Tap Changer for Transformer Products
CVT Vacuum on-Load Tap Changer for Dry Type Transformer Power Transformer Switch
on-Load Tap Changer for Transformer Load Break Switch Tap Changer
Zmd High-Quality on-Load Tap-Changer Below 252kv for Three Phase Neutral Point Voltage Regulation
Wsl Head Motorized off-Circuit Tap Changer for Transformers
off-Circuit Tap Changer for Transformers Distribution Transformer off Load Switch
Vacuum on-Load Tap Changers for Oil Immersed Transformer Switch off Circuit Tap Changer
Popular Transformer Switch Conventional Oil Type on-Load Tap Changer CV Products
Popular transformer tap changer Products
Vacuum on-Load Tap Changer for Voltage Regulating by Change Tap Position
Cm Transformer Switch Conventional Oil Type on-Load Tap Changers Type Cm
10KV TGV II Dry-Type Vacuum On Load Tap Changer Switcher
Wdl off-Circuit Tap Changers for Transformers/ Transformer Switch
off-Circuit Capacity Regulating Tap Changer Circuit Switch
15KV TGV II Dry-Type Vacuum On Load Tap Changer Switcher
Tags: cnville, Tap Changer for Transformer, Transformer Switch Conventional Oil Type on-Load Tap Changer CV, transformer tap changer