The following documents were referred to during the preparation of this specification. In case of conflict, the provisions of this specification shall take precedence.
IEC 129:1975: Alternating Current Disconnectors (Isolators) and Earthing Switches
IEC 60694:2002: Common Specifications for High Voltage Switchgear and Controlgear
BS 729: Hot dip galvanized coating on iron and steel articles
IEC62271-102
Isolator (Disconnector) – a mechanical switching device which provides, in the open position, an isolating distance in accordance with Electrical Safety requirements.
SERVICE CONDITIONS
The isolator shall be suitable for continuous operation outdoors in tropical areas at altitudes of up to 2200m above sea level, humidities of up to 90%, average ambient temperature of +30ºC with a minimum of -1ºC and a maximum of +40ºC and heavy saline conditions along the coast.
4.2. DESIGN AND CONSTRUCTION
4.2.1 The Isolator, Solid Link shall be designed and constructed in accordance with IEC 129 and IEC 60694.
4.2.2 The isolating link shall be of the vertical opening, designed for single phase manual operation. It shall be easily removed and replaced by using a portable operating rod.
4.2.3 The isolating link shall incorporate double porcelain insulators to suit voltage requirements and mounted on hot dipped galvanised steel under base suitable for vertical mounting.
4.2.4 The isolating link shall be arranged so that each unit is mounted independently on an angle bracket. It shall be supplied complete with the angle bracket and accessories suitable for mounting on ‘U’ type steel channel. The drawings to be submitted shall indicate all the applicable mounting positions.
4.2.5 The isolator shall be designed such that in fully open position, it shall provide adequate electrical isolation between the contacts on each phase. It shall conform to the requirement as single point isolation for safety.
4.2.6 All steel parts shall be hot dip galvanized to BS 729. The minimum coating of galvanizing required is 80 microns.
4.2.7 The solid link shall be removable from the mounting by use of operating rod.
4.2.8 All current carrying parts of the isolator shall be made of high conductivity material.
4.2.9 The isolator shall be fitted with clamp connectors for Aluminium (ACSR) conductor of Aluminium (ACSR)conductor of up to 18.2mm diameter.
The rating of the complete isolator shall be as follows: –
Rated voltage
36 kV
Rated frequency
50 Hz
Rated lightning impulse withstand voltage
200 kV
Rated power frequency withstand voltage, dry
95 kV
Rated normal current
400 Amps
Rated short time withstand current for 3 sec, min.
18.0 kA
Minimum creepage distance of insulators
900 mm
We are China Substation Disconnector Double Break Switch manufacture and supplier,You can get more details with Email,you will get cheap price or factory price.
Get Latest Price Request a quote
Popular Disconnector Switch Products
Gw4 Outdoor AC High Voltage Disconnector Switch / Hv Isolation Switch
Grounding Switch 145 Kv, 31.5 Ka
High-Voltage Disconnector Switch 33kv
Popular jgtrade1 Products
Fuse Link High Voltage Type “ T”
Yh10W-12, Sharp Head 10kv 12ka Surge Arrester
Fuse Cutout, Drop out Fuses 36kv 100A
Fuse Cutout, Drop out Fuses 15kv 100A
Yh10W-33kv, Sharp Head 33kv 10ka Surge Arrester
Popular Rotary Switch Products
75kv Isolator Switch Images Vertical Break Disconnector and Isolator
22kv Porcelan Pin-Type Insulator
Seccionador Tripolar, Break Isolator, Substation
Chave Fusivel Porcelana 27kv Disconnector Switch
Popular Switch Disconnector Products
Terminal Connectors Bolted Type, Type SL, Group B
High Voltage Power Distribution Equipment 20kv 24kv 33kv Fuse Cutout
12V 3 Phase Electrical Load Break Indoor High-Voltage Isolation Switch Gn19
High-Voltage Disconnector Switch 126kv
252kv 3 Pole High Voltage Disconnectors
Tags: Disconnector Switch, jgtrade1, Rotary Switch, Switch Disconnector