kV to 38 kV grounded systems with 100 or 200 A nominal currents.
Especially designed to protect transformers, capacitors, cables or lines.
It is robust construction, made of rigorously tested material, will interrupt all faults under the
most severe conditions, maintaining mechanical and electric characteristics.
The inserts, hardware and structural bolts and nuts are made from heavy galvanized steel.
The Fuse Cutout type OEI can be applied on all three-phase system rated at or below the maximum
operational rating of the cutout.
| S/N | Description | Units | Schedule A | Schedule B | |
| 1 | Current ratings | A | 5 | ||
| 2 | Frequency | Hz | 50 | ||
| 3 | Rated Speed ratio | Type K as per IEC 60282 -2 |
|||
| 4 | Class of fuse link | Class B as per IEC 60282-2 |
|||
| 5 | Fuse element | Tin or Silver | |||
| 6 | Following Routine test results shall be provided on delivery of fuse links | Yes/No |
a) a static strength test; and | Yes | |
| b) a resistance test, with the fuse-link under strain. |
Yes |
||||
| 7 | The following tests shall be performed on one fuse-link per batch and test results provided on delivery of fuse links: |
Yes/No |
a)confirmation of the time/current characteristics; and |
Yes |
|
| b) a dynamic strength test. | Yes | ||||
| 8 | Drawing showing construction and dimensions as per figure 1 below to be provided with bid |
Yes/No | Yes | ||
| 9 | Previous type tests reports/certificate to be provided on bid. |
Yes/No |
Yes |
||
| 10 | Altitude above sea level | m | 1400 | ||
| 11 | Ambient operating | oC | -1 to 40 | ||
| Performance Characteristic | |
| Applied standard | IEEE C37.42-2009 |
| Catalog number | |
| Nominal system voltage kV | 22 |
| Rated Frequency Hz | 50 |
| Rated m aximum(design) voltage | 27 |
| Rated Continuous current A-RMS | 100 |
| Rated Interrupting current asymmetrical/symmetrical A-RMS | 12000/8000 |
| BIL 1.2×50 µs kV-peak | 125 |
| Minimum critical impulse flashover voltage(CFO)KV peak | 140 |
| Dry withstand voltage kV-RMS | 42 |
| Wet withstand voltage kV-RMS | 36 |
| Creepage distance to group Min.mm | 320 |
| Minimum creepage factor of insulator (Creepage Distance/arcing distance) | 2 |
| Performance Characteristic | |
| Applied standard | IEC60282-2 |
| Catalog number | |
| Nominal system voltage kV | 11 |
| Rated Frequency Hz | 50 |
| Rated m aximum(design) voltage | 12 |
| Rated Continuous current A-RMS | 100 |
| Rated Interrupting current asymmetrical/symmetrical A-RMS | 12000/8000 |
| BIL 1.2×50 µs kV-peak | 125 |
| Minimum critical impulse flashover voltage(CFO)KV peak | 140 |
| Dry withstand voltage kV-RMS | 42 |
| Wet withstand voltage kV-RMS | 36 |
| Creepage distance to group Min.mm | 372 |
| Minimum creepage factor of insulator (Creepage Distance/arcing distance) | N/A |
| Performance Characteristic | |
| Applied standard | IEEE C37.42-2009 |
| Catalog number | |
| Nominal system voltage kV | 33 |
| Rated Frequency Hz | 50 |
| Rated m aximum(design) voltage | 38 |
| Rated Continuous current A-RMS | 100 |
| Rated Interrupting current asymmetrical/symmetrical A-RMS | 8000/5000 |
| BIL 1.2×50 µs kV-peak | 150 |
| Minimum critical impulse flashover voltage(CFO)KV peak | 165 |
| Dry withstand voltage kV-RMS | 70 |
| Wet withstand voltage kV-RMS | 60 |
| Creepage distance to group Min.mm | 650 |
| Minimum creepage factor of insulator (Creepage Distance/arcing distance) | 2.3 |
| DIMENSION(mm) | |||||
| RATED CURRENT (A) |
A | B | C | D | L MN |
| 1 to 25 | 12.5+0.2 | 19.0+0.2 | 6.5 | 2.0 | 533,600,787 |
| 30 to 40 | 12.5+0.2 | 19.0+0.2 | 8.0 | 3.0 | 533,600,787 |
| 50 to 100 | 19.0+0.3 | not applicable | 9.0 | 5.0 | 533,600,787 |
| 140 to 200 | 19.0+0.3 | not applicable | 13.0 | 7.0 | 533,600,787 |
Recommended for You
Not exactly what you want?
Post Sourcing Request
Hot Searches
Voltage Fuse
Protection Fuse
Fuse Box
Low Voltage Fuse
Fast Fuse
We are China Ut Connectors manufacture and supplier,You can get more details with Email,you will get cheap price or factory price.
Get Latest Price Request a quote
Popular Fuse Link Products
13G Nitrile Glovespolyesterorange 7-11
Nitrile Gloves, Safety Cuff3/4 Nitrile Coatedblue 7-11
2 Threads Latex Glovespolyester Linerorange7-11
Square Frame Type Spacer-Dampers for 500kv Lines
Popular High Voltage Fuse Products
Polymer Fuse Cutout, Drop out Fuses 36kv 200A
Polymer Fuse Cutout, Drop out Fuses 18kv 200A
Polymer Fuse Cutout, Drop out Fuses 27kv 100A
Hrw 12/35kv Outdoor High Voltage Protection AC Drop-out Fuse
Popular jgtrade1 Products
Best Price36kv 100A Ceramic Types Drop out Fuses Cutout/Cut out Fuse
Polymeric Expulsion Fuses 36kv 100A
High -Voltage Isolator /Earth Switch 12kv 400A
Switch Disconnector Fuse Holder, 27 Kv - 100 AMP, Without Arc Chute
Terminal Connectors Type Sy, Compression Type, Group a
Splice Full Traction ACSR-AAAC No. 1/0 to 1/0 AWG