Fuse Link, 3 AMPS -T
Fuse Link, 3 AMPS -T image
Get Latest Price Request a quote
Quick Details
Product Details
Markings shall be provided on the fuse-links in accordance with ANSI/IEEE Standards.
Maximum altitude above mean sea level less than 1,000 m;
Maximum ambient air temperature 400C;
Maximum daily average ambient air temperature 300C;
Minimum ambient temperature150C; and
Maximum relative humidity 100%.
Requirements
The fuse-links and fuse-end fittings shall be of the following ratings (table below) and comply with the IEEE Std C37.4 -2016 or an equivalent international standard. The fuse- links shall be used primarily for protection of distribution transformers, laterals and sub- laterals.
The fuse links shall be capable of withstanding 125% ofthe transformer rated full load current continuously and periodic over-loads up to 150% ofthe transformer rated full load current.
The current-time characteristics of the fuse-links offered shall be submitted with the tender
Markings shall be provided on the fuse-links in accordance with ANSI/IEEE Standards.
S/N | TECHNICAL DETAILS | UNITS | DATA |
1. | Description | Station type lightning arrestor complete with steel support structures. |
|
2. | Type | Zinc oxide gapless lightning arrestor |
|
System parameters | |||
3. | Nominal system voltage | kV | 66 |
4. | Highest system voltage | kV | 72.5 |
5. | Power frequency | Hz | 50 |
6. | Type of system earthing | Effective/Non effective | |
7. | Type of arrestor connection to system | Line to ground | |
3. Ratings and type of surge arrester |
|||
8. | Rated voltage of surge arrester | kV rms | 54 |
9. | Nominal, 8/20 µs, discharge current rating of surge arrester | kA peak | 10 |
10. | Maximum continuous operating voltage of surge arrester | kV | 43 |
11. | Minimum one minute wet power frequency withstand voltage | kVrms | 140 |
of external insulation of surge arrester housing | |||
12. | Maximum steep current impulse residual voltage for a 2 kA, 30/60 µs, discharge current |
kVpeak | 104 |
13. | Maximum lightning impulse residual voltage for a 10 kA, 8/20 µs, discharge current |
kVpeak | 127 |
14. | Minimum lightning, 1,2/50 µs, impulse withstand level of external insulation of surge arrester housing |
325 | |
15. | Line discharge class rating | 2 | |
16. | Lighting arrestor counter, leakage current meter and their accessories to be provided |
Yes/No | Yes |
17. | Gapless or gapped type metal–oxide surge arrester | Gapless | |
18. | Insulation Material | Porcelain | |
19. | Cantilever strength of surge arrester | Nm | 3000 |
20. | Rated frequency of surge arrester | Hz | 50 |
21. | Maximum angle from vertical at which surge arrester is fully functional |
Deg | 45 |
22. | Design altitude of surge arrester (above sea level) | m | 1400 m |
23. | Design ambient temperature of surge arrester | oC | –1 to 40 |
24. | Humidity | % | 85 |
25. | Specific phase–to–ground creepage of surge arrester | .mm/kV | 25 |
26. | Corrosion protection of metal and alloy parts: galvanising specification and/or stainless steel grade |
to SABS 763 or 316 stainless steel |
|
27. | Previous type test results/certificate to be provided with bid | Yes/No | Yes |
28. | Design drawings showing dimensions including foundations and brochures to be provided with bid |
Yes/No | Yes |
29. | Quality Assurance certification to be provided with the bid | Yes/No | Yes |
30. | Routine test results/certificate to be provided on delivery | Yes/No | Yes |
31. | Galvanized steel support structures complete with bolts & washers to be provided on delivery |
Yes/No | Yes |
32. | Applicable standard | IEC60099 |
Recommended for You
Not exactly what you want?
Post Sourcing Request
Hot Searches
Protective Device
Power Surge
Surge Protection
Arrester
Surge Protector
We are China Fuse Link, 3 AMPS -T manufacture and supplier,You can get more details with Email,you will get cheap price or factory price.
Get Latest Price Request a quote
Popular jgtrade1 Products
Sleeve; Pre-Insul Service Ysu 2W 2W
Insulation Piercing Clamp 25-75sqmm
Fuse Cutout, Drop out Fuses 33kv 200A
Popular Lightning Arrester Products
33kv Silicon Type Surge Arrester Cma10W-33
Lightning Arrester 10 Ka Type Metal Gapless Oxide 11kv
24kv Composite Surge Arrester Lightning Arrester Metal Oxide Gapless Polymer Synthetic Polymeric
63kv to 220kv Sealed Metal Oxide Surge Arrester for Gis
Station Class High Voltage 21kv Gapless Polymeric Surge Arrester 10ka
30kv Polymeric Housed Metal-Oxide Lightning Arrester Without Gaps
Popular Lightning Arrestors Products
Cable 19'33kv 3core 70mm2 Insulated (Underground Cable)
Yh10W-24, 24kv 10ka Surge Arrester
Hy5wz-3.8/13.5 Zinc-Oxide Arrester
Popular Surge Arrester Products
Wedged Insulation Strain Clamp
Hot Sell Gapless Zinc Oxide Lighting Arrester
Yh10W-60, 60kv- 10ka Surge Arrester
10ka Polymer Housed Lightning Arrester Surgearrester
11kv High Voltage Metal Oxide Lightning Arrester
Substation 33kv Types of Lightning Arrester with Disconnector
Tags: jgtrade1, Lightning Arrester, Lightning Arrestors, Surge Arrester