Aerial Bundle Cable ABC to Sans 1418 Size 3X70+54.6
Aerial Bundle Cable ABC to Sans 1418 Size 3X70+54.6 image
Get Latest Price Request a quote
Quick Details
Product Details
Table 01
Type of conductor or core | Norminal cross-sectional area mm2 | Nubmer of wires Min. |
Diameter of conductormm | Resistanceat 20ºC Ω/km Max. | Breaking force(N) | Thickness of insulation (mm) | Outer diameter of core(mm) | |||
Min. | Max. | Min. | Average | Min. | Min. | Max. | ||||
Phase or auxiliary or non-strain-bearing netural(aluminium) | +16 | 6 | 4.6 | 5.1 | 1.91 | 2070 | 1.2 | 0.98 | 7.0 | 7.8 |
25 | 6 | 5.8 | 6.3 | 1.2 | 3300 | 1.4 | 1.16 | 8.6 | 9.4 | |
35 | 6 | 6.8 | 7.3 | 0.868 | 4500 | 1.6 | 1.34 | 10.0 | 10.9 | |
50 | 6 | 7.9 | 8.4 | 0.641 | 6200 | 1.6 | 1.34 | 11.1 | 12.0 | |
70 | 12 | 9.7 | 10.2 | 0.443 | 8900 | 1.8 | 1.52 | 13.3 | 14.2 | |
95 | 15 | 11.0 | 12.0 | 0.320 | 12300 | 1.8 | 1.52 | 14.6 | 16.0 | |
120 | 15 | 12.5 | 13.5 | 0.253 | 15600 | 1.8 | 1.52 | 16.3 | 17.5 | |
150 | 15 | 13.9 | 15.0 | 0.206 | 19200 | 1.8 | 1.52 | 17.1 | 18.6 | |
Service connection(aluminium) | 16 | 6 | 4.6 | 5.2 | 1.91 | 2070 | 1.2 | 0.98 | 7.0 | 8.0 |
25 | 6 | 5.6 | 6.5 | 1.2 | 3300 | 1.4 | 1.16 | 8.6 | 9.6 | |
Service connection(copper) | 10 | 6 | – | 4.2 | 1.83 | 3600 | 1.2 | 0.98 | 6.2 | 7.0 |
16 | 6 | – | 5.3 | 1.15 | 5760 | 1.2 | 0.98 | 7.2 | 8.0 | |
25 | 6 | – | 6.6 | 0.727 | 8750 | 1.4 | 1.16 | 8.6 | 9.6 | |
Number and nominal diameter of wires mm |
||||||||||
Supporting core(aluminium alloy) |
54.6 | 7×3.15 | 9.2 | 9.6 | 0.630 | 16600 | 1.6 | 1.34 | 12.3 | 13.0 |
70 | 7×3.50 | 10.0 | 10.4 | 0.500 | 20100 | 1.6 | 1.34 | 12.9 | 13.6 | |
+Auxiliary conductors or cores only |
When a supporting core is specified in a tender invitation,the combinations listed in Table 02 below:
Table 02
1 | 2 |
Nominal cross sectional area of supporting conductor mm2 | Nominal cross-sectional areas of phase conductors mm2 |
54.6 | 25,35,50,70,95 |
70 | 70,95,120 |
95 | 95,120,150 |
—————————————————————————————————————————–
Aerial Bundle Conductor-ABC(South Africa Custimized Size Specification)
Table 03
Type of conductor or core | Norminal cross-sectional area mm2 | Nubmer of wires | Diameter of conductormm | Resistanceat 20ºC Ω/km Max. | Breaking force(N) | Thickness of insulation (mm) | Outer diameter of core(mm) | |||
Min. | Max. | Min. | Average | Min. | Min. | Max. | ||||
Phase or auxiliary or non-strain-bearing netural(aluminium) | 16 | 7/1.65 | 4.6 | 5.1 | 1.91 | 2070 | 1.2 | 0.98 | 7.0 | 7.8 |
25 | 7/2.15 | 5.8 | 6.3 | 1.2 | 3300 | 1.4 | 1.16 | 8.6 | 9.4 | |
35 | 7/2.55 | 6.8 | 7.3 | 0.868 | 4500 | 1.6 | 1.34 | 10.0 | 10.9 | |
50 | 7/2.99 | 7.9 | 8.4 | 0.641 | 6200 | 1.6 | 1.34 | 11.1 | 12.0 | |
70 | 14/2.59 | 9.7 | 10.2 | 0.443 | 8900 | 1.8 | 1.52 | 13.3 | 14.2 | |
95 | 19/2.59 | 11.0 | 12.0 | 0.320 | 12300 | 1.8 | 1.52 | 14.6 | 16.0 | |
120 | 19/2.99 | 12.5 | 13.5 | 0.253 | 15600 | 1.8 | 1.52 | 16.3 | 17.5 | |
150 | 30/2.59 | 13.9 | 15.0 | 0.206 | 19200 | 1.8 | 1.52 | 17.1 | 18.6 | |
Service connection(aluminium) | 16 | 7/1.65 | 4.6 | 5.2 | 1.91 | 2070 | 1.2 | 0.98 | 7.0 | 8.0 |
25 | 7/2.15 | 5.6 | 6.5 | 1.2 | 3300 | 1.4 | 1.16 | 8.6 | 9.6 | |
Service connection(copper) | 10 | 7/1.35 | – | 4.2 | 1.83 | 3600 | 1.2 | 0.98 | 6.2 | 7.0 |
16 | 7/1.69 | – | 5.3 | 1.15 | 5760 | 1.2 | 0.98 | 7.2 | 8.0 | |
25 | 7/2.19 | – | 6.6 | 0.727 | 8750 | 1.4 | 1.16 | 8.6 | 9.6 | |
Supporting core(aluminium alloy) | 16 | 7/1.71 | 5.1 | 5.2 | 2.053 | 5070 | 1.4 | 1.16 | 7.9 | 8.0 |
25 | 7/2.15 | 6.4 | 6.5 | 1.314 | 8000 | 1.4 | 1.16 | 9.2 | 9.3 | |
35 | 7/2.48 | 6.6 | 7.5 | 0.986 | 10300 | 1.6 | 1.34 | 10.7 | 10.8 | |
50 | 7/2.89 | 7.7 | 8.4 | 0.720 | 14200 | 1.6 | 1.34 | 11.9 | 12.0 | |
54.6 | 7/3.15 | 9.2 | 9.6 | 0.630 | 16600 | 1.6 | 1.34 | 12.3 | 13.0 | |
70 | 7/3.50 | 10.0 | 10.4 | 0.500 | 20100 | 1.6 | 1.34 | 12.9 | 13.6 |
We are China Aerial Bundle Cable ABC to Sans 1418 Size 3X70+54.6 manufacture and supplier,You can get more details with Email,you will get cheap price or factory price.
Get Latest Price Request a quote
Popular ABC Products
Aerial Bundle Cable with Aluminum Conductor
Quadruplex 0.6/1kv XLPE Insulated Al Conductor Aerial Bundle Overhead ABC Cable
ASTM Standard Aerial Aluminum Bouded Cable
3 X 70 50 Low Voltage Aerial Bundled Cable with Strand Aluminum Conductor
LV Aerial Bundled Cable ABC One Phase Aluminum Conductor 1X50+1X54.6mm2 0.6/1KV
Popular ABC Sans Products
Overhead Transmission ABC Cable to Sans 1418 Size 3X95+54.6
Aerial Bundle Cable (ABC cables with XLPE insulation) Size 4X35
Popular Aerial Bundled Cable Products
1kv XLPE/PVC Insulated ABC Aerial Bundle Cable with Aluminium Conductor
Aerial Bundle Cable ABC Aerial Overhead Cable with ACSR Messenger Core
Insulated Aerial Bundled Cable Manufacturer Price
LV Aerial Bundled Cable ABC for Overhead Transmission
ACSR Conductor Aerail Bundled Cable
3*70+1*54.6mm2 Aluminum Norme NFC33-209 Insulation 0.6/1kvaerial Bundle Cable
Popular jytopcable Products
PVC Insulated Thw Wire Building Wire Electric Wire
PVC Insulated Control Cable for 4mm2
4X95mm2 Copper or Aluminum Conductor XLPE/PVC Insulated PVC Sheath Power Cable
1kv Nayry Cable Aluminum Cable, Armoured Cable PVC Power Cable
Low Voltage 600V Triplex Service Cable 2X4AWG+4AWG
Aluminum PVC Cable, Swa Cable Steel Wire Armored Cable
Tags: ABC, ABC Sans, Aerial Bundled Cable, jytopcable