Aluminum Conductor XLPE Insulated and Hffr Sheath Na2xh Power Cable
Aluminum Conductor XLPE Insulated and Hffr Sheath Na2xh Power Cable image
Get Latest Price Request a quote
- Overview
- Product Description
- Product Parameters
Basic Info.
Product Description
Power cable 0,6/1 kV with Al conductors, XLPE insulated and HFFR sheathed -NA2XH
Application:
In earth, ducts, on support brackets, in dry and wet conditions etc., where one does not expect mechanical damages and the cables are not exposed to the mechanical tensile strain. In urban networks, industrial plants, electric power plants and other electricity consumers and for connection of control devices in industry, traffic etc.
NA2XH CABLE CONSTRUCTION:
Conductors: Al, class 1 (RE/SE) or class 2 (RM/SM) according to EN 60228
Insulation: XLPE compound DIX 3
Bedding: Extruded elastomere or plastomere compound or plastic tape
Sheath: HFFR compound HM 4
Technical data:
CPR class: Eca
Test voltage: 4 kV
Rated voltage: 0,6/1,0 kV
Bending radius (min): single-core – 15D;
multicore – 12D
Min. laying temperature: -5°C
Max. conductor temperature: 90°C
Max. short-circuit temperature: 250°C
Industry: Building & Construction, Transmission, Distribution & Power Networks
Standard: IEC 60502-1, SI 1516-1
Type: Industrial Cable, LSZH Cable, Power Network & Local Distribution Cable
NA2XH CABLE DIMENSION:
SINGLE – CORE CABLES: | ||||||||
NOMINAL CROSS SECTION | CONDUCTOR CONSTRUCTION | NOM. THICKNESS OF INSUL. | OUTER DIAM. (APPROX.) | METAL WEIGHT | CABLE WEIGHT (APPROX.) | MAX. RESISTANCE AT 20°C | CURRENT CAPACITY IN AIR | CURRENT CAPACITY IN EARTH |
mm2 | mm | mm | kg/km | kg/km | ohm/km | A | A | |
1×16 | rm | 0,7 | 9,5 | 46,2 | 122 | 1,910 | – | – |
1×25 | rm | 0,9 | 11,9 | 72,5 | 175 | 1,200 | 106 | 114 |
1×35 | rm | 0,9 | 13,0 | 101,5 | 206 | 0,868 | 130 | 136 |
1×50 | rm | 1,0 | 14,9 | 145,0 | 267 | 0,641 | 161 | 162 |
1×70 | rm | 1,1 | 17,0 | 203,0 | 358 | 0,443 | 204 | 199 |
1×95 | rm | 1,1 | 18,9 | 275,5 | 451 | 0,320 | 252 | 238 |
1×120 | rm | 1,2 | 20,7 | 348,0 | 546 | 0,253 | 295 | 272 |
1×150 | rm | 1,4 | 22,7 | 435,0 | 655 | 0,206 | 339 | 305 |
1×185 | rm | 1,6 | 25,1 | 536,5 | 800 | 0,164 | 395 | 347 |
1×240 | rm | 1,7 | 27,6 | 696,0 | 987 | 0,125 | 472 | 404 |
1×300 | rm | 1,8 | 31,9 | 870,0 | 1324 | 0,100 | 547 | 457 |
1×400 | rm | 2,0 | 34,9 | 1160,0 | 1640 | 0,0778 | 643 | 525 |
1×500 | rm | 2,2 | 39,3 | 1450,0 | 2030 | 0,0605 | 754 | 601 |
1×630 | rm | 2,4 | 44,1 | 1827,0 | 2400 | 0,0469 | 882 | 687 |
1×800 | rm | 2,6 | 46,5 | 2320,0 | 2505 | 0,0367 | 1019 | 776 |
1×1000 | rm | 2,8 | 52,0 | 2900,0 | 3115 | 0,0291 | 1157 | 865 |
THREE – CORE CABLES: | ||||||||
NOMINAL CROSS SECTION | CONDUCTOR CONSTRUCTION | NOM. THICKNESS OF INSUL. | OUTER DIAM. (APPROX.) | METAL WEIGHT | CABLE WEIGHT (APPROX.) | MAX. RESISTANCE AT 20°C | CURRENT CAPACITY IN AIR | CURRENT CAPACITY IN EARTH |
mm2 | mm | mm | kg/km | kg/km | ohm/km | A | A | |
3×16 | rm | 0,7 | 16,5 | 139,2 | 397 | 1,910 | – | – |
3×25 | rm | 0,9 | 20,0 | 217,5 | 587 | 1,200 | 102 | 112 |
3×35 | rm/sm | 0,9 | 22,5 | 304,5 | 531 | 0,868 | 126 | 135 |
3×50 | rm | 1,0 | 27,6 | 435,0 | 1007 | 0,641 | 149 | 158 |
3×70 | rm | 1,1 | 30,6 | 609,0 | 1401 | 0,443 | 191 | 196 |
3×95 | rm | 1,1 | 33,8 | 826,5 | 1801 | 0,320 | 234 | 234 |
3×120 | rm | 1,2 | 37,5 | 1044,0 | 2226 | 0,253 | 273 | 268 |
3×50 | se/sm | 1,0 | 26,0 | 435,0 | 720 | 0,641 | 149 | 158 |
3×70 | se/sm | 1,1 | 29,7 | 609,0 | 963 | 0,443 | 191 | 196 |
3×95 | se/sm | 1,1 | 33,4 | 826,5 | 1246 | 0,320 | 234 | 234 |
3×120 | se/sm | 1,2 | 37,1 | 1044,0 | 1545 | 0,253 | 273 | 268 |
3×150 | se/sm | 1,4 | 41,2 | 1305,0 | 1916 | 0,206 | 311 | 300 |
3×185 | se/sm | 1,6 | 45,7 | 1609,5 | 2347 | 0,164 | 360 | 342 |
3×240 | se/sm | 1,7 | 51,6 | 2088,0 | 2987 | 0,125 | 427 | 398 |
3×300 | se/sm | 1,8 | 56,7 | 2160,0 | 3663 | 0,100 | 507 | 457 |
FOUR – CORE CABLES | ||||||||
NOMINAL CROSS SECTION | CONDUCTOR CONSTRUCTION | NOM. THICKNESS OF INSUL. | OUTER DIAM. (APPROX.) | METAL WEIGHT | CABLE WEIGHT (APPROX.) | MAX. RESISTANCE AT 20°C | CURRENT CAPACITY IN AIR | CURRENT CAPACITY IN EARTH |
mm2 | mm | mm | kg/km | kg/km | ohm/km | A | A | |
3×70+35 | sm/sm | 1,1/0,9 | 28,8 | 655,4 | 935 | 0,443/0,868 | 191 | 196 |
3×95+50 | sm/sm | 1,1/1,0 | 32,2 | 899,0 | 1120 | 0,320/0,641 | 234 | 234 |
3×120+70 | sm/sm | 1,2/1,1 | 34,6 | 1145,5 | 1430 | 0,253/0,443 | 273 | 268 |
3×150+70 | sm/sm | 1,4/1,1 | 38,5 | 1450,0 | 1950 | 0,206/0,443 | 311 | 300 |
3×185+95 | sm/sm | 1,6/1,1 | 42,4 | 1812,5 | 2345 | 0,164/0,320 | 360 | 342 |
3×240+120 | sm/sm | 1,7/1,2 | 47,2 | 2363,5 | 2980 | 0,125/0,253 | 427 | 398 |
4×35 | sm | 0,9 | 25,9 | 406,0 | 690 | 0,868 | 126 | 135 |
4×50 | se/sm | 1,0 | 28,4 | 580,0 | 832 | 0,641 | 149 | 158 |
4×70 | se/sm | 1,1 | 32,4 | 812,0 | 1234 | 0,443 | 191 | 196 |
4×95 | se/sm | 1,1 | 35,6 | 1102,0 | 1460 | 0,320 | 234 | 234 |
4×120 | se/sm | 1,2 | 40,6 | 1392,0 | 1861 | 0,253 | 273 | 268 |
4×150 | se/sm | 1,4 | 44,8 | 1740,0 | 2386 | 0,206 | 311 | 300 |
4×185 | se/sm | 1,6 | 49,2 | 2146,0 | 2866 | 0,164 | 360 | 342 |
4×240 | se/sm | 1,7 | 54,9 | 2784,0 | 3616 | 0,125 | 427 | 398 |
4×300 | se/sm | 1,8 | 58,8 | 3480,0 | 4500 | 0,100 | 507 | 457 |
FOUR – CORE CABLES WITH CONTROL CONDUCTOR | ||||||||
NOMINAL CROSS SECTION | CONDUCTOR CONSTRUCTION | NOM. THICKNESS OF INSUL. | OUTER DIAM. (APPROX.) | METAL WEIGHT | CABLE WEIGHT (APPROX.) | MAX. RESISTANCE AT 20°C | CURRENT CAPACITY IN AIR | CURRENT CAPACITY IN EARTH |
mm2 | mm | mm | kg/km | kg/km | ohm/km | A | A | |
4×16+1,5 | re/rm | 0,7 | 22,1 | 185,6 | 615 | 1,910 | – | – |
4×25+1,5 | re/rm | 0,9 | 26,2 | 290,0 | 870 | 1,200 | 102 | 112 |
4×35+1,5 | re/rm | 0,9 | 28,9 | 406,0 | 1074 | 0,868 | 126 | 135 |
4×35+1,5 | sm | 0,9 | 23,1 | 406,0 | 630 | 0,868 | 126 | 135 |
4×50+1,5 | se/sm | 1,0 | 26,0 | 580,0 | 847 | 0,641 | 149 | 158 |
4×70+1,5 | se/sm | 1,1 | 30,0 | 812,0 | 1135 | 0,443 | 191 | 196 |
4×95+1,5 | se/sm | 1,1 | 33,6 | 1102,0 | 1480 | 0,320 | 234 | 234 |
4×120+1,5 | se/sm | 1,2 | 37,3 | 1392,0 | 1826 | 0,253 | 273 | 268 |
4×150+1,5 | se/sm | 1,4 | 42,0 | 1740,0 | 2282 | 0,206 | 311 | 300 |
4×185+1,5 | se/sm | 1,6 | 46,3 | 2146,0 | 2766 | 0,164 | 360 | 342 |
4×240+1,5 | se/sm | 1,7 | 52,1 | 2784,0 | 3572 | 0,125 | 427 | 398 |
4×300+1,5 | se/sm | 1,8 | 56,8 | 3480,0 | 4374 | 0,100 | 507 | 457 |
SIGNAL CU WIRE: Nominal cross section: 1,5 mm² Max. resistance at 20°C :12,1 Ω/km Nom. thicknss of insul. :0,7mm Outer diameter :2,9mm
FIVE – CORE CABLES | ||||||||
NOMINAL CROSS SECTION | CONDUCTOR CONSTRUCTION | NOM. THICKNESS OF INSUL. | OUTER DIAM. (APPROX.) | METAL WEIGHT | CABLE WEIGHT (APPROX.) | MAX. RESISTANCE AT 20°C | CURRENT CAPACITY IN AIR | CURRENT CAPACITY IN EARTH |
mm2 | mm | mm | kg/km | kg/km | ohm/km | A | A | |
5×16 | rm | 0,7 | 23,4 | 232,0 | 625 | 1,910 | – | – |
5×25 | rm | 0,9 | 28,2 | 362,5 | 950 | 1,200 | 102 | 112 |
5×35 | rm | 0,9 | 31,0 | 507,5 | 1195 | 0,868 | 126 | 135 |
5×50 | rm | 1,0 | 36,8 | 725,0 | 1540 | 0,641 | 149 | 158 |
5×70 | rm | 1,1 | 42,8 | 1015,0 | 2240 | 0,443 | 191 | 196 |
5×95 | rm | 1,1 | 48,5 | 1377,5 | 3015 | 0,320 | 234 | 234 |
5×120 | rm | 1,2 | 53,6 | 1740,0 | 3580 | 0,253 | 273 | 268 |
NA2XH CABLE SELECTION:
In addition to our portfolio of European power cables we also supply British standard low voltage power cables including armoured cable with its LSZH outer sheathing. Our technical has a wealth of experience in providing support in the selection of the right cable for your application. Please call to discuss your specific application.
If you have another question, pls feel free to contact us below
We are China Aluminum Conductor XLPE Insulated and Hffr Sheath Na2xh Power Cable manufacture and supplier,You can get more details with Email,you will get cheap price or factory price.
Get Latest Price Request a quote
Popular Aluminum Conductor XLPE Insulated and Hffr Sheath Na2xh Power Cable Products
Popular Na2xh Cable Products
AC2xh Na2xh XLPE Insulated Halogen Free Power Cable
Na2xh 0.6/1 K Al Conductors XLPE Insulated and Hffr Sheathed Aluminum Cable
Popular Power Cable Products
XLPE Insulated Power Cable PVC Sheathed Low Voltage Power Cable
Yjv Yjv22 Yjv32 0.6/1kv Cu/XLPE/PVC Steel Wire or Tape Armour Power Cable with Good Price
Low Voltage 50mm2 Fire Resistant Power Cable Waterproof Underground
Mv-90, Power Cable, 8 Kv, 3/C, Cu/XLPE/Cts/PVC (ICEA S-93-639/NEMA WC71/UL 1072)
25mm 70mm Copper Earth Grounding Cable
26/35kv Three Core Mv XLPE Insulated Black Jacket Copper/Cu Power Cable
Popular zzhongdacable Products
4*25 ABC Aluminum Cable Insulated Overhead Cable Service Cable
Fire Resistant Copper Core PVC Insualted Flexible Electric Wire
0.6/1kv Axmk 4X240 Axmk-PE Aluminum Conductor XLPE Insulated Power Cable
1.0mm Cilicone Single Insulated Fireproof Wire 0.15 Diameter or 0.5 0AWG-30AWG
U1000 R2V 3G1.5 3G2.5 4G1.5 4G2.5 5g1.5 5g2.5mm2 Cable
Tags: Aluminum Conductor XLPE Insulated and Hffr Sheath Na2xh Power Cable, Na2xh Cable, Power Cable, zzhongdacable