0.6/1kv ABC cable duplex/triplex/quadruplex service drop cable aerial bundled cable
I:Applications:
Primarily used for overheard service applications such as street lighting,outdoor lighting,and temporary service for construction.To be used at votage of 600V phase-to-phase and conductor temperatures not to exceed 75ºC for polyethylene insulated conductors or 90ºC for crossliked polythylene(XLPE)insulated conductors.
II: Service drop cable meets or exceeds the following specifications:
1.Aluminum Wire,1350-H19 for Electrical Purposes.
2.Aluminum Conductor,Concentric-Lay-Stranded.
3.Aluminum Conductor,Concentric-Lay-Stranded.Coated Steel Reinforced(ACSR).
4. Concentric-Lay-Stranded 6201-T81 Conductors.
5. Service drop cable meets or exceeds all applicable requirement of ANSI/ICEA S-76-474.
Standards:
B-230 Aluminum Wire 1350-H19 for Electrical Purposes
B-231 Aluminum Conductors, Concentric-Lay-Stranded
B-232 Aluminum Conductors, Concentric-Lay-Stranded, Coated Steel Reinforced (ACSR)
B-399 Concentric-Lay-Stranded 6201-T81 Aluminum Alloy Conductors
B-498 Zinc-Coated Steel Core Wire for Aluminum Conductors, Steel Reinforced (ACSR).
Triplex Service Drop cable meets or exceeds all applicable requirements of ANSI/ICEA body S-76-474.
There is a lot of debate still going on as to whether copper is better for electrical purposes or aluminum. If price was not a critical factor, most would suggest going in for silver as it is said to be the best conductor of electricity but has a low strength. However, when it comes to electrical wiring, price is a factor, as is efficiency.
Triplex Aluminum Service Drop Cable
| Code Word | Phase conductor | Bare Neutral Messenger | Weight Per 1000 ft. (lbs.) | Allowable Ampacity+ | |||||||
| Size (AWG) | Stranding | Insul. Thick. (mils) | Size (AWG) | Size (kcmil) | Strand- ing | Rated Strength (lbs.) | XLP | POLY | XLP | POLY | |
| AAAC 6201 ALLOY FULL NEUTRAL MESSENGER | |||||||||||
| Minex | 6 | 1 | 45 | 6 | 30.58 | 7 | 1110 | 101 | 101 | 85 | 70 |
| Hippa | 6 | 7 | 45 | 6 | 30.58 | 7 | 1110 | 107 | 107 | 85 | 70 |
| Prawn | 4 | 1 | 45 | 4 | 48.69 | 7 | 1760 | 152 | 152 | 115 | 90 |
| Barnacle | 4 | 7 | 45 | 4 | 48.69 | 7 | 1760 | 160 | 160 | 115 | 90 |
| Shrimp | 2 | 7 | 45 | 2 | 77.47 | 7 | 2800 | 243 | 243 | 150 | 120 |
| Gammarus | 1/0 | 7 | 60 | 1/0 | 123.3 | 7 | 4460 | 390 | 390 | 205 | 160 |
| Leda | 1/0 | 9 | 60 | 1/0 | 123.3 | 7 | 4460 | 384 | 384 | 205 | 160 |
| Dunganese | 2/0 | 7 | 60 | 2/0 | 155.4 | 7 | 5390 | 474 | 474 | 235 | 185 |
| Cyclops | 2/0 | 11 | 60 | 2/0 | 155.4 | 7 | 5390 | 474 | 474 | 235 | 185 |
| Flustra | 3/0 | 17 | 60 | 3/0 | 195.7 | 7 | 6790 | 587 | 587 | 275 | 215 |
| Lepas | 4/0 | 18 | 60 | 4/0 | 246.9 | 7 | 8560 | 728 | 728 | 315 | 245 |
| *Code words for XLP insulated products are formed by adding "/XLP" to the conventional code words above (e.g.-Haiotis/XLP).+Conductor temperature of 90°C for XLP, 75°C for Poly; ambient temperature of 40°C; emissivity 0.9; 2 ft./sec. wind in sun.++Designated sizes are: ACSR 6/1 diameter equivalent and AAC with equivalent resistivity per ASTM B-399 for 6201. | |||||||||||
| Code Word | Phase conductor | Bare Neutral Messenger | Weight Per 1000 ft. (lbs.) | Allowable Ampacity+ | |||||||
| Size (AWG) | Stranding | Insul. Thick. (mils) | Size (AWG) | Size (kcmil) | Strand- ing | Rated Strength (lbs.) | XLP | POLY | XLP | POLY | |
| AAAC 6201 ALLOY REDUCED NEUTRAL MESSANGER | |||||||||||
| Artemia | 4 | 1 | 45 | 6 | 30.58 | 7 | 1110 | 135 | 135 | 115 | 90 |
| Crab | 4 | 7 | 45 | 6 | 30.58 | 7 | 1110 | 143 | 143 | 115 | 90 |
| Solaster | 2 | 7 | 45 | 4 | 48.69 | 7 | 1760 | 216 | 216 | 150 | 120 |
| Sandcrab | 1/0 | 7 | 60 | 2 | 77.47 | 7 | 2800 | 347 | 347 | 205 | 160 |
| Echinus | 1/0 | 9 | 60 | 2 | 77.47 | 7 | 2800 | 341 | 341 | 205 | 160 |
| Crayfish | 2/0 | 7/w | 60 mls | 2/0 | — | 7 | 2510 | 485.8 | 455.3 | 235 Amps | 185 Amps |
| Sipho | 2/0 | 7/w | 60 mls | 2/0 | — | 7 | 2510 | 485.8 | 455.3 | 235 Amps | 185 Amps |
| Fulgar | 3/0 | 17 | 60 | 1/0 | 123.3 | 7 | 4460 | 519 | 519 | 275 | 215 |
| Arca | 4/0 | 18 | 60 | 2/0 | 155.4 | 7 | 5390 | 643 | 643 | 315 | 245 |
| *Code words for XLP insulated products are formed by adding "/XLP" to the conventional code words above (e.g.-Haiotis/XLP).+Conductor temperature of 90°C for XLP, 75°C for Poly; ambient temperature of 40°C; emissivity 0.9; 2 ft./sec. wind in sun.++Designated sizes are: ACSR 6/1 diameter equivalent and AAC with equivalent resistivity per ASTM B-399 for 6201. | |||||||||||
| Code Word | Phase conductor | Bare Neutral Messenger | Weight Per 1000 ft. (lbs.) | Allowable Ampacity+…………… | ||||||
| Size (AWG) | Stranding | Insul. Thick. (mils) | Size (AWG) | Strand- ing | Rated Strength (lbs.) | XLP | POLY | XLP | POLY | |
| AAC NEUTRAL-MESSENGER | ||||||||||
| Haiotis | 6 | 7/w | 45 mls | 6 | 7 | 563 | 109.1 | 101.6 | 85 Amps | 70 Amps |
| Patella | 6 | 7 | 45 | 6 | 7 | 563 | 103 | 103 | 85 | 70 |
| Fusus | 4 | 7/w | 45 mls | 4 | 7 | 881 | 161.8 | 151.7 | 115 Amps | 90 Amps |
| Oyster | 4 | 7 | 45 | 4 | 7 | 881 | 154 | 154 | 115 | 90 |
| Clam | 2 | 7 | 45 | 2 | 7 | 1350 | 233 | 233 | 150 | 120 |
| Murex | 1/0 | 7 | 60 | 1/0 | 7 | 1990 | 374 | 374 | 205 | 160 |
| Purpura | 1/0 | 9 | 60 | 1/0 | 7 | 1990 | 368 | 368 | 205 | 160 |
| Nassa | 2/0 | 7 | 60 | 2/0 | 7 | 2510 | 462 | 462 | 235 | 185 |
| Melita | 3/0 | 17 | 60 | 3/0 | 19 | 3310 | 562 | 562 | 275 | 215 |
| Portunus | 4/0 | 18 | 60 | 4/0 | 19 | 4020 | 696 | 696 | 315 | 245 |
| Nannynose | 336.4 | 19 | 80 | 336.4 | 19 | 6146 | 1118 | 1118 | 420 | 325 |
| * Code words for XLP insulated products are formed by adding "/XLP" to the conventional code words above (e.g.-Haiotis/XLP).+ Conductor temperature of 90°C for XLP, 75°C for Poly; ambient temperature of 40°C; emissivity 0.9; 2 ft./sec. wind in sun. | ||||||||||
| Code Word | Phase conductor | Bare Neutral Messenger | Weight Per 1000 ft. (lbs.) | Allowable Ampacity+ | ||||||
| Size (AWG) | Stranding | Insul. Thick. (mils) | Size (AWG) | Strand- ing | Rated Strength (lbs.) | XLP | POLY | XLP | POLY | |
| ASCR NEUTRAL-MESSENGER | ||||||||||
| Paludina | 6 | 1 | 45 | 6 | 6/1 | 1190 | 109 | 109 | 85 | 70 |
| Voluta | 6 | 7 | 45 | 6 | 6/1 | 1190 | 114 | 114 | 86 | 70 |
| Whelk | 4 | 1 | 45 | 4 | 6/1 | 1860 | — | 164 | 115 | 90 |
| Periwinkle | 4 | 7 | 45 | 4 | 6/1 | 1860 | 172 | 172 | 115 | 90 |
| Conch | 2 | 7 | 60 | 1/0 | 6/1 | 4380 | 420 | 420 | 205 | 160 |
| Neritina | 1/0 | 7 | 60 | 1/0 | 6/1 | 4380 | 420 | 420 | 205 | 160 |
| Cenia | 1/0 | 9 | 60 | 1/0 | 6/1 | 4380 | 414 | 414 | 205 | 160 |
| Runcina | 2/0 | 7 | 60 | 2/0 | 6/1 | 5310 | 520 | 520 | 235 | 185 |
| Triton | 2/0 | 11 | 60 | 2/0 | 6/1 | 5310 | 512 | 512 | 235 | 185 |
| Mursia | 3/0 | 17 | 60 | 3/0 | 6/1 | 6620 | 635 | 635 | 275 | 215 |
| Zuzara | 4/0 | 18 | 60 | 4/0 | 6/1 | 8350 | 789 | 789 | 315 | 245 |
| Limpet | 336.4 | 19 | 80 | 336.4 | 18/1 | 8680 | 1167 | 1167 | 420 | 325 |
| *Code words for XLP insulated products are formed by adding "/XLP" to the conventional code words above (e.g.-Haiotis/XLP).+Conductor temperature of 90°C for XLP, 75°C for Poly; ambient temperature of 40°C; emissivity 0.9; 2 ft./sec. wind in sun. | ||||||||||
| Code Word | Phase conductor | Bare Neutral Messenger | Weight Per 1000 ft. (lbs.) | Allowable Ampacity+ | ||||||
| Size (AWG) | Stranding | Insul. Thick. (mils) | Size (AWG) | Strand- ing | Rated Strength (lbs.) | XLP | POLY | XLP | POLY | |
| ASCR REDUCED NEUTRAL-MESSENGER | ||||||||||
| Scallop | 4 | 1 | 45 | 6 | 6/1 | 1190 | — | 142 | 115 | 90 |
| Strombus | 4 | 7 | 45 | 6 | 6/1 | 1190 | 151 | 151 | 115 | 90 |
| Cockle | 2 | 7 | 45 | 4 | 6/1 | 1190 | 220 | 220 | 150 | 120 |
| Janthina | 1/0 | 7 | 60 | 2 | 6/1 | 2853 | 366 | 366 | 205 | 160 |
| Ranella | 1/0 | 9 | 60 | 2 | 6/1 | 2853 | 360 | 360 | 205 | 160 |
| Cavolinia | 2/0 | 7 | 60 | 1 | 6/1 | 3550 | 453 | 453 | 235 | 185 |
| Clio | 2/0 | 11 | 60 | 1 | 6/1 | 3550 | 444 | 444 | 235 | 185 |
| Sanddollar | 3/0 | 19/w | 60 mls | 1/0 | 6/1 | 4380 | 565 | 552 | 275 Amps | 215 Amps |
| Aega | 3/0 | 17 | 60 | 1/0 | 6/1 | 4380 | 549 | 549 | 275 | 215 |
| Cuttlefish | 4/0 | 19/w | 60 mls | 2/0 | 6/1 | 5310 | 699 | 684 | 315 Amps | 245 Amps |
| Cerapus | 4/0 | 18 | 60 | 2/0 | 6/1 | 5310 | 681 | 681 | 315 | 245 |
| Cowery | 336.4 | 19 | 80 mls | 336/4 | 18/1 | 8680 | 1209 | 1167 | 420 Amps | 325 Amps |
| *Code words for XLP insulated products are formed by adding "/XLP" to the conventional code words above (e.g.-Haiotis/XLP).+Conductor temperature of 90°C for XLP, 75°C for Poly; ambient temperature of 40°C; emissivity 0.9; 2 ft./sec. wind in sun. | ||||||||||
We are China 0.6/1kv ABC Cable Duplex/Triplex/Quadruplex Service Drop Cable Aerial Bundled Cable, Power Cable manufacture and supplier,You can get more details with Email,you will get cheap price or factory price.
Get Latest Price Request a quote
Popular ABC Cable Products
Aluminum Conductor XLPE Insulated ABC Cable Overhead Power Cable 0.6/1 Kv
Low Voltage ABC Cable 4X25mm, Aerial Bundle Cable Manufacturer
PE/XLPE Insulated Power Cable ABC Cable 4*50mm2
Duplex AAC/ACSR Conductor Overhead Power Transmission Used XLPE Twisted ABC Power Cable
PE/XLPE Insulated Overhead Power Transmission Aerial ABC Cable
Duplex Serivice Drop Cable AAC Conductor Customized Insulated ABC Cable
Popular Aerial Bundled Cable Products
10kv Copper Core XLPE Insulated Cable for Overhead
0.6/1kv ABC Cable Overhead Transmission Line Aerial Bunched Caai Cable / Self-Supporting Cable
0.6/1kV Overhead XLPE Insulated Cable Al Twisted ABC Cable
4X4mm2 33kv ABC Aerial Bundle Electrical Power Cable with High Quality
4 Cores Conductor Aerial Bundle Cable ABC Cable 35mm2
Popular huatongcable Products
25 Kv Sac Cable Al/XLPE HDPE Cable
Overhead Line AAC Overhead Wire All Aluminiun Stranded Conductor
Hot Dipped Galvanized Steel Wire Galvanzied Steel Wire Stay Wire
ABC Triplex 2/0 AWG Cyclops Alloy Neutral Service Drop
Concentric Neutral Cable 3*1/0AWG
Multi-Core Rubber Insulation Copper Power Cable
Popular PVC XLPE Insulated Products
5 X 150mm2 XLPE Insulated Wire Power Cable 5 Core Cable
Aerial Bundle Cable ABC Aerial Overhead Cable with ACSR Messenger Core
Supply Best Price of Service Drop Cable AAC ACSR /PVC Cable ABC Cable
Overhead Stranded Conductor ABC Cable Aerial Bundled Cables with AAC ACSR AAAC Neutral Message
3 Core 5 Core 2.5 mm 6mm 10mm 16mm 25mm 50mm Copper Conductor Cable PVC Electrical Cable 3X25
Tags: ABC Cable, Aerial Bundled Cable, huatongcable, PVC XLPE Insulated