The following documents were referred to during the preparation of this specification. In case of conflict, the provisions of this specification shall take precedence.
IEC 129:1975: Alternating Current Disconnectors (Isolators) and Earthing Switches
IEC 60694:2002: Common Specifications for High Voltage Switchgear and Controlgear
BS 729: Hot dip galvanized coating on iron and steel articles
IEC62271-102
Isolator (Disconnector) – a mechanical switching device which provides, in the open position, an isolating distance in accordance with Electrical Safety requirements.
SERVICE CONDITIONS
The isolator shall be suitable for continuous operation outdoors in tropical areas at altitudes of up to 2200m above sea level, humidities of up to 90%, average ambient temperature of +30ºC with a minimum of -1ºC and a maximum of +40ºC and heavy saline conditions along the coast.
4.2. DESIGN AND CONSTRUCTION
4.2.1 The Isolator, Solid Link shall be designed and constructed in accordance with IEC 129 and IEC 60694.
4.2.2 The isolating link shall be of the vertical opening, designed for single phase manual operation. It shall be easily removed and replaced by using a portable operating rod.
4.2.3 The isolating link shall incorporate double porcelain insulators to suit voltage requirements and mounted on hot dipped galvanised steel under base suitable for vertical mounting.
4.2.4 The isolating link shall be arranged so that each unit is mounted independently on an angle bracket. It shall be supplied complete with the angle bracket and accessories suitable for mounting on ‘U’ type steel channel. The drawings to be submitted shall indicate all the applicable mounting positions.
4.2.5 The isolator shall be designed such that in fully open position, it shall provide adequate electrical isolation between the contacts on each phase. It shall conform to the requirement as single point isolation for safety.
4.2.6 All steel parts shall be hot dip galvanized to BS 729. The minimum coating of galvanizing required is 80 microns.
4.2.7 The solid link shall be removable from the mounting by use of operating rod.
4.2.8 All current carrying parts of the isolator shall be made of high conductivity material.
4.2.9 The isolator shall be fitted with clamp connectors for Aluminium (ACSR) conductor of Aluminium (ACSR)conductor of up to 18.2mm diameter.
The rating of the complete isolator shall be as follows: –
Rated voltage
36 kV
Rated frequency
50 Hz
Rated lightning impulse withstand voltage
200 kV
Rated power frequency withstand voltage, dry
95 kV
Rated normal current
400 Amps
Rated short time withstand current for 3 sec, min.
18.0 kA
Minimum creepage distance of insulators
900 mm
We are China Gang Operated Air Break Switches 33 manufacture and supplier,You can get more details with Email,you will get cheap price or factory price.
Get Latest Price Request a quote
Popular Disconnector Switch Products
Spindle (pin) 33kv 200kg M20X200
High Quality Onload Break Switch Load Break Switch
24kv 3 Phase Outdoor Switch Disconnector
33kv/69kv Outdoor High Voltage Three Phase Isolator Disconnector Switch
Popular jgtrade1 Products
2 Threads Latex Glovespolyester Linergreen
Low Voltage Draw out Switchgear
Terminal Connectors for Heat-Resistant Conductor Type Sy, Group a
Yh10W-48, 48kv 10ka Surge Arrester
Popular Rotary Switch Products
24kv 3 Phase Outdoor Switch Disconnector
34.5/0.433kv, 315kVA Pole Mounted Distribution Transformer
Rgw 1 Type Three Pole Outdoor Disconnector with Fuse -Bases (Export)
Popular Switch Disconnector Products
33kv Isolator Current 2000A with Earth Switch Isolator
Hangzhou High Voltage Ceramics Drop out Fuse 33kv 24kv 11kv
33kv Porcelan Pin-Type Insulator
High -Voltage Isolate Switch 24kv 1250A
Tags: Disconnector Switch, jgtrade1, Rotary Switch, Switch Disconnector