21kv High Quality Oxide Zinc Lightning Arrester for Substation
21kv High Quality Oxide Zinc Lightning Arrester for Substation image
Get Latest Price Request a quote
Basic Info.
Product Description
Surge Arrester Series
General
1. Ratings:0.22~500KV (porcelain),0.22~220KV(composite)
2. Application:for protection of power transmission & distribution system from over-voltage.
3. Features:
1)Silicone polymer housing composite metal oxide surge arrester and porcelain housing metal Oxide surge arresters are available.
2)Easy installation and maintenance.
3)Good sealing capability to ensure reliable operation.
4)Protection and reliability of the surge arrester have been greatly enhanced.
Working Condition
1. Ambient air temperature:-40ºC ~+40ºC ;
2. Altitude:<=2000m;
3. Frequency: 48Hz~62Hz;
4. Power frequency voltage applied between terminals of surge arrester must not exceed continuous operating voltage of surge arrerter;
5. Earthquake intensity is less than 8 degree;
6. Max. Wind speed is 35m/s.
Main Techical Parameter
1. Metal oxide Polymer Housing (Gapless) type Surge Arrester for A.C System(5kA series)
Model | Rated voltage (kVr.m.s) | Continuous operating Voltage(KVr.m.s) | Lightening impulse residual voltage under nominal discharge current (<=KVp) | Line discharge class | Creepage distance(mm) | 2ms square wave impulse current withstands(A) | 4/10μhigh current impulse Withstands(KAp) |
YH-5W-6 | 6 | 5.1 | 18 | 320 | 150 | 65 | |
YH-5W-9 | 9 | 7.65 | 27 | 430 | 150 | 65 | |
YH-5W-12 | 12 | 10.2 | 36 | 430 | 150 | 65 | |
YH-5W-15 | 15 | 12.75 | 45 | 530 | 150 | 65 | |
YH-5W-18 | 18 |
15.3 |
54 | 530 | 150 | 65 | |
YH-5W-21 | 21 | 16.8 | 63 | 640 | 150 | 65 | |
YH-5W-24 | 24 | 19.2 | 72 | 640 | 150 | 65 | |
YH-5W-27 | 27 | 21.6 | 81 | 740 | 150 | 65 | |
YH-5W-30 | 30 | 24 | 90 | 890 | 150 | 65 | |
YH-5W-33 | 33 | 26.4 | 99 | 890 | 150 | 65 | |
YH-5W-36 | 36 | 28.8 | 108 | 1115 | 150 | 65 |
2. Metal Oxide Polymer Housing (Gapless) type Surge Arrester for A.C. System (10KA series)
Model | Rated voltage (kVr.m.s) | Continuous operating Voltage(KVr.m.s) | Lightening impulse residual voltage under nominal discharge current (<=KVp) | Line discharge class | Creepage distance(mm) | 2ms square wave impulse current withstands(A) | 4/10μhigh current impulse Withstands(KAp) |
YH-10W-6 | 6 | 5.1 | 18 | 1 | 320 | 250 | 100 |
YH-10W-9 | 9 | 7.65 | 27 | 1 | 430 | 250 | 100 |
YH-10W-12 | 12 | 10.2 | 36 | 1 | 430 | 250 | 100 |
YH-10W-15 | 15 | 12.75 | 45 | 1 | 530 | 250 | 100 |
YH-10W-18 | 18 | 15.3 | 54 | 1 | 530 | 250 | 100 |
YH-10W-21 | 21 | 16.8 | 63 | 1 | 640 | 250 | 100 |
YH-10W-24 | 24 | 19.2 | 72 | 1 | 740 | 250 | 100 |
YH-10W-27 | 27 | 21.6 | 81 | 1 | 740 | 250 | 100 |
YH-10W-30 | 30 | 24 | 90 | 1 | 890 | 250 | 100 |
YH-10W-33 | 33 | 26.4 | 99 | 1 | 890 | 250 | 100 |
YH-10W-36 | 36 | 28.8 | 108 | 1 | 1115 | 250 | 100 |
YH-10W-42 | 42 | 33.6 | 126 | 2 | 1260 | 400 | 100 |
YH-10W-48 | 48 | 39 | 139 | 2 | 1260 | 400 | 100 |
YH-10W-54 | 54 | 42 | 160 | 2 | 1260 | 400 | 100 |
YH-10W-60 | 60 | 48 | 178 | 2 | 1465 | 400 | 100 |
YH-10W-66 | 66 | 52.8 | 196 | 2 | 1465 | 400 | 100 |
YH-10W-72 | 72 | 57 | 214 | 2 | 2255 | 400 | 100 |
YH-10W-84 | 84 | 67.2 | 244 | 2 | 2255 | 400 | 100 |
YH-10W-90 | 90 | 72.5 | 249 | 2 | 2255 | 400 | 100 |
YH-10W-96 | 96 | 75 | 265 | 3 | 3555 | 800 | 100 |
YH-10W-108 | 108 | 84 | 281 | 3 | 3555 | 800 | 100 |
YH-10W-120 | 120 | 96 | 300 | 3 | 4153 | 800 | 100 |
YH-10W-150 | 150 | 120 | 416 | 3 | 5040 | 800 | 100 |
YH-10W-200 | 200 | 156 | 520 | 3 | 7110 | 800 | 100 |
3. Metal Oxide Polymer Housing (Gapless) type Surge Arrester for A.C. System (20KA series)
Model | Rated voltage (kVr.m.s) | Continuous operating Voltage(KVr.m.s) | Lightening impulse residual voltage under nominal discharge current (<=KVp) | Line discharge class | Creepage distance(mm) | 2ms square wave impulse current withstands(A) | 4/10μhigh current impulse Withstands(KAp) |
YH-20W-108 | 108 | 84 | 281 | 3 | 3555 | 800 | 100 |
YH-20W-120 | 120 | 96 | 300 | 3 | 4153 | 800 | 100 |
YH-20W-150 | 150 | 120 | 416 | 3 | 5040 | 800 | 100 |
YH-20W-200 | 200 | 156 | 520 | 3 | 7110 | 800 | 100 |
4. Metal Oxide Porcelain Housing (Gapless) type Surge Arrester for A.C. System (5KA series)
Model | Rated voltage (kVr.m.s) | Continuous operating Voltage(KVr.m.s) | Lightening impulse residual voltage under nominal discharge current (<=KVp) | Line discharge class | Creepage distance(mm) | 2ms square wave impulse current withstands(A) | 4/10μhigh current impulse Withstands(KAp) |
Y5W-6 | 6 | 5.1 | 18 | 280 | 150 | 65 | |
Y5W-9 | 9 | 7.65 | 27 | 320 | 150 | 65 | |
Y5W-12 | 12 | 10.2 | 36 | 320 | 150 | 65 | |
Y5W-15 | 15 | 12.75 | 45 | 450 | 150 | 65 | |
Y5W-18 | 18 |
15.3 |
54 | 450 | 150 | 65 | |
Y5W-21 | 21 | 16.8 | 63 | 450 | 150 | 65 | |
Y5W-24 | 24 | 19.2 | 72 | 510 | 150 | 65 | |
Y5W-27 | 27 | 21.6 | 81 | 510 | 150 | 65 | |
Y5W-30 | 30 | 24 | 90 | 890 | 150 | 65 | |
Y5W-33 | 33 | 26.4 | 99 | 890 | 150 | 65 | |
Y5W-36 | 36 | 28.8 | 108 | 890 | 150 | 65 |
5. Metal Oxide Polymer Housing (Gapless) type Surge Arrester for A.C. System (10KA series)
Model | Rated voltage (kVr.m.s) | Continuous operating Voltage(KVr.m.s) | Lightening impulse residual voltage under nominal discharge current (<=KVp) | Line discharge class | Creepage distance(mm) | 2ms square wave impulse current withstands(A) | 4/10μhigh current impulse Withstands(KAp) |
Y10W-6 | 6 | 5.1 | 18 | 1 | 280 | 250 | 100 |
Y10W-9 | 9 | 7.65 | 27 | 1 | 320 | 250 | 100 |
Y10W-12 | 12 | 10.2 | 36 | 1 | 320 | 250 | 100 |
Y10W-15 | 15 | 12.75 | 45 | 1 | 450 | 250 | 100 |
Y10W-18 | 18 | 15.3 | 54 | 1 | 450 | 250 | 100 |
Y10W-21 | 21 | 16.8 | 63 | 1 | 450 | 250 | 100 |
Y10W-24 | 24 | 19.2 | 72 | 1 | 510 | 250 | 100 |
Y10W-27 | 27 | 21.6 | 81 | 1 | 510 | 250 | 100 |
Y10W-30 | 30 | 24 | 90 | 1 | 890 | 250 | 100 |
Y10W-33 | 33 | 26.4 | 99 | 1 | 890 | 250 | 100 |
Y10W-36 | 36 | 28.8 | 108 | 1 | 890 | 250 | 100 |
Y10W-42 | 42 | 33.6 | 126 | 2 | 1256 | 400 | 100 |
Y10W-48 | 48 | 39 | 139 | 2 | 1256 | 400 | 100 |
Y10W-54 | 54 | 42 | 160 | 2 | 1256 | 400 | 100 |
Y10W-60 | 60 | 48 | 178 | 2 | 1440 | 400 | 100 |
Y10W-66 | 66 | 52.8 | 196 | 2 | 1440 | 400 | 100 |
Y10W-72 | 72 | 57 | 214 | 2 | 1440 | 400 | 100 |
Y10W-84 | 84 | 67.2 | 244 | 2 | 2200 | 400 | 100 |
Y10W-90 | 90 | 72.5 | 249 | 2 | 2200 | 400 | 100 |
Y10W-96 | 96 | 75 | 265 | 3 | 3350 | 800 | 100 |
Y10W-108 | 108 | 84 | 281 | 3 | 3350 | 800 | 100 |
Y10W-120 | 120 | 96 | 300 | 3 | 3948 | 800 | 100 |
Y10W-150 | 150 | 120 | 416 | 3 | 4400 | 800 | 100 |
Y10W-200 | 200 | 156 | 520 | 3 | 6700 | 800 | 100 |
6. Metal Oxide Polymer Housing (Gapless) type Surge Arrester for A.C. System (20KA series)
Model | Rated voltage (kVr.m.s) | Continuous operating Voltage(KVr.m.s) | Lightening impulse residual voltage under nominal discharge current (<=KVp) | Line discharge class | Creepage distance(mm) | 2ms square wave impulse current withstands(A) | 4/10μhigh current impulse Withstands(KAp) |
Y20W-108 | 108 | 84 | 281 | 3 | 3555 | 800 | 100 |
Y20W-120 | 120 | 96 | 300 | 3 | 4106 | 800 | 100 |
Y20W-150 | 150 | 120 | 416 | 3 | 4400 | 800 | 100 |
Y20W-200 | 200 | 156 | 520 | 3 | 6700 | 800 | 100 |
Y20W-444 | 444 | 324 | 1106 | 4 | 17052 | 2000 | 100 |
Note: For details, please refer to the catalogue.
Participate in the exhibition pictures
testing report
We are China 21kv High Quality Oxide Zinc Lightning Arrester for Substation manufacture and supplier,You can get more details with Email,you will get cheap price or factory price.
Get Latest Price Request a quote
Popular High Quality Oxide Zinc Lightning Arrester Products
36kv High Quality Oxide Zinc Lightning Arrester for Substation
12kv High Quality Oxide Zinc Lightning Arrester for Substation
27kv High Quality Oxide Zinc Lightning Arrester for Substation
24kv High Quality Oxide Zinc Lightning Arrester for Substation
18kv High Quality Oxide Zinc Lightning Arrester for Substation
9kv High Quality Oxide Zinc Lightning Arrester for Substation
Popular Lightning Arrester Products
11kv Porcelain Surge Arrester/Lighting Arrester
Stainless Steel Telescopic Fence (belt type)
Polymer Housed ZnO 36kv 10ka Surge Arrester Moa
24kv Polymeric Housed Metal-Oxide Lightning Arrester Without Gaps
Popular Oxide Zinc Lightning Arrester for Substation Products
30kv High Quality Oxide Zinc Lightning Arrester for Substation
33kv High Quality Oxide Zinc Lightning Arrester for Substation
24kv High Quality Oxide Zinc Lightning Arrester for Substation
9kv High Quality Oxide Zinc Lightning Arrester for Substation
12kv High Quality Oxide Zinc Lightning Arrester for Substation
18kv High Quality Oxide Zinc Lightning Arrester for Substation
Popular people Products
15kv Silicone Rubber Polymer Insulator for Support Wire
High Voltage Suspension Composite Insulator
24kv High Voltage Surge Arrester for Distribution Line
60kv High Voltage Electrical Lightning Arrester for Transmission Line
11kv Lightning Arrester (polymer type)
Long Rod Suspension Composite Insulator
Tags: High Quality Oxide Zinc Lightning Arrester, Lightning Arrester, Oxide Zinc Lightning Arrester for Substation, people