Fuse Links Mv Type J Slotted (400 AMPS)
Fuse Links Mv Type J Slotted (400 AMPS) image
Get Latest Price Request a quote
Quick Details
Product Details
Slotted J type Low voltage fuse link to BS 88 for Utility applications
The Fuse Cutout type OEI was developed to operate in overhead distribution systems rated at 11
kV to 38 kV grounded systems with 100 or 200 A nominal currents.
Especially designed to protect transformers, capacitors, cables or lines.
It is robust construction, made of rigorously tested material, will interrupt all faults under the
most severe conditions, maintaining mechanical and electric characteristics.
The inserts, hardware and structural bolts and nuts are made from heavy galvanized steel.
The Fuse Cutout type OEI can be applied on all three-phase system rated at or below the maximum
operational rating of the cutout.
| S/N | Description | Units | Schedule A | Schedule B | |
| 1 | Current ratings | A | 5 | ||
| 2 | Frequency | Hz | 50 | ||
| 3 | Rated Speed ratio | Type K as per IEC 60282 -2 |
|||
| 4 | Class of fuse link | Class B as per IEC 60282-2 |
|||
| 5 | Fuse element | Tin or Silver | |||
| 6 | Following Routine test results shall be provided on delivery of fuse links | Yes/No |
a) a static strength test; and | Yes | |
| b) a resistance test, with the fuse-link under strain. |
Yes |
||||
| 7 | The following tests shall be performed on one fuse-link per batch and test results provided on delivery of fuse links: |
Yes/No |
a)confirmation of the time/current characteristics; and |
Yes |
|
| b) a dynamic strength test. | Yes | ||||
| 8 | Drawing showing construction and dimensions as per figure 1 below to be provided with bid |
Yes/No | Yes | ||
| 9 | Previous type tests reports/certificate to be provided on bid. |
Yes/No |
Yes |
||
| 10 | Altitude above sea level | m | 1400 | ||
| 11 | Ambient operating | oC | -1 to 40 | ||
| Performance Characteristic | |
| Applied standard | IEEE C37.42-2009 |
| Catalog number | |
| Nominal system voltage kV | 22 |
| Rated Frequency Hz | 50 |
| Rated m aximum(design) voltage | 27 |
| Rated Continuous current A-RMS | 100 |
| Rated Interrupting current asymmetrical/symmetrical A-RMS | 12000/8000 |
| BIL 1.2×50 µs kV-peak | 125 |
| Minimum critical impulse flashover voltage(CFO)KV peak | 140 |
| Dry withstand voltage kV-RMS | 42 |
| Wet withstand voltage kV-RMS | 36 |
| Creepage distance to group Min.mm | 320 |
| Minimum creepage factor of insulator (Creepage Distance/arcing distance) | 2 |
| Performance Characteristic | |
| Applied standard | IEC60282-2 |
| Catalog number | |
| Nominal system voltage kV | 11 |
| Rated Frequency Hz | 50 |
| Rated m aximum(design) voltage | 12 |
| Rated Continuous current A-RMS | 100 |
| Rated Interrupting current asymmetrical/symmetrical A-RMS | 12000/8000 |
| BIL 1.2×50 µs kV-peak | 125 |
| Minimum critical impulse flashover voltage(CFO)KV peak | 140 |
| Dry withstand voltage kV-RMS | 42 |
| Wet withstand voltage kV-RMS | 36 |
| Creepage distance to group Min.mm | 372 |
| Minimum creepage factor of insulator (Creepage Distance/arcing distance) | N/A |
| Performance Characteristic | |
| Applied standard | IEEE C37.42-2009 |
| Catalog number | |
| Nominal system voltage kV | 33 |
| Rated Frequency Hz | 50 |
| Rated m aximum(design) voltage | 38 |
| Rated Continuous current A-RMS | 100 |
| Rated Interrupting current asymmetrical/symmetrical A-RMS | 8000/5000 |
| BIL 1.2×50 µs kV-peak | 150 |
| Minimum critical impulse flashover voltage(CFO)KV peak | 165 |
| Dry withstand voltage kV-RMS | 70 |
| Wet withstand voltage kV-RMS | 60 |
| Creepage distance to group Min.mm | 650 |
| Minimum creepage factor of insulator (Creepage Distance/arcing distance) | 2.3 |
| DIMENSION(mm) | |||||
| RATED CURRENT (A) |
A | B | C | D | L MN |
| 1 to 25 | 12.5+0.2 | 19.0+0.2 | 6.5 | 2.0 | 533,600,787 |
| 30 to 40 | 12.5+0.2 | 19.0+0.2 | 8.0 | 3.0 | 533,600,787 |
| 50 to 100 | 19.0+0.3 | not applicable | 9.0 | 5.0 | 533,600,787 |
| 140 to 200 | 19.0+0.3 | not applicable | 13.0 | 7.0 | 533,600,787 |
We are China Fuse Links Mv Type J Slotted (400 AMPS) manufacture and supplier,You can get more details with Email,you will get cheap price or factory price.
Get Latest Price Request a quote
Popular Fuse Link Products
Connector, Burndy Oxlip 400/500kvsu 34
Interlock Liner Fully Dipped Blue Nitrile
Spacers for Two-Bundle Conductor Type Mrj, Suitable for Large Cross-Sectional Conductor
Spacers for Two-Bundle Conductor Type Mrj
Popular High Voltage Fuse Products
Cross Type Spacer-Dampers for 500kv Lines
PVC Gloves Sandy Finish Green 30cm
Polyester Glove Latex Coated, Crinkle Finish (black)
U3 Knitted Nitrile Glovespolyesterblack 7-11
Popular jgtrade1 Products
Polymer Fuse Cutout, Drop out Fuses 72kv 200A
Polymer Fuse Cutout, Drop out Fuses 75kv 100A
Parallel Groove Clamp Capg Pg Clamp
Popular K Products
Connector, Oklip 250-300 / 6-350 Kvsu31
Tags: Fuse Link, High Voltage Fuse, jgtrade1, K