AAC Conductor, ACSR Conductor, AAAC Conductor
AAC Conductor, ACSR Conductor, AAAC Conductor image
Get Latest Price Request a quote
Quick Details
Product Details
AAC Conductor, ACSR Conductor, AAAC Conductor
1.Applications
Conductor(AAC,AAAC and ACSR) have been widely used in power transmission lines with various voltage levels,because they have such good characteristics as simple structure,convenient installation and maintenance,low cost large transmission capacity.And they are also suitable for laying across rivers valleys and the places where special geographical features exist.
2.Service Performance
(1).The permissible long-time operating temperature for aerial conductor is 70oC.
(2).Under the circumstance that rare climate is occuring and ice coverage rate low in heavy ice area,the biggest stress of cable at the lowest point of the sag should not exceed 60% of the short-time destructive power.
(3).When connecting conductors,the conductor beside the connecting tube cant be prominent.Otherwise,the force on the operating conductors will be unbalanced.After connectors are install,the connecting tube should be painted by moisture-proof varnish in order to protect it from corrosion.
(4).Under installaion,the arc downing stress of all the conductors should be the same.With in the permissible distance of crossing buildings or dropping to the ground,the stress can be 10-15% higher than regular stress.
3.Material Standard
(1).The hard aluminum conductor used for AAC and ACSR conforms to the standard GB/T 17048-1997(equivalent to IEC 60889:1987).
(2).The zinc coated steel wire used for ACSR conforms to IEC 60888:1987.
(3).Production can be arranged according to customers requirements for material standard,etc.
Construction of All Aluminum Conductor and Aluminum Conductor Steel Reinforced
4.Technical details
AAC Technical Characteristics Based on Standard DIN 48201 / DIN EN50182
Code number | Area | Number of wires | Wire diameter | Conductor diameter | Linear mass | Rated strength | D.C. resistance at 20oC |
mm2 | No. | mm | mm | kg/km | kN | Ω/km | |
16 | 15.9 | 7 | 1.7 | 5.1 | 43.4 | 3.02 | 1.7986 |
25 | 24.2 | 7 | 2.1 | 6.3 | 66.3 | 4.36 | 1.1787 |
35 | 34.4 | 7 | 2.5 | 7.5 | 93.9 | 6.01 | 0.8317 |
50 | 49.5 | 7 | 3 | 9 | 135.2 | 8.41 | 0.5776 |
50 | 48.3 | 19 | 1.8 | 9 | 132.9 | 8.94 | 0.5944 |
70 | 65.8 | 19 | 2.1 | 10.5 | 180.9 | 11.85 | 0.4367 |
95 | 93.3 | 19 | 2.5 | 12.5 | 256.3 | 16.32 | 0.3081 |
120 | 117 | 19 | 2.8 | 14 | 321.5 | 19.89 | 0.2456 |
150 | 147.1 | 37 | 2.25 | 15.8 | 405.7 | 26.48 | 0.196 |
185 | 181.6 | 37 | 2.5 | 17.5 | 500.9 | 31.78 | 0.1588 |
240 | 242.5 | 61 | 2.25 | 20.3 | 671.1 | 43.66 | 0.1193 |
300 | 299.4 | 61 | 2.5 | 22.5 | 828.5 | 52.4 | 0.0966 |
ACSR Technical Characteristics Based on Standard BS 215-2
Code name | Nominal aluminium area | Stranding and wire diameter | Sectional area of aluminium | Total sectional area | Approx. overall diameter | Approx. mass | Calculated D.C. resistance at 20oC | Calculated breaking load | |
Al | Steel | ||||||||
mm2 | No./mm | mm2 | mm2 | mm | kg/km | Ω/km | kN | ||
RABBIT | 50 | 6/3.35 | 1/3.35 | 52.88 | 61.7 | 10.05 | 214 | 0.5426 | 18.35 |
DOG | 100 | 6/4.72 | 7/1.57 | 105 | 118.5 | 14.15 | 394 | 0.2733 | 32.7 |
WOLF | 150 | 30/2.59 | 7/2.59 | 158.1 | 194.9 | 18.13 | 726 | 0.1828 | 69.2 |
DINGO | 150 | 18/3.35 | 1/3.35 | 158.7 | 167.5 | 16.75 | 506 | 0.1815 | 35.7 |
LYNX | 175 | 30/2.79 | 7/2.79 | 183.4 | 226.2 | 19.53 | 842 | 0.1576 | 79.8 |
ZEBRA | 400 | 54/3.18 | 7/3.18 | 428.9 | 484.5 | 28.62 | 1621 | 0.0674 | 131.9 |
AAAC Technical Characteristics Based on Standard BS 3242
Code name | Nominal aluminium area | Stranding and wire diameter | Sectional area | Approx. overall diameter | Approx. mass | Calculated D.C. resistance at 20oC | Calculated breaking load |
mm2 | No./mm | mm2 | mm | kg/km | Ω/km | kN | |
ALMOND | 25 | 7/2.34 | 30.1 | 7.02 | 82 | 1.094 | 8.44 |
CEDAR | 30 | 7/2.54 | 35.47 | 7.62 | 97 | 0.9281 | 9.94 |
FIR | 40 | 7/2.95 | 47.84 | 8.85 | 131 | 0.688 | 13.4 |
HAZEL | 50 | 7/3.30 | 59.87 | 9.9 | 164 | 0.5498 | 16.8 |
OAK | 100 | 7/4.65 | 118.9 | 13.95 | 325 | 0.2769 | 33.3 |
ASH | 150 | 19/3.48 | 180.7 | 17.4 | 497 | 0.183 | 50.65 |
ELM | 175 | 19/3.76 | 211 | 18.8 | 580 | 0.1568 | 59.1 |
UPAS | 300 | 37/3.53 | 362.1 | 24.71 | 997 | 0.09155 | 101.5 |
Company Information
We are China AAC Conductor, ACSR Conductor, AAAC Conductor manufacture and supplier,You can get more details with Email,you will get cheap price or factory price.
Get Latest Price Request a quote
Popular AAC Conductor Products
2017 Hot Sale Overhead Bare Aluminum AAC AAAC Conductor
0.6/1 Kv 33kv 50mm2 120mm2 All Aluminum Conductor AAC Cable
ASTM Standard Peachbell 6AWG AAC Bare Conductor
AAC Conductor All Aluminium Conductor Power Cable
Aluminum Bare Conductor AAC Wasp
None Jacket Overhead Cable All Aluminum AAC Conductor
Popular Aluminum Conductor Products
Aluminum Conductor Steel Reinforced DIN48204
ACSR Bare Conductor ACSR for Transmission Line Use
ACSR Conductor with ASTM Standard 1200mcm
Aaaac Aluminum Conductor Overhead Cable
Aluminum Conductor AAC Conductor 1/0AWG ASTM Standard
0.6/1kv Aluminum Conductor Overhead ABC Cable
Popular Aluminum Wire Products
Multi Core ABC Service Drop Aerial Bundled Cable ABC Overhead Cable
Copper Clad Aluminum Wire and Aluminium Cable
Aluminum Wire/Single Core Aluminum Electric Wire
Flexible Solid Stranded Copper Aluminium PVC Insulated Electric Cable Wires
Bare Aluminum AAC Carnation Conductor
450/750V PVC Insulated Electric Wire for Aluminum Conductor
Popular zzjinshui Products
Duplex Triplex Quadruplex ABC Cable Aerial Bundled Cable
Bare Condcutor for High Voltage Cable
Screened Rubber Sheathed Movable & Flexible Mine Cables
Ser/Seu Concentric Cable /Service Entrance Cable Flat 8+8AWG
Factory Low Price Yjlv Aluminum Core XLPE Insulated Power Cable
Low Voltage XLPE Insulated Aluminium Cable
Tags: AAC Conductor, Aluminum Conductor, Aluminum Wire, zzjinshui