AAAC AS 1531 Aluminium Alloy 6201 Ruby
AAAC AS 1531 Aluminium Alloy 6201 Ruby image
Get Latest Price Request a quote
Quick Details
Product Details
AAAC (All Aluminum Alloy Conductor) referred to have higher strength but lower conductivity than pure aluminum. Being lighter, alloy conductors can sometimes be used to advantage in place of the more conventional ACSR;
Having lower breaking loads than the latter, their use becomes particularly favourable when ice and win loadings are low.
We can supply this conductor according to different recognized standards, such as BS EN50182, IEC61089, ASTM B399DIN 48, customer special specification also can be satisfied.
2. Applications:
Used as bare overhead conductor for primary and secondary distribution. Designed utilizing a high-strength aluminum-alloy to achieve a high strength-to-weight ratio; affords good sag characteristics. Aluminum-alloy gives 6201-T81 gives AAAC higher resistance to corrosion than ACSR.
3. Standards&Specifications:
All Aluminium Alloy Conductor-AAAC (DIN 48201 Standard Sizes)
| Nominal Area | Conductor Construction | Calculated Area | Overall Diameter | Weight | DC Resistance at 20 |
| mm2 | No./mm | mm2 | mm | kg/km | Ω/km |
| 16 | 7/1.70 | 15.9 | 5.1 | 43.5 | 2.091 |
| 25 | 7/2.10 | 24.2 | 6.3 | 66.4 | 1.370 |
| 35 | 7/2.50 | 34.4 | 7.5 | 94.1 | 0.9669 |
| 50 | 7/3.00 | 49.5 | 9.0 | 135 | 0.6714 |
| 50 | 19/1.80 | 48.3 | 9.0 | 133 | 0.6905 |
| 70 | 19/2.10 | 65.8 | 10.5 | 181 | 0.5073 |
| 95 | 19/2.50 | 93.3 | 12.5 | 257 | 0.358 |
| 120 | 19/2.80 | 117 | 14 | 322 | 0.2854 |
| 150 | 37/2.25 | 147 | 15.7 | 406 | 0.2274 |
| 185 | 37/2.50 | 182 | 17.5 | 501 | 0.1842 |
| 240 | 61/2.25 | 243 | 20.2 | 671 | 0.1383 |
| 300 | 61/2.50 | 299 | 22.5 | 828 | 0.1120 |
| 400 | 61/2.89 | 400 | 26.0 | 1,106 | 0.0838 |
| 500 | 61/3.23 | 500 | 29.1 | 1382 | 0.06709 |
| 625 | 91/2.96 | 626 | 32.6 | 1,735 | 0.05367 |
| 800 | 91/3.35 | 802 | 36.9 | 2,222 | 0.0419 |
| 1000 | 91/3.74 | 1,000 | 41.1 | 2,770 | 0.03362 |
| ALUMINIUM ALLOY CONDUCTOR ASTM B399 | |||||||||
| Code Name | Area | Size&Stranding of ACSR with equal diameter | No. and diameter | Overall diameter | Weight | Nominal breaking load | MAX .DC resistance at 20ºC | ||
| Nominal | Actual | AWG or MCM | Al/St | ||||||
| MCM | mm2 | mm | mm | kg/km | kN | ohm/km | |||
| AKRON | 30.58 | 15.48 | 6 | 6/1 | 7/1.68 | 5.04 | 42.7 | 4.92 | 0.3966 |
| ALTON | 48.69 | 24.71 | 4 | 6/1 | 7/2.12 | 6.35 | 68 | 7.84 | 0.3811 |
| AMES | 77.47 | 39.22 | 2 | 6/1 | 7/2.67 | 8.02 | 108 | 12.45 | 0.3671 |
| AZUSA | 123.3 | 62.38 | 1/0 | 6/1 | 7/3.37 | 10.11 | 172 | 18.97 | 0.3524 |
| ANAHEIM | 155.4 | 78.65 | 2/0 | 6/1 | 7/3.78 | 11.35 | 217 | 23.93 | 0.3448 |
| AMHERST | 195.7 | 99.22 | 3/0 | 6/1 | 7/4.25 | 12.75 | 273 | 30.18 | 0.3375 |
| ALLIANCE | 246.9 | 125.1 | 4/0 | 6/1 | 7/4.77 | 14.31 | 345 | 38.05 | 0.3306 |
| BUTTE | 312.8 | 158.6 | 266.8 | 26/7 | 19/3.26 | 16.3 | 437 | 48.76 | 0.3196 |
| CANTON | 394.5 | 199.9 | 366.4 | 26/7 | 19/3.66 | 18.3 | 551 | 58.91 | 0.3124 |
| CAIRO | 465.4 | 235.8 | 397.5 | 26/7 | 19/3.98 | 19.88 | 650 | 69.48 | 0.3071 |
| DARIEN | 559.5 | 283.5 | 477 | 26/7 | 19/4.36 | 21.79 | 781 | 83.52 | 0.3014 |
| ELGIN | 652.4 | 330.6 | 556.5 | 26/7 | 19/4.71 | 23.54 | 911 | 97.42 | 0.2966 |
| FLINT | 740.8 | 375.3 | 636 | 26/7 | 37/3.59 | 25.16 | 1035 | 108.21 | 0.2917 |
| GREELY | 927.2 | 469.8 | 795 | 26/7 | 37/4.02 | 28.14 | 1295 | 135.47 | 0.2846 |
| Area | Stranding and wire diameter | Approx. overall diameter | Weight | Nominal Breaking Load | MAX .DC resistance at 20ºC | |
| Nominal | Actual | |||||
| AWGorMCM | (mm2) | (mm) | (mm) | (kg/km) | (kN) | (ohm/km) |
| 6 | 13.30 | 7/1.554 | 4.67 | 37 | 4.22 | 2.5199 |
| 4 | 21.15 | 1/1.961 | 5.89 | 58 | 6.71 | 1.5824 |
| 2 | 33.63 | 7/2.474 | 7.42 | 93 | 10.68 | 0.9942 |
| 1/0 | 53.48 | 7/3.119 | 9.36 | 148 | 16.97 | 0.6256 |
| 2/0 | 67.42 | 7/3.503 | 10.51 | 186 | 20.52 | 0.4959 |
| 3/0 | 85.03 | 7/3.932 | 11.8 | 234 | 25.86 | 0.3936 |
| 4/0 | 107.23 | 7/4.417 | 13.26 | 296 | 32.63 | 0.3119 |
| 250 | 126.66 | 19/2.913 | 14.57 | 349 | 38.93 | 0.2642 |
| 300 | 152.1 | 19/3.193 | 15.97 | 419 | 46.77 | 0.2199 |
| 350 | 177.35 | 19/3.447 | 17.24 | 489 | 52.25 | 0.1887 |
| 400 | 202.71 | 19/3.686 | 18.43 | 559 | 59.74 | 0.1650 |
| 450 | 228 | 19/3.909 | 19.55 | 629 | 67.19 | 0.1467 |
| 500 | 253.35 | 19/4.120 | 20.60 | 698 | 74.64 | 0.1321 |
| 550 | 278.60 | 37/3.096 | 21.67 | 768 | 83.80 | 0.1202 |
| 600 | 303.80 | 37/3.233 | 22.63 | 838 | 91.38 | 0.1102 |
| 650 | 329.25 | 37/3.366 | 23.56 | 908 | 97.94 | 0.1016 |
| 700 | 354.55 | 37/3.493 | 24.45 | 978 | 102.20 | 0.0944 |
| 750 | 380.20 | 37/3.617 | 25.32 | 1049 | 109.60 | 0.0880 |
| 800 | 405.15 | 37/3.734 | 26.14 | 1117 | 116.80 | 0.0826 |
| 900 | 456.16 | 37/3.962 | 27.73 | 1258 | 131.50 | 0.0733 |
| 1000 | 506.71 | 37/4.176 | 29.23 | 1399 | 146.10 | 0.0660 |
| 1100 | 557 | 61/3.41 | 30.69 | 1537 | 162.16 | 0.0589 |
| 1200 | 608 | 61/3.56 | 32.04 | 1677 | 176.75 | 0.0541 |
| 1300 | 659 | 61/3.71 | 33.39 | 1816 | 191.95 | 0.0498 |
| 1400 | 709 | 61/3.85 | 34.65 | 1955 | 206.72 | 0.0463 |
| 1500 | 760 | 61/3.98 | 35.82 | 2095 | 220.90 | 0.0441 |
| 1600 | 811 | 61/4.12 | 37.08 | 2236 | 235.57 | 0.0405 |
| 1700 | 861 | 61/4.24 | 38.16 | 2374 | 250.72 | 0.0382 |
| 1800 | 912 | 61/4.36 | 39.28 | 2514 | 265.11 | 0.03693 |
| 1900 | 963 | 91/3.67 | 40.37 | 2655 | 277.10 | 0.03411 |
| 2000 | 1013 | 91/3.76 | 41.4 | 2793 | 292.41 | 0.03243 |
| ALUMINIUM ALLOY CONDUCTOR BSEN50183 | |||||||
| Code Name | Calculated Area | No. Of Wires | Diameter | Weight | Rated Strength | MAX .DC resistance at 20ºC | |
| Wire | Cond. | ||||||
| mm2 | mm | mm | kg/km | Kn | ohm/km | ||
| Box | 18.8 | 7 | 1.85 | 5.55 | 51.4 | 5.55 | 1.748 |
| Acacia | 23.8 | 7 | 2.08 | 6.24 | 64.9 | 7.02 | 1.3828 |
| Almond | 30.1 | 7 | 2.34 | 7.02 | 82.2 | 8.88 | 1.0926 |
| Cedar | 35.5 | 7 | 2.54 | 7.62 | 96.8 | 10.46 | 0.9273 |
| Deodar | 42.2 | 7 | 2.77 | 8.31 | 115.2 | 12.44 | 0.7797 |
| Fir | 47.8 | 7 | 2.95 | 8.85 | 130.6 | 14.11 | 0.6875 |
| Hazel | 59.9 | 7 | 3.3 | 9.9 | 163.4 | 17.66 | 0.5494 |
| Pine | 71.6 | 7 | 3.61 | 10.8 | 195.6 | 21.14 | 0.4591 |
| Holly | 84.1 | 7 | 3.91 | 11.7 | 229.5 | 24.79 | 0.3913 |
| Willow | 89.7 | 7 | 4.04 | 12.1 | 245 | 26.47 | 0.3665 |
| Oak | 118.9 | 7 | 4.65 | 14 | 324.5 | 35.07 | 0.2767 |
| Mulberry | 150.9 | 19 | 3.18 | 15.9 | 414.3 | 44.52 | 0.2192 |
| Ash | 180.7 | 19 | 3.48 | 17.4 | 496.1 | 53.31 | 0.183 |
| Elm | 211 | 19 | 3.76 | 18.8 | 579.2 | 62.24 | 0.1568 |
| Poplar | 239.4 | 37 | 2.87 | 20.1 | 659.4 | 70.61 | 0.1387 |
| Sycamore | 303.2 | 37 | 3.23 | 22.6 | 835.2 | 89.4 | 0.1095 |
| Upas | 362.1 | 37 | 3.53 | 24.7 | 997.5 | 106.82 | 0.0917 |
| Yew | 479 | 37 | 4.06 | 28.4 | 1319.6 | 141.31 | 0.0693 |
| Totara | 498.1 | 37 | 4.14 | 29 | 1372.1 | 146.93 | 0.0666 |
| Rubus | 586.9 | 61 | 3.5 | 31.5 | 1622 | 173.13 | 0.0567 |
| Sorbus | 659.4 | 61 | 3.71 | 33.4 | 1822.5 | 194.53 | 0.0505 |
| Araucaria | 821.1 | 61 | 4.14 | 37.3 | 2269.4 | 242.24 | 0.0406 |
| Redwood | 996.2 | 61 | 4.56 | 41 | 2753.2 | 293.88 | 0.0334 |
| ALUMINIUM ALLOY CONDUCTOR BS 3242 | |||||||
| Code Name | Calculated Area | No. Of Wires | Diameter | Weight | Rated Strength | MAX .DC resistance at 20ºC | |
| Wire | Cond. | ||||||
| mm2 | mm | mm | kg/km | Kn | ohm/km | ||
| Box | 15 | 7/1.85 | 18.82 | 5.55 | 51 | 537 | 1.7495 |
| Acacia | 20 | 7/2.08 | 23.79 | 6.24 | 65 | 680 | 1.384 |
| Almond | 25 | 7/2.34 | 30.1 | 7.02 | 82 | 861 | 1.0934 |
| Cedar | 30 | 7/2.54 | 35.47 | 7.62 | 97 | 1014 | 0.9281 |
| – | 35 | 7/2.77 | 42.18 | 8.31 | 115 | 1205 | 0.7804 |
| Fir | 40 | 7/2.95 | 47.87 | 8.85 | 131 | 1367 | 0.688 |
| Hazel | 50 | 7/3.30 | 59.87 | 9.9 | 164 | 1711 | 0.5498 |
| Pine | 60 | 7/3.61 | 71.65 | 10.83 | 196 | 2048 | 0.4594 |
| – | 70 | 7/3.91 | 84.05 | 11.73 | 230 | 2402 | 0.3917 |
| Willow | 75 | 7/4.04 | 89.73 | 12.12 | 245 | 2565 | 0.3669 |
| – | 80 | 7/4.19 | 96.52 | 12.57 | 264 | 2758 | 0.3441 |
| – | 90 | 7/4.44 | 108 | 13.32 | 298 | 3112 | 0.3023 |
| Oak | 100 | 7/4.65 | 118.9 | 13.95 | 325 | 3398 | 0.2769 |
| – | 100 | 19/2.82 | 118.7 | 14.1 | 326 | 3393 | 0.2787 |
| Mulbery | 125 | 19/3.18 | 150.9 | 15.9 | 415 | 4312 | 0.2192 |
| Ash | 150 | 19/3.48 | 180.7 | 17.4 | 497 | 5164 | 0.1831 |
| Elm | 175 | 19/3.76 | 211 | 18.8 | 580 | 6030 | 0.1568 |
| Poplar | 200 | 37/2.87 | 239.4 | 20.09 | 659 | 8841 | 0.1385 |
| – | 225 | 37/3.05 | 270.3 | 21.35 | 744 | 7724 | 0.1227 |
| Sycamore | 250 | 37/3.22 | 303.2 | 22.54 | 835 | 8664 | 0.1093 |
| Upas | 300 | 37/3.53 | 362.1 | 24.71 | 997 | 10350 | 0.09156 |
| Walnut | 350 | 37/3.81 | 421.8 | 26.67 | 1162 | 12053 | 0.0786 |
| Yew | 400 | 37/4.06 | 479 | 28.42 | 1319 | 13685 | 0.06921 |
| Totara | 425 | 37/4.14 | 498.1 | 28.98 | 1372 | 14233 | 0.06656 |
| Rubus | 500 | 61/3.50 | 586.9 | 31.5 | 1620 | 16771 | 0.05662 |
| Araucaria | 700 | 61/4.14 | 821.1 | 37.26 | 2266 | 23450 | 0.04047 |
4.FAQ
(1).When can I get the price?
We usually quote within 6 hours after we get your inquiry. If you are very urgent to get the price, please
call us or tell us in your e-mail so that we will regard your inquiry priority.
(2).How can I get a sample to check your quality?
After price confirmation, you can require for samples to check our quality. Sample is free, but the freight
charge should be paid.
(3).How long can I expect to get the sample?
After you pay the freight charge and send us confirmed files, the samples will be ready for delivery in 3-7
days. The samples will be sent to you via express and arrive in 3~5 days. You can use your own express account orprepay us if you do not have an account.
(4).What about the lead time for mass production?
Honestly, it depends on the order quantity and the season you place the order.The best record we keep is
delivering 10 kilometers cable within a week. Generally speaking, we suggest that you start inquiry two months
before the date you would like to get the products at your country.
We are China AAAC AS 1531 Aluminium Alloy 6201 Ruby manufacture and supplier,You can get more details with Email,you will get cheap price or factory price.
Get Latest Price Request a quote
Popular AAAC Conductor Products
Competitive Price of High Grade Aluminium Conductor Alloy Reinforced Acar
AAC AAAC ACSR Aacsr Acar Steel Wire Overhead Bare Conductor
Light Weight High Strength Electric Transmission Lines AAAC
AAAC Conductor 50mm2 Aluminum Cable Price
Bare Conductors AAAC (All Aluminium alloy conductor) Power Conductors
Manufacture High Quality AAAC Conductor with ASTM B399 Standard
Popular Aluminum Alloy 6201-T81 Conductor Products
AAAC as 1531 Aluminium Alloy 6201 Emerald
Overhead ACSR, AAC, AAAC, Acss/Tw, Accc, Aacsr, Acar, Opgw Bare Conductor
AAAC Conductor ASTM B399 Bare Aluminium Alloy 6201-T81 350mcm
AAAC Conductor ASTM B399 Bare Aluminium Alloy 6201-T81 Canton
AAAC Conductor ASTM B399 Bare Aluminium Alloy 6201-T81 1/0AWG
AAAC as 1531 Aluminium Alloy 6201 Opal
Popular Aluminum Alloy Conductor AAAC Products
AAAC Conductor ASTM B399 Bare Aluminium Alloy 6201-T81 Cairo
AAAC as 1531 Aluminium Alloy 6201 Diamond
AAAC Conductor ASTM B399 Bare Aluminium Alloy 6201-T81 Greeley
AAAC Conductor ASTM B399 Bare Aluminium Alloy 6201-T81 Canton
AAAC Conductor ASTM B399 Bare Aluminium Alloy 6201-T81 2AWG
AAAC Conductor ASTM B399 Bare Aluminium Alloy 6201-T81 350mcm
Popular huatongcable Products
IEC60502-2 Copper XLPE Insualted 18/30kv 3X35mm2 Armored Underground Cable
Electrical Twisted ABC Cable, Low Voltage Twisted Cable
LV Conductor, 600V Urd Aluminum Cable, Overhead Line Cable
XLPE Insulated Triplex Service Drop Aluminum Conductor Cable ABC
6.35/11kv 12/20kv 18/30kv Armored Cable
Overhead Triplex Service Drop Lobster Aerial Bundled Cable for Transmission Line
Tags: AAAC Conductor, Aluminum Alloy 6201-T81 Conductor, Aluminum Alloy Conductor AAAC, huatongcable