Interrupteur aé Rien à Commande Manuelle Rocking Disconnectors

GW4-33 2000

OEI Power

Wooden Case

IEC IEEE

China Nanyang

8535309000

Product Details

Center Break Isolator and double Break Isolator

 

These disconnectors are , no load switching devices
which physically isolate the lines. They are designed for
horizontal outdoor application and can also be designed
for vertical installation. For earthing and closing of
switchyard portions of the installation, the earthing
switches are provided on disconnector. If required.

The following documents were referred to during the preparation of this specification. In case of conflict, the provisions of this specification shall take precedence.
IEC 129:1975: Alternating Current Disconnectors (Isolators) and Earthing Switches
IEC 60694:2002: Common Specifications for High Voltage Switchgear and Controlgear
BS 729: Hot dip galvanized coating on iron and steel articles
IEC62271-102
Isolator (Disconnector) – a mechanical switching device which provides, in the open position, an isolating distance in accordance with Electrical Safety requirements.

SERVICE CONDITIONS
The isolator shall be suitable for continuous operation outdoors in tropical areas at altitudes of up to 2200m above sea level, humidities of up to 90%, average ambient temperature of +30ºC with a minimum of -1ºC and a maximum of +40ºC and heavy saline conditions along the coast.

4.2. DESIGN AND CONSTRUCTION
4.2.1 The Isolator, Solid Link shall be designed and constructed in accordance with IEC 129 and IEC 60694.
4.2.2 The isolating link shall be of the vertical opening, designed for single phase manual operation. It shall be easily removed and replaced by using a portable operating rod.
4.2.3 The isolating link shall incorporate double porcelain insulators to suit voltage requirements and mounted on hot dipped galvanised steel under base suitable for vertical mounting.
4.2.4 The isolating link shall be arranged so that each unit is mounted independently on an angle bracket. It shall be supplied complete with the angle bracket and accessories suitable for mounting on ‘U’ type steel channel. The drawings to be submitted shall indicate all the applicable mounting positions.
4.2.5 The isolator shall be designed such that in fully open position, it shall provide adequate electrical isolation between the contacts on each phase. It shall conform to the requirement as single point isolation for safety.
4.2.6 All steel parts shall be hot dip galvanized to BS 729. The minimum coating of galvanizing required is 80 microns.
4.2.7 The solid link shall be removable from the mounting by use of operating rod.
4.2.8 All current carrying parts of the isolator shall be made of high conductivity material.
4.2.9 The isolator shall be fitted with clamp connectors for Aluminium (ACSR) conductor of Aluminium (ACSR)conductor of up to 18.2mm diameter.

The rating of the complete isolator shall be as follows: –
Rated voltage
36 kV
Rated frequency
50 Hz
Rated lightning impulse withstand voltage
200 kV
Rated power frequency withstand voltage, dry
95 kV
Rated normal current
400 Amps
Rated short time withstand current for 3 sec, min.
18.0 kA
Minimum creepage distance of insulators
900 mm
 
 

  System Voltages 132kV
1 System: 50 Hz, 3phase
2 Neutral Point Earthing Solidly Earthed Earthing Resistor
3 Nominal voltage of networks 132kV
4 Highest system voltage as defined by IEC – 38 145kV
5 Short circuit not less than [MVA] N/A
6 Short circuit and earth fault current, symmetrical r.m.s. value not less than N/A
7 Thermal short circuit current, 1 second not less than 31.5 kA
8 Dynamic Peak current not less than 80 kA
9 Continuously rated currents of Isolating Switches: 1 600 A
10 Isolation Voltage according to IEC – 71  
10 a – Switching Surge withstand voltage  
  Phase to earth 275 kV
  – Longitudinal impulse component of combined test 325 kV
10 b – Lightning Impulse withstand voltage 1.2/50 micro-s  
  To earth and between phases 650kVp
  Across the isolating distance of isolating switches 750 kVp
10 c – Test voltage at power frequency 1 minute, dry and wet 
  (at sea level)
 
  To earth and between phases (r.m.s.) N/A
  Across the isolating distance of isolating switches N/A
 11 For the design and erection of the conductors in the switchyard the following minimum distance shall be observed:  
11a Phasetoground [mm] 1 500
11b – Phasetophase 2 330
11c Busbars phasetophase 3 500
11d Height to live parts above ground 5 500
11e Height to live parts above ground at   
  service/transportation strips                           [mm]
5 500
11f – Lowest part of insulators above ground         [mm] 3 500
12 Maximum temperature rise of conductors
above ambient temperature (45oC)
40oC
13 Maximum wind pressure on conductors and cylindrical objects 430N/m2
14 Maximum wind pressure on flat surfaces 820N/m2
15 Minimum nominal creepage distance as defined in IEC 815, Table II 25 mm/kV

We are China Interrupteur aé Rien à Commande Manuelle Rocking Disconnectors manufacture and supplier,You can get more details with Email,you will get cheap price or factory price.

Get Latest Price Request a quote

Popular Disconnect Switch Products

Isolator, Gang Operated

Outdoor High Voltage Porcelain Isolated Switch Series

Outdoor Gis, Gas Insulated Electric Switchgear for Power Network Distribution Panel Equipment with IEC

Medium Voltage Switchboard, Electric Switch, 27.5V Outdoor Air Insulated Switchgear for Power Grid/ Subway

11kv High Voltage Disconnect Switch for Distribution Line

Hgw9-12/1250A Isolation Switch Outdoor High Voltage with Polymer Insulator

Popular Disconnector Products

245kv Centre Berak Two Post Ceramic Insulator Disconnector Switch

110kv Outdoor Substation Hv Sf6 Gas Live Tank Disconnector Circuit Breaker

High -Voltage Isolate Switch 40.5kv

110kv 126kv 145kv 1250A 2000A Double Earthed Disconnector / Isolator Switch

High Voltage Disconnector Isolators Switch

Gw8 Neutral Point Disconnector 145kv

Popular Isolator Switch Products

High-Voltage Disconnector Switch 21kv

Flexible Steel Cable

Single Phase Split Prepayment Energy Meters 2-Way Polotop Enclosure (Meter Box)

Isolator, Gang Operated

Gw4 Outdoor High Voltage 33kv 35kv 400A 630A 1000A 1250A Three Phase Isolator

Strain Clamps Bolt Type

Popular jgtrade1 Products

Fuse Cutout, Drop out Fuse 11-38kv

11kv Load Isolators

Bolted Tension Strings for (150) mm2 Aluminum Alloy Conductor

1 0.5-Inch Gray Cow Hide Split Leather, Green Leather Reinforced Double Palm,

Self-Tightening Clamps for ACSR Conductor ‘ Sock’ Type

Clamp Aluminum Netsuke