250kVA 315kVA 10kv on Load Tap Changer Distribution Transformer

China 
                250kVA 315kVA 10kv on Load Tap Changer Distribution Transformer
              manufacture and supplier

250kVA 315kVA 10kv on Load Tap Changer Distribution Transformer image

Get Latest Price Request a quote

Basic Info.

Model NO.
sz-m-315/10kv

Usage
Power Transformer

Frequency Characteristics
Power Frequency

Shape of Core
Ring

Brand
Ville

Regulating
315kVA Power Transformer

Oil Immersed
10kv

Transport Package
Wooden Cases

Specification
IEC CE, ISO

Trademark
ville

Origin
Ningbo China

HS Code
8504231100

Production Capacity
50000 Sets/Year

Product Description

General:

The SZ series load regulating power transformer is developed and produced according to the requirement of the market. It can be widely

used in urban & rural, industrial & agricultural power network, which has a great significance for energy-saving and environment protection.

The lamination method of this product’s iron core is ladder form, instead of the traditional iron core lamination technology, which improves the

magnetic circuit distribution inside the iron core. It can be seen as a revolution of transformer iron core manufacturing.

Compared with the traditional, the no-load loss, no-load current and noise of the new one decrease 20% respectively, and load loss

decreases 10%. The new product applies CAD, with advance design, reasonable structure, and excellent materials. Each index complies

with the standards of GB1094-1996 “Power Transformer” GB/T6451-1999 “Technical Parameters and Requirements of Three-phase Oil-

immersed Type Power Transformer”. Now its level is n the leading position of our country.

 

1. Application
The three phase oil-immersed transformer 250kVA/10kV .After normal transportation, the assembly can be made
with dismounted component without untanking inspection. It can be put into operation after acceptance factory test.
2. Service condition
Normal service condition
2.1 Elevation Height: up to 2000m
2.2 Ambient temperature:Max.temperature:+40 °C
Max. average daily temperature+30°C
Max. average annual temperature +20 °C
Min.temperature:-30°C
2.3 Service site :outdoor.
2.4 Symmetry of power source
The voltage of power source for the three phase transformer shall be approximately symmetrical.

4. Parameters and outline dimension ( refer to table 1,2,3,4)

Transformer capacity:  315kva 

Primary voltage: 10KV 

Second voltage: 380V 

UK:4%

On-load loss(w): 670w 

Load loss(w):3650w
 

5. Transportation

5.1 Road and railway transportation are two ways to deliver transformer to installation site, which is normally full

of oil during the transportation. Attached accessories, fittings and related documents shall be packed with trans-

former for delivery.

5.2 Four lifting lugs on the tank wall, bearing the total weight of transformer, shall be used at the same time when

the transformer is lifted. The lifing block is only used for the active part, the angle between the lifting rope and

vertical line shall not be more than 15°.

6. Acceptance and storage

After receipt of transformer, its type, specification shall be inspected by the purchaser according to the nameplate

&contract. The related technical documents and accessories shall be checked according to the list of ex-works

documents. The inspection shall be carried out as following:

6.1 No oil leakage.

6.2 No damage both product and accessories

6.3 Parts of product such as temperature controller, bushing, Buchholz relay (for products above 630kVA trans-

former), temperature indicator (for products above 1000kVA transformer) and so on.

6.4 During the storage of transformer, the oil level shall be kept to the level of cover and regular inspection shall

be done. For the dismantled transformer during the transportation, the conservator must be mounted due to the oil

pressure and its volume varying with the different temperature when the transformer is put into operation.

6.5 Voltage withstand test has been carried before the deliverv from the factorv according to IEC60076-3. Ifit is

necessary to cary out the test again by the client, its applied value shall be 80% of ex-work testing value.

7. Installation and Maintenance

7.1 The test items could be carried out before the operation when the transformer is delivered without any

dismantling.

7.2 W hen the mercury thermometer and temperature controller are installed, oil shall be filleld into the pocket

of transformer.

7.3 The oil shall be added into the lower part of it when the breathing dehydrator is mounted. Refer to the

operation manual of breathing dehydrator.

7.4 Others are to be put on.

7.5 The height of oil level shall be inspected when the oil level is lower than the normal position. Open the plug

of conservator and fill in the high quality oil to the normal level inside the conservator.

7.6 The draining plug of Buchholz relay shall be sealed well after oil filling. Please check all the sealing surface

and rest 24 hrs to check the leakage, exhaust air from the Buchholz relay again. Attention to the type,

manufacturing place of refilling oil when the oil is refilled. The different type of oil shall not be used and

mixed.

7.7 Oil sample shall be taken for test and analysis.

7.8 Testing notice

Order Instructions

When you choose our company product, please offer following data:

Transformer model:                     

Rated capacity:                     kVA

Phase       :    Three-phase

  • Single-phase

Frequency   :     50HZ

  •  60HZ

Rated voltage ( H.V. / L.V. ):                

Tapping range: ±       ×       %

Insulation level: LI       AC       / LI       AC        kv

Veotor group:  Dyn11

             Yyno

             Other

Short-circuit Impedance:        %

Cooling method:  ONAN

                ONAF

Tapping method:  OLTC

                OCTC

                Other

Other requirement:                                            

Notes:

  1. We also can design special products according to customer’s particular requirements.
  2. The final dimension is subject to outline drawing.

  

Thanks for choosing VILLE as your reliable partner and please trust both

of us will create a brilliant future!
/* January 22, 2024 19:08:37 */!function(){function s(e,r){var a,o={};try{e&&e.split(“,”).forEach(function(e,t){e&&(a=e.match(/(.*?):(.*)$/))&&1

We are China 250kVA 315kVA 10kv on Load Tap Changer Distribution Transformer manufacture and supplier,You can get more details with Email,you will get cheap price or factory price.

Get Latest Price Request a quote

Popular 250kVA 315kVA 10kv on Load Tap Changer Distribution Transformer Products

  • No related articles
  • Popular 315kVA Transformer on Load Tap Changer Products

  • No related articles
  • Popular cnville Products

    2mva 10kv Wond Core Type Hermetically Sealed Oil Immersed Transformer Earthing Transformer

    Rebuilding of Transformer Cooler Device

    Steel Composite Plate Series Box-Type Transformer Substation Enclosure

    40mva 220kv Double-Winding off-Circuit-Tap-Changer Power Transformer

    Steam Turbine a Rang From 0.5MW to 3MW

    HS-2000/10 2mva 10kv Electric Arc Furnace Transformer 50mva 33kv, up to 110kv, 160mva Arc Furnace Transformer

    Popular Oil Immersed Transformer Products

    Vacuum Permanent-Magnet (horizontal) On Load Tap changer for Oil-immersed Transformer

    BFY type oil-immersed load break switch used for compounded type transformer

    S11-M Oil Immersed Transformer 3 Phase 6kv 11kv 15 Kv 33kv 100-3150kVA Oil Immersed Power Transformer

    Two-position Sidewall Oil-immersed Load Switch components of Pad Mounted Transformer

    33kv 11kv Oil Immersed Power Transformer Distribution Transformer S9 S11

    11kv S13-M Sealed Oil Immersed Transformer