Quick Details
Product Details
kV to 38 kV grounded systems with 100 or 200 A nominal currents.
Especially designed to protect transformers, capacitors, cables or lines.
It is robust construction, made of rigorously tested material, will interrupt all faults under the
most severe conditions, maintaining mechanical and electric characteristics.
The inserts, hardware and structural bolts and nuts are made from heavy galvanized steel.
The Fuse Cutout type OEI can be applied on all three-phase system rated at or below the maximum
operational rating of the cutout.
| S/N | Description | Units | Schedule A | Schedule B | |
| 1 | Current ratings | A | 5 | ||
| 2 | Frequency | Hz | 50 | ||
| 3 | Rated Speed ratio | Type K as per IEC 60282 -2 |
|||
| 4 | Class of fuse link | Class B as per IEC 60282-2 |
|||
| 5 | Fuse element | Tin or Silver | |||
| 6 | Following Routine test results shall be provided on delivery of fuse links | Yes/No |
a) a static strength test; and | Yes | |
| b) a resistance test, with the fuse-link under strain. |
Yes |
||||
| 7 | The following tests shall be performed on one fuse-link per batch and test results provided on delivery of fuse links: |
Yes/No |
a)confirmation of the time/current characteristics; and |
Yes |
|
| b) a dynamic strength test. | Yes | ||||
| 8 | Drawing showing construction and dimensions as per figure 1 below to be provided with bid |
Yes/No | Yes | ||
| 9 | Previous type tests reports/certificate to be provided on bid. |
Yes/No |
Yes |
||
| 10 | Altitude above sea level | m | 1400 | ||
| 11 | Ambient operating | oC | -1 to 40 | ||
| Performance Characteristic | |
| Applied standard | IEEE C37.42-2009 |
| Catalog number | |
| Nominal system voltage kV | 22 |
| Rated Frequency Hz | 50 |
| Rated m aximum(design) voltage | 27 |
| Rated Continuous current A-RMS | 100 |
| Rated Interrupting current asymmetrical/symmetrical A-RMS | 12000/8000 |
| BIL 1.2×50 µs kV-peak | 125 |
| Minimum critical impulse flashover voltage(CFO)KV peak | 140 |
| Dry withstand voltage kV-RMS | 42 |
| Wet withstand voltage kV-RMS | 36 |
| Creepage distance to group Min.mm | 320 |
| Minimum creepage factor of insulator (Creepage Distance/arcing distance) | 2 |
| Performance Characteristic | |
| Applied standard | IEC60282-2 |
| Catalog number | |
| Nominal system voltage kV | 11 |
| Rated Frequency Hz | 50 |
| Rated m aximum(design) voltage | 12 |
| Rated Continuous current A-RMS | 100 |
| Rated Interrupting current asymmetrical/symmetrical A-RMS | 12000/8000 |
| BIL 1.2×50 µs kV-peak | 125 |
| Minimum critical impulse flashover voltage(CFO)KV peak | 140 |
| Dry withstand voltage kV-RMS | 42 |
| Wet withstand voltage kV-RMS | 36 |
| Creepage distance to group Min.mm | 372 |
| Minimum creepage factor of insulator (Creepage Distance/arcing distance) | N/A |
| Performance Characteristic | |
| Applied standard | IEEE C37.42-2009 |
| Catalog number | |
| Nominal system voltage kV | 33 |
| Rated Frequency Hz | 50 |
| Rated m aximum(design) voltage | 38 |
| Rated Continuous current A-RMS | 100 |
| Rated Interrupting current asymmetrical/symmetrical A-RMS | 8000/5000 |
| BIL 1.2×50 µs kV-peak | 150 |
| Minimum critical impulse flashover voltage(CFO)KV peak | 165 |
| Dry withstand voltage kV-RMS | 70 |
| Wet withstand voltage kV-RMS | 60 |
| Creepage distance to group Min.mm | 650 |
| Minimum creepage factor of insulator (Creepage Distance/arcing distance) | 2.3 |
| DIMENSION(mm) | |||||
| RATED CURRENT (A) |
A | B | C | D | L MN |
| 1 to 25 | 12.5+0.2 | 19.0+0.2 | 6.5 | 2.0 | 533,600,787 |
| 30 to 40 | 12.5+0.2 | 19.0+0.2 | 8.0 | 3.0 | 533,600,787 |
| 50 to 100 | 19.0+0.3 | not applicable | 9.0 | 5.0 | 533,600,787 |
| 140 to 200 | 19.0+0.3 | not applicable | 13.0 | 7.0 | 533,600,787 |
We are China Overhead Service Pole Mounted Fuse Cut out and Carrier 100A manufacture and supplier,You can get more details with Email,you will get cheap price or factory price.
Get Latest Price Request a quote
Popular 82mm 92mm Products
J Type Fuse Holder 82mm 92mm Jpu 630A 500A 400A 600V 415V Wedge J Type Fuse
Fuseholder 100 AMPS, 15kv, 110kv, Bil, Chance Cat
Overhead Service LV Pole Mounted Fuse Cut out and Carrier 415V
High Quality 415V 80A Slotted Wedge HRC High Breaking Capacity Jpu BS88 Fuse Link
J Type Fuses Holder Base, J Services Cutout Fuse Box House Holder Base
Overhead Service Pole Mounted Fuse Cut out and Carrier 415V 100A
Popular HRC Fuse Link Products
High Quality 415V/80A Slotted Wedge HRC High Breaking Capacity Jpu BS88 Fuse Link Jpu
Overhead Service LV Pole Mounted Fuse Cut out and Carrier 415V
J Type Fuse Holder 82mm 92mm Jpu 630A 500A 400A 600V 415V Wedge J Type Fuse
Overhead Service Mv Pole Mounted Fuse Cut out and Carrier 400A
Overhead Service Pole Mounted Fuse Cut out and Carrier 415V 100A
Popular jgtrade1 Products
46kv Polymer Strain Insulators
High Quality 415V/500V Slotted Wedge HRC High Breaking Capacity Jpu BS88
Fuse Cutout, Drop out Fuses 36kv 200A
72.5kv 110kv 126kv 132kv 145kv Gw4 Outdoor High Voltage Disconnector
Popular Low Voltage Fuse Products
J Type Fuses Holder Base, J Services Cutout Fuse Box House Holder Base
New HRC Jpu Type 415V 100A Fuses Base /Cutout Fuse
Fuseholder 100 AMPS, 15kv, 110kv, Bil, Chance Cat
High Quality 415V 80A Slotted Wedge HRC High Breaking Capacity Jpu BS88 Fuse Link
Overhead Service Pole Mounted Fuse Cut out and Carrier 415V 100A
Tags: 82mm 92mm, HRC Fuse Link, jgtrade1, Low Voltage Fuse