33kv High Quality Oxide Zinc Lightning Arrester for Substation
33kv High Quality Oxide Zinc Lightning Arrester for Substation image
Get Latest Price Request a quote
Basic Info.
Product Description
Surge Arrester Series
General
1. Ratings:0.22~500KV (porcelain),0.22~220KV(composite)
2. Application:for protection of power transmission & distribution system from over-voltage.
3. Features:
1)Silicone polymer housing composite metal oxide surge arrester and porcelain housing metal Oxide surge arresters are available.
2)Easy installation and maintenance.
3)Good sealing capability to ensure reliable operation.
4)Protection and reliability of the surge arrester have been greatly enhanced.
Working Condition
1. Ambient air temperature:-40ºC ~+40ºC ;
2. Altitude:<=2000m;
3. Frequency: 48Hz~62Hz;
4. Power frequency voltage applied between terminals of surge arrester must not exceed continuous operating voltage of surge arrerter;
5. Earthquake intensity is less than 8 degree;
6. Max. Wind speed is 35m/s.
Main Techical Parameter
1. Metal oxide Polymer Housing (Gapless) type Surge Arrester for A.C System(5kA series)
Model | Rated voltage (kVr.m.s) | Continuous operating Voltage(KVr.m.s) | Lightening impulse residual voltage under nominal discharge current (<=KVp) | Line discharge class | Creepage distance(mm) | 2ms square wave impulse current withstands(A) | 4/10μhigh current impulse Withstands(KAp) |
YH-5W-6 | 6 | 5.1 | 18 | 320 | 150 | 65 | |
YH-5W-9 | 9 | 7.65 | 27 | 430 | 150 | 65 | |
YH-5W-12 | 12 | 10.2 | 36 | 430 | 150 | 65 | |
YH-5W-15 | 15 | 12.75 | 45 | 530 | 150 | 65 | |
YH-5W-18 | 18 |
15.3 |
54 | 530 | 150 | 65 | |
YH-5W-21 | 21 | 16.8 | 63 | 640 | 150 | 65 | |
YH-5W-24 | 24 | 19.2 | 72 | 640 | 150 | 65 | |
YH-5W-27 | 27 | 21.6 | 81 | 740 | 150 | 65 | |
YH-5W-30 | 30 | 24 | 90 | 890 | 150 | 65 | |
YH-5W-33 | 33 | 26.4 | 99 | 890 | 150 | 65 | |
YH-5W-36 | 36 | 28.8 | 108 | 1115 | 150 | 65 |
2. Metal Oxide Polymer Housing (Gapless) type Surge Arrester for A.C. System (10KA series)
Model | Rated voltage (kVr.m.s) | Continuous operating Voltage(KVr.m.s) | Lightening impulse residual voltage under nominal discharge current (<=KVp) | Line discharge class | Creepage distance(mm) | 2ms square wave impulse current withstands(A) | 4/10μhigh current impulse Withstands(KAp) |
YH-10W-6 | 6 | 5.1 | 18 | 1 | 320 | 250 | 100 |
YH-10W-9 | 9 | 7.65 | 27 | 1 | 430 | 250 | 100 |
YH-10W-12 | 12 | 10.2 | 36 | 1 | 430 | 250 | 100 |
YH-10W-15 | 15 | 12.75 | 45 | 1 | 530 | 250 | 100 |
YH-10W-18 | 18 | 15.3 | 54 | 1 | 530 | 250 | 100 |
YH-10W-21 | 21 | 16.8 | 63 | 1 | 640 | 250 | 100 |
YH-10W-24 | 24 | 19.2 | 72 | 1 | 740 | 250 | 100 |
YH-10W-27 | 27 | 21.6 | 81 | 1 | 740 | 250 | 100 |
YH-10W-30 | 30 | 24 | 90 | 1 | 890 | 250 | 100 |
YH-10W-33 | 33 | 26.4 | 99 | 1 | 890 | 250 | 100 |
YH-10W-36 | 36 | 28.8 | 108 | 1 | 1115 | 250 | 100 |
YH-10W-42 | 42 | 33.6 | 126 | 2 | 1260 | 400 | 100 |
YH-10W-48 | 48 | 39 | 139 | 2 | 1260 | 400 | 100 |
YH-10W-54 | 54 | 42 | 160 | 2 | 1260 | 400 | 100 |
YH-10W-60 | 60 | 48 | 178 | 2 | 1465 | 400 | 100 |
YH-10W-66 | 66 | 52.8 | 196 | 2 | 1465 | 400 | 100 |
YH-10W-72 | 72 | 57 | 214 | 2 | 2255 | 400 | 100 |
YH-10W-84 | 84 | 67.2 | 244 | 2 | 2255 | 400 | 100 |
YH-10W-90 | 90 | 72.5 | 249 | 2 | 2255 | 400 | 100 |
YH-10W-96 | 96 | 75 | 265 | 3 | 3555 | 800 | 100 |
YH-10W-108 | 108 | 84 | 281 | 3 | 3555 | 800 | 100 |
YH-10W-120 | 120 | 96 | 300 | 3 | 4153 | 800 | 100 |
YH-10W-150 | 150 | 120 | 416 | 3 | 5040 | 800 | 100 |
YH-10W-200 | 200 | 156 | 520 | 3 | 7110 | 800 | 100 |
3. Metal Oxide Polymer Housing (Gapless) type Surge Arrester for A.C. System (20KA series)
Model | Rated voltage (kVr.m.s) | Continuous operating Voltage(KVr.m.s) | Lightening impulse residual voltage under nominal discharge current (<=KVp) | Line discharge class | Creepage distance(mm) | 2ms square wave impulse current withstands(A) | 4/10μhigh current impulse Withstands(KAp) |
YH-20W-108 | 108 | 84 | 281 | 3 | 3555 | 800 | 100 |
YH-20W-120 | 120 | 96 | 300 | 3 | 4153 | 800 | 100 |
YH-20W-150 | 150 | 120 | 416 | 3 | 5040 | 800 | 100 |
YH-20W-200 | 200 | 156 | 520 | 3 | 7110 | 800 | 100 |
4. Metal Oxide Porcelain Housing (Gapless) type Surge Arrester for A.C. System (5KA series)
Model | Rated voltage (kVr.m.s) | Continuous operating Voltage(KVr.m.s) | Lightening impulse residual voltage under nominal discharge current (<=KVp) | Line discharge class | Creepage distance(mm) | 2ms square wave impulse current withstands(A) | 4/10μhigh current impulse Withstands(KAp) |
Y5W-6 | 6 | 5.1 | 18 | 280 | 150 | 65 | |
Y5W-9 | 9 | 7.65 | 27 | 320 | 150 | 65 | |
Y5W-12 | 12 | 10.2 | 36 | 320 | 150 | 65 | |
Y5W-15 | 15 | 12.75 | 45 | 450 | 150 | 65 | |
Y5W-18 | 18 |
15.3 |
54 | 450 | 150 | 65 | |
Y5W-21 | 21 | 16.8 | 63 | 450 | 150 | 65 | |
Y5W-24 | 24 | 19.2 | 72 | 510 | 150 | 65 | |
Y5W-27 | 27 | 21.6 | 81 | 510 | 150 | 65 | |
Y5W-30 | 30 | 24 | 90 | 890 | 150 | 65 | |
Y5W-33 | 33 | 26.4 | 99 | 890 | 150 | 65 | |
Y5W-36 | 36 | 28.8 | 108 | 890 | 150 | 65 |
5. Metal Oxide Polymer Housing (Gapless) type Surge Arrester for A.C. System (10KA series)
Model | Rated voltage (kVr.m.s) | Continuous operating Voltage(KVr.m.s) | Lightening impulse residual voltage under nominal discharge current (<=KVp) | Line discharge class | Creepage distance(mm) | 2ms square wave impulse current withstands(A) | 4/10μhigh current impulse Withstands(KAp) |
Y10W-6 | 6 | 5.1 | 18 | 1 | 280 | 250 | 100 |
Y10W-9 | 9 | 7.65 | 27 | 1 | 320 | 250 | 100 |
Y10W-12 | 12 | 10.2 | 36 | 1 | 320 | 250 | 100 |
Y10W-15 | 15 | 12.75 | 45 | 1 | 450 | 250 | 100 |
Y10W-18 | 18 | 15.3 | 54 | 1 | 450 | 250 | 100 |
Y10W-21 | 21 | 16.8 | 63 | 1 | 450 | 250 | 100 |
Y10W-24 | 24 | 19.2 | 72 | 1 | 510 | 250 | 100 |
Y10W-27 | 27 | 21.6 | 81 | 1 | 510 | 250 | 100 |
Y10W-30 | 30 | 24 | 90 | 1 | 890 | 250 | 100 |
Y10W-33 | 33 | 26.4 | 99 | 1 | 890 | 250 | 100 |
Y10W-36 | 36 | 28.8 | 108 | 1 | 890 | 250 | 100 |
Y10W-42 | 42 | 33.6 | 126 | 2 | 1256 | 400 | 100 |
Y10W-48 | 48 | 39 | 139 | 2 | 1256 | 400 | 100 |
Y10W-54 | 54 | 42 | 160 | 2 | 1256 | 400 | 100 |
Y10W-60 | 60 | 48 | 178 | 2 | 1440 | 400 | 100 |
Y10W-66 | 66 | 52.8 | 196 | 2 | 1440 | 400 | 100 |
Y10W-72 | 72 | 57 | 214 | 2 | 1440 | 400 | 100 |
Y10W-84 | 84 | 67.2 | 244 | 2 | 2200 | 400 | 100 |
Y10W-90 | 90 | 72.5 | 249 | 2 | 2200 | 400 | 100 |
Y10W-96 | 96 | 75 | 265 | 3 | 3350 | 800 | 100 |
Y10W-108 | 108 | 84 | 281 | 3 | 3350 | 800 | 100 |
Y10W-120 | 120 | 96 | 300 | 3 | 3948 | 800 | 100 |
Y10W-150 | 150 | 120 | 416 | 3 | 4400 | 800 | 100 |
Y10W-200 | 200 | 156 | 520 | 3 | 6700 | 800 | 100 |
6. Metal Oxide Polymer Housing (Gapless) type Surge Arrester for A.C. System (20KA series)
Model | Rated voltage (kVr.m.s) | Continuous operating Voltage(KVr.m.s) | Lightening impulse residual voltage under nominal discharge current (<=KVp) | Line discharge class | Creepage distance(mm) | 2ms square wave impulse current withstands(A) | 4/10μhigh current impulse Withstands(KAp) |
Y20W-108 | 108 | 84 | 281 | 3 | 3555 | 800 | 100 |
Y20W-120 | 120 | 96 | 300 | 3 | 4106 | 800 | 100 |
Y20W-150 | 150 | 120 | 416 | 3 | 4400 | 800 | 100 |
Y20W-200 | 200 | 156 | 520 | 3 | 6700 | 800 | 100 |
Y20W-444 | 444 | 324 | 1106 | 4 | 17052 | 2000 | 100 |
Note: For details, please refer to the catalogue.
Participate in the exhibition pictures
testing report
We are China 33kv High Quality Oxide Zinc Lightning Arrester for Substation manufacture and supplier,You can get more details with Email,you will get cheap price or factory price.
Get Latest Price Request a quote
Popular High Quality Oxide Zinc Lightning Arrester Products
36kv High Quality Oxide Zinc Lightning Arrester for Substation
18kv High Quality Oxide Zinc Lightning Arrester for Substation
15kv High Quality Oxide Zinc Lightning Arrester for Substation
21kv High Quality Oxide Zinc Lightning Arrester for Substation
12kv High Quality Oxide Zinc Lightning Arrester for Substation
24kv High Quality Oxide Zinc Lightning Arrester for Substation
Popular Lightning Arrester Products
High Voltage Polymeric Cross Arm Insulator Surge Arrester 35kv in Power Zinc Oxide Lighting Arrester
24kv Metal Oxide Lightning Arrester for Overvoltage Protection
220kv Silicon Type Surge Arrester CMA10WS-216/562
High Voltage Polymeric Lightning Arrester
24kv Silicon Type Surge Arrester Cmr5w-24
Porcelain Metal Oxide Lightning Arrester Surge Arrester Moa Y10W-11kv
Popular Oxide Zinc Lightning Arrester for Substation Products
21kv High Quality Oxide Zinc Lightning Arrester for Substation
24kv High Quality Oxide Zinc Lightning Arrester for Substation
30kv High Quality Oxide Zinc Lightning Arrester for Substation
12kv High Quality Oxide Zinc Lightning Arrester for Substation
15kv High Quality Oxide Zinc Lightning Arrester for Substation
36kv High Quality Oxide Zinc Lightning Arrester for Substation
Popular people Products
6kv Silicone Polymer Housing Composite Metal Oxide Surge Arrester
36kv High Voltage Electrical Lightning Arrester for Transmission Line
33kv Outdoor Expulsion Drop-out Type Loadbreak Fuse Cutout
24kv High Voltage Cutout Switch with Disconnect Blade for Distribution Line
36kv 5kn Polymer Line Horizontal Post Insulator
High Voltage Porcelain Composite Insulators
Tags: High Quality Oxide Zinc Lightning Arrester, Lightning Arrester, Oxide Zinc Lightning Arrester for Substation, people