AAC Conductor, ACSR Conductor, AAAC Conductor
AAC Conductor, ACSR Conductor, AAAC Conductor image
Get Latest Price Request a quote
Quick Details
Product Details
AAC Conductor, ACSR Conductor, AAAC Conductor
1.Applications
Conductor(AAC,AAAC and ACSR) have been widely used in power transmission lines with various voltage levels,because they have such good characteristics as simple structure,convenient installation and maintenance,low cost large transmission capacity.And they are also suitable for laying across rivers valleys and the places where special geographical features exist.
2.Service Performance
(1).The permissible long-time operating temperature for aerial conductor is 70oC.
(2).Under the circumstance that rare climate is occuring and ice coverage rate low in heavy ice area,the biggest stress of cable at the lowest point of the sag should not exceed 60% of the short-time destructive power.
(3).When connecting conductors,the conductor beside the connecting tube cant be prominent.Otherwise,the force on the operating conductors will be unbalanced.After connectors are install,the connecting tube should be painted by moisture-proof varnish in order to protect it from corrosion.
(4).Under installaion,the arc downing stress of all the conductors should be the same.With in the permissible distance of crossing buildings or dropping to the ground,the stress can be 10-15% higher than regular stress.
3.Material Standard
(1).The hard aluminum conductor used for AAC and ACSR conforms to the standard GB/T 17048-1997(equivalent to IEC 60889:1987).
(2).The zinc coated steel wire used for ACSR conforms to IEC 60888:1987.
(3).Production can be arranged according to customers requirements for material standard,etc.
Construction of All Aluminum Conductor and Aluminum Conductor Steel Reinforced
4.Technical details
AAC Technical Characteristics Based on Standard DIN 48201 / DIN EN50182
| Code number | Area | Number of wires | Wire diameter | Conductor diameter | Linear mass | Rated strength | D.C. resistance at 20oC |
| mm2 | No. | mm | mm | kg/km | kN | Ω/km | |
| 16 | 15.9 | 7 | 1.7 | 5.1 | 43.4 | 3.02 | 1.7986 |
| 25 | 24.2 | 7 | 2.1 | 6.3 | 66.3 | 4.36 | 1.1787 |
| 35 | 34.4 | 7 | 2.5 | 7.5 | 93.9 | 6.01 | 0.8317 |
| 50 | 49.5 | 7 | 3 | 9 | 135.2 | 8.41 | 0.5776 |
| 50 | 48.3 | 19 | 1.8 | 9 | 132.9 | 8.94 | 0.5944 |
| 70 | 65.8 | 19 | 2.1 | 10.5 | 180.9 | 11.85 | 0.4367 |
| 95 | 93.3 | 19 | 2.5 | 12.5 | 256.3 | 16.32 | 0.3081 |
| 120 | 117 | 19 | 2.8 | 14 | 321.5 | 19.89 | 0.2456 |
| 150 | 147.1 | 37 | 2.25 | 15.8 | 405.7 | 26.48 | 0.196 |
| 185 | 181.6 | 37 | 2.5 | 17.5 | 500.9 | 31.78 | 0.1588 |
| 240 | 242.5 | 61 | 2.25 | 20.3 | 671.1 | 43.66 | 0.1193 |
| 300 | 299.4 | 61 | 2.5 | 22.5 | 828.5 | 52.4 | 0.0966 |
ACSR Technical Characteristics Based on Standard BS 215-2
| Code name | Nominal aluminium area | Stranding and wire diameter | Sectional area of aluminium | Total sectional area | Approx. overall diameter | Approx. mass | Calculated D.C. resistance at 20oC | Calculated breaking load | |
| Al | Steel | ||||||||
| mm2 | No./mm | mm2 | mm2 | mm | kg/km | Ω/km | kN | ||
| RABBIT | 50 | 6/3.35 | 1/3.35 | 52.88 | 61.7 | 10.05 | 214 | 0.5426 | 18.35 |
| DOG | 100 | 6/4.72 | 7/1.57 | 105 | 118.5 | 14.15 | 394 | 0.2733 | 32.7 |
| WOLF | 150 | 30/2.59 | 7/2.59 | 158.1 | 194.9 | 18.13 | 726 | 0.1828 | 69.2 |
| DINGO | 150 | 18/3.35 | 1/3.35 | 158.7 | 167.5 | 16.75 | 506 | 0.1815 | 35.7 |
| LYNX | 175 | 30/2.79 | 7/2.79 | 183.4 | 226.2 | 19.53 | 842 | 0.1576 | 79.8 |
| ZEBRA | 400 | 54/3.18 | 7/3.18 | 428.9 | 484.5 | 28.62 | 1621 | 0.0674 | 131.9 |
AAAC Technical Characteristics Based on Standard BS 3242
| Code name | Nominal aluminium area | Stranding and wire diameter | Sectional area | Approx. overall diameter | Approx. mass | Calculated D.C. resistance at 20oC | Calculated breaking load |
| mm2 | No./mm | mm2 | mm | kg/km | Ω/km | kN | |
| ALMOND | 25 | 7/2.34 | 30.1 | 7.02 | 82 | 1.094 | 8.44 |
| CEDAR | 30 | 7/2.54 | 35.47 | 7.62 | 97 | 0.9281 | 9.94 |
| FIR | 40 | 7/2.95 | 47.84 | 8.85 | 131 | 0.688 | 13.4 |
| HAZEL | 50 | 7/3.30 | 59.87 | 9.9 | 164 | 0.5498 | 16.8 |
| OAK | 100 | 7/4.65 | 118.9 | 13.95 | 325 | 0.2769 | 33.3 |
| ASH | 150 | 19/3.48 | 180.7 | 17.4 | 497 | 0.183 | 50.65 |
| ELM | 175 | 19/3.76 | 211 | 18.8 | 580 | 0.1568 | 59.1 |
| UPAS | 300 | 37/3.53 | 362.1 | 24.71 | 997 | 0.09155 | 101.5 |
Company Information
We are China AAC Conductor, ACSR Conductor, AAAC Conductor manufacture and supplier,You can get more details with Email,you will get cheap price or factory price.
Get Latest Price Request a quote
Popular AAC Conductor Products
Bare Aluminum Conductor AAC or Asc Conductor Wasp
AAC Overhead Bare Conductor 150mm2
Aluminum Conductor Material and Overhead Application High Quality ACSR Peacock Conductor
IEC, ASTM, BS Standard AAC Conductor From Factory
Turkey Bare Overhead AAAC Conductor ACSR Conductors
Popular Aluminum Conductor Products
ACSR 120/20 and Caa Conductor ACSR Aluminum Conductor Steel Reiforced
IEC Standard ACSR Bison Conductor Bare Aluminum Clad Steel Conductor
AAAC Conductor, All Aluminium Alloy Conductor (UNE 21018)
LV Cable Triplex Aluminum Insulated 1/0 AWG Abccable
ASTM B 498 Class B Coating ACSR Steel Wire
1350/1370 Aluminum Electrical Wire Cable 4mm 6mm 1.5mm 2mm
Popular Aluminum Wire Products
9.5mm 12mm 15mm 1350/1370/1A60/ Aluminum Wire Rod
0.6/1kv Al PVC Insulation Cable Aluminum Conductor Wire
Ec Grade 1370 Aluminum Wire Rod Manufacture for Electrical Purposes
Bare Aluminum AAC Carnation Conductor
Solid Conductor Tie Wire #4AWG Hard Drawn Aluminium HDAL ASTM B 233
Popular zzjinshui Products
11kv ABC Cable by Jinshui Manumfactory
Overhead Power Cable ABC Cable
Copper/PVC Insulated Electric Wires/Building Wire House Wire 1.5 2.5 4 6
Aerial Overhead Cable Insulation XLPE Compound ABC Cable
Standard Bare AAC Asc ACSR Aacsr
Tags: AAC Conductor, Aluminum Conductor, Aluminum Wire, zzjinshui