9kv Polymeric Housed Metal-Oxide Lightning Arrester Without Gaps
9kv Polymeric Housed Metal-Oxide Lightning Arrester Without Gaps image
Get Latest Price Request a quote
Basic Info.
Product Description
Surge Arrester Series
General
1. Ratings:0.22~500KV (porcelain),0.22~220KV(composite)
2. Application:for protection of power transmission & distribution system from over-voltage.
3. Features:
1)Silicone polymer housing composite metal oxide surge arrester and porcelain housing metal Oxide surge arresters are available.
2)Easy installation and maintenance.
3)Good sealing capability to ensure reliable operation.
4)Protection and reliability of the surge arrester have been greatly enhanced.
Working Condition
1. Ambient air temperature:-40ºC ~+40ºC ;
2. Altitude:<=2000m;
3. Frequency: 48Hz~62Hz;
4. Power frequency voltage applied between terminals of surge arrester must not exceed continuous operating voltage of surge arrerter;
5. Earthquake intensity is less than 8 degree;
6. Max. Wind speed is 35m/s.
Main Techical Parameter
1. Metal oxide Polymer Housing (Gapless) type Surge Arrester for A.C System(5kA series)
Model | Rated voltage (kVr.m.s) | Continuous operating Voltage(KVr.m.s) | Lightening impulse residual voltage under nominal discharge current (<=KVp) | Line discharge class | Creepage distance(mm) | 2ms square wave impulse current withstands(A) | 4/10μhigh current impulse Withstands(KAp) |
YH-5W-6 | 6 | 5.1 | 18 | 320 | 150 | 65 | |
YH-5W-9 | 9 | 7.65 | 27 | 430 | 150 | 65 | |
YH-5W-12 | 12 | 10.2 | 36 | 430 | 150 | 65 | |
YH-5W-15 | 15 | 12.75 | 45 | 530 | 150 | 65 | |
YH-5W-18 | 18 |
15.3 |
54 | 530 | 150 | 65 | |
YH-5W-21 | 21 | 16.8 | 63 | 640 | 150 | 65 | |
YH-5W-24 | 24 | 19.2 | 72 | 640 | 150 | 65 | |
YH-5W-27 | 27 | 21.6 | 81 | 740 | 150 | 65 | |
YH-5W-30 | 30 | 24 | 90 | 890 | 150 | 65 | |
YH-5W-33 | 33 | 26.4 | 99 | 890 | 150 | 65 | |
YH-5W-36 | 36 | 28.8 | 108 | 1115 | 150 | 65 |
2. Metal Oxide Polymer Housing (Gapless) type Surge Arrester for A.C. System (10KA series)
Model | Rated voltage (kVr.m.s) | Continuous operating Voltage(KVr.m.s) | Lightening impulse residual voltage under nominal discharge current (<=KVp) | Line discharge class | Creepage distance(mm) | 2ms square wave impulse current withstands(A) | 4/10μhigh current impulse Withstands(KAp) |
YH-10W-6 | 6 | 5.1 | 18 | 1 | 320 | 250 | 100 |
YH-10W-9 | 9 | 7.65 | 27 | 1 | 430 | 250 | 100 |
YH-10W-12 | 12 | 10.2 | 36 | 1 | 430 | 250 | 100 |
YH-10W-15 | 15 | 12.75 | 45 | 1 | 530 | 250 | 100 |
YH-10W-18 | 18 | 15.3 | 54 | 1 | 530 | 250 | 100 |
YH-10W-21 | 21 | 16.8 | 63 | 1 | 640 | 250 | 100 |
YH-10W-24 | 24 | 19.2 | 72 | 1 | 740 | 250 | 100 |
YH-10W-27 | 27 | 21.6 | 81 | 1 | 740 | 250 | 100 |
YH-10W-30 | 30 | 24 | 90 | 1 | 890 | 250 | 100 |
YH-10W-33 | 33 | 26.4 | 99 | 1 | 890 | 250 | 100 |
YH-10W-36 | 36 | 28.8 | 108 | 1 | 1115 | 250 | 100 |
YH-10W-42 | 42 | 33.6 | 126 | 2 | 1260 | 400 | 100 |
YH-10W-48 | 48 | 39 | 139 | 2 | 1260 | 400 | 100 |
YH-10W-54 | 54 | 42 | 160 | 2 | 1260 | 400 | 100 |
YH-10W-60 | 60 | 48 | 178 | 2 | 1465 | 400 | 100 |
YH-10W-66 | 66 | 52.8 | 196 | 2 | 1465 | 400 | 100 |
YH-10W-72 | 72 | 57 | 214 | 2 | 2255 | 400 | 100 |
YH-10W-84 | 84 | 67.2 | 244 | 2 | 2255 | 400 | 100 |
YH-10W-90 | 90 | 72.5 | 249 | 2 | 2255 | 400 | 100 |
YH-10W-96 | 96 | 75 | 265 | 3 | 3555 | 800 | 100 |
YH-10W-108 | 108 | 84 | 281 | 3 | 3555 | 800 | 100 |
YH-10W-120 | 120 | 96 | 300 | 3 | 4153 | 800 | 100 |
YH-10W-150 | 150 | 120 | 416 | 3 | 5040 | 800 | 100 |
YH-10W-200 | 200 | 156 | 520 | 3 | 7110 | 800 | 100 |
3. Metal Oxide Polymer Housing (Gapless) type Surge Arrester for A.C. System (20KA series)
Model | Rated voltage (kVr.m.s) | Continuous operating Voltage(KVr.m.s) | Lightening impulse residual voltage under nominal discharge current (<=KVp) | Line discharge class | Creepage distance(mm) | 2ms square wave impulse current withstands(A) | 4/10μhigh current impulse Withstands(KAp) |
YH-20W-108 | 108 | 84 | 281 | 3 | 3555 | 800 | 100 |
YH-20W-120 | 120 | 96 | 300 | 3 | 4153 | 800 | 100 |
YH-20W-150 | 150 | 120 | 416 | 3 | 5040 | 800 | 100 |
YH-20W-200 | 200 | 156 | 520 | 3 | 7110 | 800 | 100 |
4. Metal Oxide Porcelain Housing (Gapless) type Surge Arrester for A.C. System (5KA series)
Model | Rated voltage (kVr.m.s) | Continuous operating Voltage(KVr.m.s) | Lightening impulse residual voltage under nominal discharge current (<=KVp) | Line discharge class | Creepage distance(mm) | 2ms square wave impulse current withstands(A) | 4/10μhigh current impulse Withstands(KAp) |
Y5W-6 | 6 | 5.1 | 18 | 280 | 150 | 65 | |
Y5W-9 | 9 | 7.65 | 27 | 320 | 150 | 65 | |
Y5W-12 | 12 | 10.2 | 36 | 320 | 150 | 65 | |
Y5W-15 | 15 | 12.75 | 45 | 450 | 150 | 65 | |
Y5W-18 | 18 |
15.3 |
54 | 450 | 150 | 65 | |
Y5W-21 | 21 | 16.8 | 63 | 450 | 150 | 65 | |
Y5W-24 | 24 | 19.2 | 72 | 510 | 150 | 65 | |
Y5W-27 | 27 | 21.6 | 81 | 510 | 150 | 65 | |
Y5W-30 | 30 | 24 | 90 | 890 | 150 | 65 | |
Y5W-33 | 33 | 26.4 | 99 | 890 | 150 | 65 | |
Y5W-36 | 36 | 28.8 | 108 | 890 | 150 | 65 |
5. Metal Oxide Polymer Housing (Gapless) type Surge Arrester for A.C. System (10KA series)
Model | Rated voltage (kVr.m.s) | Continuous operating Voltage(KVr.m.s) | Lightening impulse residual voltage under nominal discharge current (<=KVp) | Line discharge class | Creepage distance(mm) | 2ms square wave impulse current withstands(A) | 4/10μhigh current impulse Withstands(KAp) |
Y10W-6 | 6 | 5.1 | 18 | 1 | 280 | 250 | 100 |
Y10W-9 | 9 | 7.65 | 27 | 1 | 320 | 250 | 100 |
Y10W-12 | 12 | 10.2 | 36 | 1 | 320 | 250 | 100 |
Y10W-15 | 15 | 12.75 | 45 | 1 | 450 | 250 | 100 |
Y10W-18 | 18 | 15.3 | 54 | 1 | 450 | 250 | 100 |
Y10W-21 | 21 | 16.8 | 63 | 1 | 450 | 250 | 100 |
Y10W-24 | 24 | 19.2 | 72 | 1 | 510 | 250 | 100 |
Y10W-27 | 27 | 21.6 | 81 | 1 | 510 | 250 | 100 |
Y10W-30 | 30 | 24 | 90 | 1 | 890 | 250 | 100 |
Y10W-33 | 33 | 26.4 | 99 | 1 | 890 | 250 | 100 |
Y10W-36 | 36 | 28.8 | 108 | 1 | 890 | 250 | 100 |
Y10W-42 | 42 | 33.6 | 126 | 2 | 1256 | 400 | 100 |
Y10W-48 | 48 | 39 | 139 | 2 | 1256 | 400 | 100 |
Y10W-54 | 54 | 42 | 160 | 2 | 1256 | 400 | 100 |
Y10W-60 | 60 | 48 | 178 | 2 | 1440 | 400 | 100 |
Y10W-66 | 66 | 52.8 | 196 | 2 | 1440 | 400 | 100 |
Y10W-72 | 72 | 57 | 214 | 2 | 1440 | 400 | 100 |
Y10W-84 | 84 | 67.2 | 244 | 2 | 2200 | 400 | 100 |
Y10W-90 | 90 | 72.5 | 249 | 2 | 2200 | 400 | 100 |
Y10W-96 | 96 | 75 | 265 | 3 | 3350 | 800 | 100 |
Y10W-108 | 108 | 84 | 281 | 3 | 3350 | 800 | 100 |
Y10W-120 | 120 | 96 | 300 | 3 | 3948 | 800 | 100 |
Y10W-150 | 150 | 120 | 416 | 3 | 4400 | 800 | 100 |
Y10W-200 | 200 | 156 | 520 | 3 | 6700 | 800 | 100 |
6. Metal Oxide Polymer Housing (Gapless) type Surge Arrester for A.C. System (20KA series)
Model | Rated voltage (kVr.m.s) | Continuous operating Voltage(KVr.m.s) | Lightening impulse residual voltage under nominal discharge current (<=KVp) | Line discharge class | Creepage distance(mm) | 2ms square wave impulse current withstands(A) | 4/10μhigh current impulse Withstands(KAp) |
Y20W-108 | 108 | 84 | 281 | 3 | 3555 | 800 | 100 |
Y20W-120 | 120 | 96 | 300 | 3 | 4106 | 800 | 100 |
Y20W-150 | 150 | 120 | 416 | 3 | 4400 | 800 | 100 |
Y20W-200 | 200 | 156 | 520 | 3 | 6700 | 800 | 100 |
Y20W-444 | 444 | 324 | 1106 | 4 | 17052 | 2000 | 100 |
Note: For details, please refer to the catalogue.
Participate in the exhibition pictures
testing report
We are China 9kv Polymeric Housed Metal-Oxide Lightning Arrester Without Gaps manufacture and supplier,You can get more details with Email,you will get cheap price or factory price.
Get Latest Price Request a quote
Popular Lightning Arrester Products
32kv 100A 10ka Polymer Housed Gapless Surge Arrester
Kema 11kv Surge Arrester Zinc Oxide Lightning Arrester
6kv Polymeric Housed Metal-Oxide Lightning Arrester Without Gaps
11kv Zinc Oxide Polymeric Lightning Arrester
120kv Polymeric Housed Metal Oxide Lightning Arrester
Popular metal oxide lightning arrester Products
24kv Polymeric Housed Metal-Oxide Lightning Arrester Without Gaps
24kv Silicone Polymer Housing Composite Metal Oxide Lightning Arrester
15kv Silicone Polymer Housing Composite Metal Oxide Lightning Arrester
6kv Polymeric Housed Metal-Oxide Lightning Arrester Without Gaps
9kv Silicone Polymer Housing Composite Metal Oxide Lightning Arrester
36kv Polymeric Housed Metal-Oxide Lightning Arrester Without Gaps
Popular people Products
36kv Polymeric Metal-Oxide Surge Arrester Electrical
12kv High Voltage Surge Arrester for Distribution Line
33kv High Voltage Surge Arrester for Distribution Line
Q/Qp Type Die Casting Ball Eyes
Flexible Laminated Connectors Type-Aluminum MS
(YH10WZ-108) Polymeric Housed Metal-Oxide Surge Arrester
Popular Polymeric Housed Lightning Arrester Products
21kv Polymeric Housed Metal-Oxide Lightning Arrester Without Gaps
33kv Polymeric Housed Metal-Oxide Lightning Arrester Without Gaps
12kv Polymeric Housed Metal-Oxide Lightning Arrester Without Gaps
15kv Polymeric Housed Metal-Oxide Lightning Arrester Without Gaps
24kv Polymeric Housed Metal-Oxide Lightning Arrester Without Gaps
27kv Polymeric Housed Metal-Oxide Lightning Arrester Without Gaps
Tags: Lightning Arrester, metal oxide lightning arrester, people, Polymeric Housed Lightning Arrester