Fuse Link, 3 AMPS -T
Fuse Link, 3 AMPS -T image
Get Latest Price Request a quote
Quick Details
Product Details
Markings shall be provided on the fuse-links in accordance with ANSI/IEEE Standards.
Maximum altitude above mean sea level less than 1,000 m;
Maximum ambient air temperature 400C;
Maximum daily average ambient air temperature 300C;
Minimum ambient temperature150C; and
Maximum relative humidity 100%.
Requirements
The fuse-links and fuse-end fittings shall be of the following ratings (table below) and comply with the IEEE Std C37.4 -2016 or an equivalent international standard. The fuse- links shall be used primarily for protection of distribution transformers, laterals and sub- laterals.
The fuse links shall be capable of withstanding 125% ofthe transformer rated full load current continuously and periodic over-loads up to 150% ofthe transformer rated full load current.
The current-time characteristics of the fuse-links offered shall be submitted with the tender
Markings shall be provided on the fuse-links in accordance with ANSI/IEEE Standards.
| S/N | TECHNICAL DETAILS | UNITS | DATA |
| 1. | Description | Station type lightning arrestor complete with steel support structures. |
|
| 2. | Type | Zinc oxide gapless lightning arrestor |
|
| System parameters | |||
| 3. | Nominal system voltage | kV | 66 |
| 4. | Highest system voltage | kV | 72.5 |
| 5. | Power frequency | Hz | 50 |
| 6. | Type of system earthing | Effective/Non effective | |
| 7. | Type of arrestor connection to system | Line to ground | |
| 3. Ratings and type of surge arrester |
|||
| 8. | Rated voltage of surge arrester | kV rms | 54 |
| 9. | Nominal, 8/20 µs, discharge current rating of surge arrester | kA peak | 10 |
| 10. | Maximum continuous operating voltage of surge arrester | kV | 43 |
| 11. | Minimum one minute wet power frequency withstand voltage | kVrms | 140 |
| of external insulation of surge arrester housing | |||
| 12. | Maximum steep current impulse residual voltage for a 2 kA, 30/60 µs, discharge current |
kVpeak | 104 |
| 13. | Maximum lightning impulse residual voltage for a 10 kA, 8/20 µs, discharge current |
kVpeak | 127 |
| 14. | Minimum lightning, 1,2/50 µs, impulse withstand level of external insulation of surge arrester housing |
325 | |
| 15. | Line discharge class rating | 2 | |
| 16. | Lighting arrestor counter, leakage current meter and their accessories to be provided |
Yes/No | Yes |
| 17. | Gapless or gapped type metal–oxide surge arrester | Gapless | |
| 18. | Insulation Material | Porcelain | |
| 19. | Cantilever strength of surge arrester | Nm | 3000 |
| 20. | Rated frequency of surge arrester | Hz | 50 |
| 21. | Maximum angle from vertical at which surge arrester is fully functional |
Deg | 45 |
| 22. | Design altitude of surge arrester (above sea level) | m | 1400 m |
| 23. | Design ambient temperature of surge arrester | oC | –1 to 40 |
| 24. | Humidity | % | 85 |
| 25. | Specific phase–to–ground creepage of surge arrester | .mm/kV | 25 |
| 26. | Corrosion protection of metal and alloy parts: galvanising specification and/or stainless steel grade |
to SABS 763 or 316 stainless steel |
|
| 27. | Previous type test results/certificate to be provided with bid | Yes/No | Yes |
| 28. | Design drawings showing dimensions including foundations and brochures to be provided with bid |
Yes/No | Yes |
| 29. | Quality Assurance certification to be provided with the bid | Yes/No | Yes |
| 30. | Routine test results/certificate to be provided on delivery | Yes/No | Yes |
| 31. | Galvanized steel support structures complete with bolts & washers to be provided on delivery |
Yes/No | Yes |
| 32. | Applicable standard | IEC60099 |
Recommended for You
Not exactly what you want?
Post Sourcing Request
Hot Searches
Protective Device
Power Surge
Surge Protection
Arrester
Surge Protector
We are China Fuse Link, 3 AMPS -T manufacture and supplier,You can get more details with Email,you will get cheap price or factory price.
Get Latest Price Request a quote
Popular jgtrade1 Products
Yh10W-36, Sharp Head 36kv 10ka Surge Arrester
Supports for Tubular Bus-Bar Type Mggb
Popular Lightning Arrester Products
Composite Gapless Zinc Oxide Lightning Arrester 33kv Lighting Arrester
Yh5wz 35kv Zinc Oxide Distribution Line Arresters for High Voltage Power Station
Yh5w-11, Lighting Arrester Surge Arrester
Kema Type Test Report 220kv Line Equipment Station Silicone Rubber Arrester
24kv Porcelain Type Surge Arrester Y5c-24
Popular Lightning Arrestors Products
Wholesale High Voltage Porcelain Metal Oxide Lightning Arrestors Surge Arresters
Popular Surge Arrester Products
3r-8 Series Tb 10ka Gdt Diode for Surge Arrester
Distribution Type Surge Arrester Post Type Lightning Arrester
Factory Bulk 3-36kv Thunder Arrester Polymeric Composite Lightning Arrester
Good Quality 9kv 11kv 24kv 33kv High Voltage Porcelain Lightning Arrester
18kv Polymeric Housed Metal Oxide Surge Arrester
Substation 24kv 33kv 66kv Polymeric Metal-Oxide Lightning Arrester
Tags: jgtrade1, Lightning Arrester, Lightning Arrestors, Surge Arrester