Fuse Link
Fuse Link image
Get Latest Price Request a quote
Basic Info.
Packaging & Delivery
Product Description
kV to 38 kV grounded systems with 100 or 200 A nominal currents.
Especially designed to protect transformers, capacitors, cables or lines.
It is robust construction, made of rigorously tested material, will interrupt all faults under the
most severe conditions, maintaining mechanical and electric characteristics.
The inserts, hardware and structural bolts and nuts are made from heavy galvanized steel.
The Fuse Cutout type OEI can be applied on all three-phase system rated at or below the maximum
operational rating of the cutout.
| S/N | Description | Units | Schedule A | Schedule B | |
| 1 | Current ratings | A | 5 | ||
| 2 | Frequency | Hz | 50 | ||
| 3 | Rated Speed ratio | Type K as per IEC 60282 -2 |
|||
| 4 | Class of fuse link | Class B as per IEC 60282-2 |
|||
| 5 | Fuse element | Tin or Silver | |||
| 6 | Following Routine test results shall be provided on delivery of fuse links | Yes/No |
a) a static strength test; and | Yes | |
| b) a resistance test, with the fuse-link under strain. |
Yes |
||||
| 7 | The following tests shall be performed on one fuse-link per batch and test results provided on delivery of fuse links: |
Yes/No |
a)confirmation of the time/current characteristics; and |
Yes |
|
| b) a dynamic strength test. | Yes | ||||
| 8 | Drawing showing construction and dimensions as per figure 1 below to be provided with bid |
Yes/No | Yes | ||
| 9 | Previous type tests reports/certificate to be provided on bid. |
Yes/No |
Yes |
||
| 10 | Altitude above sea level | m | 1400 | ||
| 11 | Ambient operating | oC | -1 to 40 | ||
| Performance Characteristic | |
| Applied standard | IEEE C37.42-2009 |
| Catalog number | |
| Nominal system voltage kV | 22 |
| Rated Frequency Hz | 50 |
| Rated m aximum(design) voltage | 27 |
| Rated Continuous current A-RMS | 100 |
| Rated Interrupting current asymmetrical/symmetrical A-RMS | 12000/8000 |
| BIL 1.2×50 µs kV-peak | 125 |
| Minimum critical impulse flashover voltage(CFO)KV peak | 140 |
| Dry withstand voltage kV-RMS | 42 |
| Wet withstand voltage kV-RMS | 36 |
| Creepage distance to group Min.mm | 320 |
| Minimum creepage factor of insulator (Creepage Distance/arcing distance) | 2 |
| Performance Characteristic | |
| Applied standard | IEC60282-2 |
| Catalog number | |
| Nominal system voltage kV | 11 |
| Rated Frequency Hz | 50 |
| Rated m aximum(design) voltage | 12 |
| Rated Continuous current A-RMS | 100 |
| Rated Interrupting current asymmetrical/symmetrical A-RMS | 12000/8000 |
| BIL 1.2×50 µs kV-peak | 125 |
| Minimum critical impulse flashover voltage(CFO)KV peak | 140 |
| Dry withstand voltage kV-RMS | 42 |
| Wet withstand voltage kV-RMS | 36 |
| Creepage distance to group Min.mm | 372 |
| Minimum creepage factor of insulator (Creepage Distance/arcing distance) | N/A |
| Performance Characteristic | |
| Applied standard | IEEE C37.42-2009 |
| Catalog number | |
| Nominal system voltage kV | 33 |
| Rated Frequency Hz | 50 |
| Rated m aximum(design) voltage | 38 |
| Rated Continuous current A-RMS | 100 |
| Rated Interrupting current asymmetrical/symmetrical A-RMS | 8000/5000 |
| BIL 1.2×50 µs kV-peak | 150 |
| Minimum critical impulse flashover voltage(CFO)KV peak | 165 |
| Dry withstand voltage kV-RMS | 70 |
| Wet withstand voltage kV-RMS | 60 |
| Creepage distance to group Min.mm | 650 |
| Minimum creepage factor of insulator (Creepage Distance/arcing distance) | 2.3 |
| DIMENSION(mm) | |||||
| RATED CURRENT (A) |
A | B | C | D | L MN |
| 1 to 25 | 12.5+0.2 | 19.0+0.2 | 6.5 | 2.0 | 533,600,787 |
| 30 to 40 | 12.5+0.2 | 19.0+0.2 | 8.0 | 3.0 | 533,600,787 |
| 50 to 100 | 19.0+0.3 | not applicable | 9.0 | 5.0 | 533,600,787 |
| 140 to 200 | 19.0+0.3 | not applicable | 13.0 | 7.0 | 533,600,787 |
We are China Fuse Link manufacture and supplier,You can get more details with Email,you will get cheap price or factory price.
Get Latest Price Request a quote
Popular Fuse Link Products
13G Nitrile Gloves Polyester Grey 7-11
Polyester Glove Latex Coated, Crinkle Finish (green)
New Type of J Series Fuse Link, /Fuse Link 400A/Fuse Carrier
PVC Gloves Sandy Finish blue 30cm
Popular HRC Fuse Link Products
High Quality 415V/80A Slotted Wedge HRC High Breaking Capacity Jpu BS88 Fuse Link Jpu
New HRC Jpu Type 415V 100A Fuses Base /Cutout Fuse
Low Voltage 415V/500V Slotted Wedge HRC High Breaking Capacity Fuse BS88 82mm Jpu
Lov Voltage High Quality 415V/500V Slotted Wedge HRC High Breaking Capacity Jpu BS88 Fuse Link
No-Filling Sealed Pipe-Type Fuse
Overhead Service Pole Mounted Fuse Cut out and Carrier 415V 100A
Popular jgtrade1 Products
Fuse Cutout, Drop out Fuses 24kv 300A
Copper-Aluminum Parallel Groove Clamp Capg Clamp
Fuse Cutout, Drop out Fuses 15kv 100A
Drop-out Fuse-Link Assembly 33kv
Popular Low Voltage Fuse Products
Overhead Service Pole Mounted Fuse Cut out and Carrier 415V 100A
J Type Fuse Holder 82mm 92mm Jpu 630A 500A 400A 600V 415V Wedge J Type Fuse
Overhead Service Mv Pole Mounted Fuse Cut out and Carrier 400A
Overhead Service Pole Mounted Fuse Cut out and Carrier 100A
J Type Fuses Holder Base, J Services Cutout Fuse Box House Holder Base
High Quality 415V 80A Slotted Wedge HRC High Breaking Capacity Jpu BS88 Fuse Link
Tags: Fuse Link, HRC Fuse Link, jgtrade1, Low Voltage Fuse