Disconnect Switch Isolator Single-Pole 17.5kv 600A
Disconnect Switch Isolator Single-Pole 17.5kv 600A image
Get Latest Price Request a quote
Basic Info.
Product Description
TECHNICAL SPECIFICATIONS
Single Pole Switch Isolator, 22kV, 800/630A
1.0 General
The single pole switch isolator are used for isolating feeders and lines.
2.0 Service Conditions
a. Ambient Temperature : 5°C – 50°C
b. Relative Humidity : 95% at 45°C (Tropicalised)
c. Environmental condition: Tropical climate with polluted atmosphere
3.0 System Parameters
The switch shall be used on a network having the following characteristics:-
a. Nominal voltage : 22 kV
b. Maximum voltage : 24 kV
c. Earthing Arrangement : Effectively earthed
d. Frequency : 50 Hz
4.0 Standards
The item conform to IEC 60129 or IEC62271-102 Ed.1.0 (2001)-Alternating current disconnectors & earthing switches or any other equivalent international standards.
It will be the responsibility of our to prove equivalency of his standard with one of these 2 standards mentioned above.
5.0 Technical requirements
a. Rated voltage : 24kV
b. Rated continuous current : 630A
c. Impulse Voltage Level (BIL) : 150kV
d. Rated Short time withstand current : 25kA/1 sec
e. Rated peak withstand current : 62kA
f. Creepage Distance : 600mm
6.0 Basic Features
The isolating switch have the following characteristics;
– Single pole type suitable for outdoor use
– Double insulator construction
– Fitted with appropriate latching device to prevent accidental opening due to faults, line vibration, wind or other environmental influences
– Operated by portable insulated hook stick
– Suitable for underslung or vertical mounting
– Fitted with Tin plated palms suitable for Copper and Aluminium compression lugs
– The palms are suitable to accommodate conductor AAAC 150mm2 to BSEN50183: 2000 or armoured cable XLPE insulated 300mm2 Copper or 240mm2 Aluminium to IEC 502
– Incoming and outgoing conductor/cable are connected on fixed parts and not on rocking parts
Information to be furnished with the offer
The following are furnished with the offer:
a) Type Test Reports conforming to the relevant IEC Standards
b) Catalogues, Technical literature and dimensional drawings of the item offered
c) Detailed list of components
d) Duly filled Schedule of guaranteed particulars (Annexure A).
e) ISO 9001:2000 Certificate including the requirements as defined by clause 7 of the ISO 9001:2000 Standard.
f) A list of the supplier’s orders for the last five years.
GUARANTEED PARTICULARS
Single pole switch isolator, 22kV , 800/630A
POV2568
| Serial No. | Description | ||
| 1. | Manufacturer’s Reference name/code | OEIpower | |
| 2. | Drawing No. | IS-24 | |
| 3. | Country of Origin | ||
| 4. | Standard specifications to which the switch conform | IEC62271-102 | |
| 5. | Rated Voltage | kV | 24 |
| 6. | Rated frequency | Hz | 50 |
| 7. | Rated continuous current | A | 630 |
| 8. | Rated short time current duration |
kA sec |
25kA/1 sec |
| 9. | Impulse voltage withstand 1.2/50µ S |
kV |
150 |
| 10. | Total creepage distance | mm | 600 |
We are China Disconnect Switch Isolator Single-Pole 17.5kv 600A manufacture and supplier,You can get more details with Email,you will get cheap price or factory price.
Get Latest Price Request a quote
Popular Disconnect Switch Isolator Single-Pole 17.5kv 600A Products
Popular Disconnector Switch Products
Gw9 -12/630 Series Hv Outdoor High Voltage Disconnect /Switch Isolator
High-Voltage Disconnector Switch 126kv
11kv Outdoor Pole Mounted ABS Load Air Break Switch
120sqmm Bimetallic Cable Lugs for Hv Side of Transformer
High Quality Gw9-12kv Outdoor Disconnect Switch Air Break Switch
Popular jgtrade1 Products
Iacm 24kv 50A 3 Phase Outdoor Switch Disconnector
Pulling Clamp with Pulley for ACSR 120‘ 20 mm2 Conductor
13G Latex Gloves Polyester Liner Black 7-11
Yh6w-24 Sharp Head 6kv 24ka Surge Arrester
Popular Switch Disconnector Products
12kv Surge Arrester Outdoor Vertical Operate Semi Pantograph Type Isolator Switch 3 Phase
Electrical Equipment Supplies Drop-out Types Ceramic Fuses of High Voltage
11kv to 33kv Power Distribution Equipment Ceramic Dropout Fuse Types
126kv 1250A Lightning Protection High Voltage Disconnector
Outdoor High Voltage Disconnecting Switch/ Isolator Power
Tags: Disconnect Switch Isolator Single-Pole 17.5kv 600A, Disconnector Switch, jgtrade1, Switch Disconnector