Cu (Al) 4 Core XLPE Insulated PVC Sheathed 16mm Armoured Cable
Cu (Al) 4 Core XLPE Insulated PVC Sheathed 16mm Armoured Cable image
Get Latest Price Request a quote
Quick Details
Product Details
Cu(Al) 4 Core, XLPE Insulated, PVC Sheathed,16mm armoured Cable
Application
Aerial Bundle Cable (ABC cable) is a very innovative concept for overhead power distribution as compared to the conventional bare conductor overhead distribution system.
It provides higher level of safety and reliability, lower power losses and ultimate system economy by reducing installation, maintenance and operative cost.
Caledonian LV Aerial Bundle Cables are designed to supply 600/1000 volt aerial service for temporary service at construction sites, as a service drop (power pole to service entrance), as a secondary cable (pole to pole) or street lighting.
This over-head cable provides reinforced insulation acc. IEC 61140 and fulfill therefore Class II acc. IEC 61140. It is not flame retardant. But this could be if requested change to a flame retardant cable.
Standard
Basic design to BS 7870 / TNB Specification(IEC 60502) / HD 626 S1 / NFC 33-209 / AS/NZS 3560-1 standards
Construction
| Conductor | Aluminium conductor, round stranded compressed (RM). |
| Insulation | XPLE compound, UV-resistant. |
| Core Identification | 1, 2 resp. 3 raised longitudinal ribs on the surface of the cores. The surface of the neutral core should have at least 12 ribs for cross-sections up to 50 mm² and a minimum of 16 ribs for cores above 50 mm². In the case of five core bundles the surface of the protective core should be smooth. |
Electrical Properties
| Rated Voltage | 0.6/1kV |
| Test Voltage | 4 Veff kV |
| Minimum Laying Temperature | -20°C |
| Operating Temperature | -40°C~ +90°C |
| Maximum Short-circuit Temperature | 250°C |
| Maximum Conductor Temperature | 80°C |
| Minimum Bending Radius | 18×OD |
Construction Parameters
BS 7870
| Number of Cores x Nominal Cross Section | Overall Diameter | Weight | Maximum Conductor Resistance | Minimum Breaking Load | Current Rating |
|---|---|---|---|---|---|
| No.×mm² | mm | Kg/Km | Ω/Km | KN | A |
| 1×16 RM | 8.0 | 74 | 1.910 | 2.5 | 72 |
| 1×25 RM | 9.0 | 106 | 1.200 | 4.0 | 107 |
| 1×35 RM | 10.5 | 138 | 0.868 | 5.5 | 132 |
| 1×50 RM | 11.8 | 182 | 0.641 | 8.0 | 165 |
| 1×70 RM | 13.0 | 252 | 0.443 | 10.7 | 205 |
| 1×95 RM | 15.4 | 333 | 0.320 | 13.7 | 240 |
| 1×120 RM | 17.0 | 408 | 0.253 | 18.6 | 290 |
| 1×150 RM | 19.0 | 502 | 0.206 | 23.2 | 334 |
| 1×185 RM | 21.0 | 611 | 0.164 | 28.7 | 389 |
| 1×240 RM | 24.0 | 801 | 0.125 | 37.2 | 467 |
| 2×16 RM | 15.6 | 147 | 1.910 | 2.5 | 72 |
| 2×25 RM | 18.0 | 208 | 1.200 | 4.0 | 107 |
| 2×35 RM | 20.0 | 277 | 0.868 | 5.5 | 132 |
| 2×50 RM | 23.5 | 361 | 0.641 | 8.0 | 165 |
| 2×70 RM | 25.4 | 505 | 0.443 | 10.7 | 205 |
| 2×95 RM | 30.3 | 666 | 0.320 | 13.7 | 240 |
| 2×150 RM | 38.0 | 1004 | 0.206 | 23.2 | 334 |
| 4×16 RM | 18.8 | 286 | 1.910 | 2.5 | 72 |
| 4×25 RM | 21.2 | 430 | 1.200 | 4.0 | 107 |
| 4×35 RM | 24.1 | 553 | 0.868 | 5.5 | 132 |
| 4×50 RM | 27.8 | 746 | 0.641 | 8.0 | 165 |
| 4×70 RM | 31.8 | 1009 | 0.443 | 10.7 | 205 |
| 4×95 RM | 37.8 | 1332 | 0.320 | 13.7 | 240 |
| 4×120 RM | 54.4 | 1632 | 0.253 | 18.6 | 290 |
| 4×50 + 1×25 RM | 31.9 | 814 | 0.641/1.200 | 8.0/4.0 | 165/107 |
| 4×50 + 1×35 RM | 31.9 | 845 | 0.641/0.868 | 8.5/5.5 | 165/132 |
| 4×70 + 1×25 RM | 36.0 | 1105 | 0.443/1.200 | 10.7/4.0 | 205/107 |
| 4×70 + 2×25 RM | 40.0 | 1217 | 0.443/1.200 | 10.7/4.0 | 205/107 |
| 4×95 + 1×25 RM | 41.8 | 1438 | 0.320/1.200 | 13.7/4.0 | 240/107 |
| 4×95 + 2×25 RM | 42.0 | 1544 | 0.320/1.200 | 13.7/4.0 | 240/107 |
| 4×120 + 1×25 RM | 59.0 | 2050 | 0.253/1.200 | 18.6/4.0 | 290/107 |
Other cross-sections can be offered upon request.
TNB Specification(IEC 60502)
| Number of Cores x Nominal Cross Section | Overal Diameter | Weight | Maximum Conductor Resistance | Minimum Breaking Load | Current Rating |
|---|---|---|---|---|---|
| No.×mm² | mm | Kg/Km | Ω/Km | KN | A |
| 1×16+1×25 RM | 15.3 | 160 | 1.910 | 2.5 | 72 |
| 3×16+1×25 RM | 19.0 | 290 | 1.200 | 4.0 | 107 |
| 3×25+1×25 RM | 23.2 | 400 | 0.868 | 5.5 | 132 |
| 3×35+1×25 RM | 25.6 | 500 | 0.641 | 8.0 | 165 |
| 3×50+1×35 RM | 30.0 | 680 | 0.443 | 10.7 | 205 |
| 3×70+1×50 RM | 34.9 | 920 | 0.320 | 13.7 | 240 |
| 3×95+1×70 RM | 40.6 | 1270 | 0.253 | 18.6 | 290 |
| 3×120+1×70 RM | 44.1 | 1510 | 0.206 | 23.2 | 334 |
| 3×150+1×95 RM | 49.2 | 1870 | 0.164 | 28.7 | 389 |
| 3×185+1×120 RM | 54.9 | 2340 | 0.125 | 37.2 | 467 |
| 3×25+1×25+1×16 RM | 23.2 | 470 | 1.910 | 2.5 | 72 |
| 3×35+1×25+1×16 RM | 25.6 | 560 | 1.200 | 4.0 | 107 |
| 3×50+1×35+1×16 RM | 30.0 | 740 | 0.868 | 5.5 | 132 |
| 3×70+1×50+1×16 RM | 34.9 | 980 | 0.641 | 8.0 | 165 |
| 3×95+1×70+1×16 RM | 40.6 | 1330 | 0.443 | 10.7 | 205 |
| 3×120+1×70+1×16 RM | 44.1 | 1580 | 0.320 | 13.7 | 240 |
| 3×150+1×95+1×16 RM | 49.2 | 1940 | 0.206 | 23.2 | 334 |
| 3×185+1×120+1×16 RM | 54.9 | 2410 | 1.910 | 2.5 | 72 |
Other cross-sections can be offered upon request.
HD 626 S1
| number of cores x nominal cross section | outer diameter | total weight | max. conductor- resistance | min. breaking load of conductor strand | current rating in the air 1) |
|---|---|---|---|---|---|
| mm² | ca. mm | ca. kg/km | Ohm/km | kN | A |
| 2x 16 RM | 15.6 | 147 | 1.910 | 2.5 | 72 |
| 2x 25 RM | 18.0 | 208 | 1.200 | 4.0 | 107 |
| 2x 35 RM | 20.0 | 277 | 0.868 | 5.5 | 132 |
| 2x 50 RM | 23.5 | 361 | 0.641 | 8.0 | 165 |
| 4x 16 RM | 18.8 | 286 | 1.910 | 2.5 | 72 |
| 4x 25 RM | 21.2 | 430 | 1.200 | 4.0 | 107 |
| 4x 35 RM | 24.1 | 553 | 0.868 | 5.5 | 132 |
| 4x 50 RM | 27.8 | 746 | 0.641 | 8.0 | 165 |
| 4x 70 RM | 31.8 | 1009 | 0.443 | 10.7 | 205 |
| 4x 95 RM | 37.8 | 1332 | 0.320 | 13.7 | 240 |
| 4x 120 RM | 54.4 | 1632 | 0.253 | 18.6 | 290 |
| 4x 35 + 1x 35 RM | 30.0 | 694 | 0.868/0.868 | 5.5/5.5 | 132/132 |
| 4x 50 + 1x 25 RM | 31.9 | 814 | 0.641/1.200 | 8.0/4.0 | 165/107 |
| 4x 50 + 1x 35 RM | 31.9 | 845 | 0.641/0.868 | 8.5/5.5 | 165/132 |
| 4x 70 + 1x 25 RM | 36.0 | 1105 | 0.443/1.200 | 10.7/4.0 | 205/107 |
| 4x 70 + 2x 25 RM | 40.0 | 1217 | 0.443/1.200 | 10.7/4.0 | 205/107 |
| 4x 70 + 1x 35 RM | 36.2 | 1150 | 0.443/0.868 | 10.7/5.5 | 205/132 |
| 4x 70 + 2x 35 RM | 40.1 | 1289 | 0.443/0.868 | 10.7/5.5 | 205/132 |
| 4x 95 + 1x 25 RM | 41.8 | 1438 | 0.320/1.200 | 13.7/4.0 | 240/107 |
| 4x 95 + 1x 35 RM | 41.8 | 1467 | 0.320/0.868 | 13.7/5.5 | 240/132 |
| 4x 95 + 2x 25 RM | 42.0 | 1544 | 0.320/1.200 | 13.7/4.0 | 240/107 |
Other cross-sections can be offered upon request.
NFC 33-209
| Number of Cores x Nominal Cross Section | Overal Diameter | Weight | Maximum Conductor Resistance | Minimum Breaking Load | Current Rating |
|---|---|---|---|---|---|
| No.×mm² | mm | Kg/Km | Ω/Km | KN | A |
| 2×10 RM | 12.8 | 93 | 3.080 | 1.5 | 38 |
| 4×10 RM | 15.4 | 183 | 3.080 | 1.5 | 38 |
| 2×16 RM | 14.8 | 129 | 1.910 | 2.3 | 72 |
| 2×16 RN + 2×1.5 RE | 14.8 | 176 | 1.910/12.100 | 2.3 | 72 |
| 4×16 RM | 17.8 | 257 | 1.910 | 2.3 | 72 |
| 4×16 RN + 2×1.5 RE | 17.8 | 304 | 1.910/12.100 | 2.3 | 72 |
| 2×25 RM | 18.0 | 202 | 1.200 | 3.8 | 107 |
| 2×25 RM + 2×1.5 RE | 18.0 | 249 | 1.200/12.100 | 3.8 | 107 |
| 4×25 RM | 21.7 | 404 | 1.200 | 3.8 | 107 |
| 4×25 RM + 2×1.5 RE | 21.7 | 451 | 1.200/12.100 | 3.8 | 107 |
| 2×35 RM | 20.8 | 269 | 0.868 | 5.2 | 132 |
| 2×35 RM + 2×1.5 RE | 20.8 | 316 | 0.868/12.100 | 5.2 | 132 |
| 4×35 RM | 25.1 | 539 | 0.868 | 5.2 | 132 |
| 4×35 RM + 2×1.5 RE | 25.1 | 586 | 0.868/12.100 | 5.2 | 132 |
| 2×50 RM | 23.4 | 352 | 0.641 | 7.6 | 165 |
| 2×50 RM + 2×1.5 RE | 23.4 | 399 | 0.641/12.100 | 7.6 | 165 |
| 1×54.6 RM + 3×25 RM | 21.7 | 507 | 0.630/1.200 | 3.8 | 107 |
| 1×54.6 RM + 3×25 RM + 1×16 RM | 24.3 | 573 | 0.630/1.200/1.910 | 3.8/2.3 | 107/72 |
| 1×54.6 RM + 3×25 RM + 2×16 RM | 29.7 | 639 | 0.630/1.200/1.910 | 3.8/2.3 | 107/72 |
| 1×54.6 RM + 3×25 RM + 3×16 RM | 31.1 | 705 | 0.630/1.200/1.910 | 3.8/2.3 | 107/72 |
| 1×54.6 RM + 3×35 RM | 25.1 | 615 | 0.630/0.868 | 5.2 | 132 |
| 1×54.6 RM + 3×35 RM + 1×16 RM | 28.1 | 680 | 0.630/0.868/1.910 | 5.2/2.3 | 132/72 |
| 1×54.6 RM + 3×35 RM + 2×16 RM | 34.3 | 748 | 0.630/0.868/1.910 | 5.2/2.3 | 132/72 |
| 1×54.6 RM + 3×35 RM + 3×16 RM | 35.9 | 814 | 0.630/0.868/1.910 | 5.2/2.3 | 132/72 |
| 1×54.6 RM + 3×35 RM + 1×25 RM | 28.1 | 714 | 0.630/0.868/1.200 | 5.2/3.8 | 132/107 |
| 1×54.6 RM + 3×50 RM | 28.2 | 741 | 0.630/0.641 | 7.6 | 165 |
| 1×54.6 RM + 3×50 RM + 1×16 RM | 31.6 | 806 | 0.630/0.641/1.910 | 7.6/2.3 | 165/72 |
| 1×54.6 RM + 3×50 RM + 2×16 RM | 38.6 | 875 | 0.630/0.641/1.910 | 7.6/2.3 | 165/72 |
| 1×54.6 RM + 3×50 RM + 3×16 RM | 40.4 | 940 | 0.630/0.641/1.910 | 7.6/2.3 | 165/72 |
| 1×54.6 RM + 3×50 RM + 1×25 RM | 31.6 | 841 | 0.630/0.641/1.200 | 7.6/3.8 | 165/107 |
| 1×54.6 RM + 3×70 RM | 33.0 | 950 | 0.630/0.443 | 10.2 | 205 |
| 1×54.6 RM + 3×70 RM + 1×16 RM | 37.0 | 1014 | 0.630/0.443/1.910 | 10.2/2.3 | 205/72 |
| 1×54.6 RM + 3×70 RM + 2×16 RM | 45.2 | 1083 | 0.630/0.443/1.910 | 10.2/2.3 | 205/72 |
| 1×54.6 RM + 3×70 RM + 3×16 RM | 47.3 | 1148 | 0.630/0.443/1.910 | 10.2/2.3 | 205/72 |
| 1×54.6 RM + 3×70 RM + 1×25 RM | 37.0 | 1048 | 0.630/0.443/1.200 | 10.2/3.8 | 205/107 |
| 1×54.6 RM + 3×70 RM + 2×25 RM | 45.2 | 1150 | 0.630/0.443/1.200 | 10.2/3.8 | 205/107 |
| 1×54.6 RM + 3×70 RM + 3×25 RM | 47.3 | 1250 | 0.630/0.443/1.200 | 10.2/3.8 | 205/107 |
| 1×54.6 RM + 3×95 RM | 37.4 | 1176 | 0.630/0.320 | 13.5 | 240 |
| 1×54.6 RM + 3×95 RM + 1×16 RM | 41.9 | 1243 | 0.630/0.320/1.910 | 13.5/2.3 | 240/72 |
Other cross-sections can be offered upon request.
AS/NZS 3560 Part 1
| Number of Cores x Nominal Cross Section | Overall Diameter | Weight | Minimum Breaking Load | Current Rating |
|---|---|---|---|---|
| No.×mm² | mm | Kg/Km | KN | A |
| 2×16 RM | 15.0 | 140 | 4.4 | 78 |
| 2×25 RM | 17.6 | 210 | 7.0 | 105 |
| 2×35 RM | 19.6 | 270 | 9.8 | 125 |
| 2×50 RM | 22.8 | 370 | 11.4 | 150 |
| 2×95 RM | 30.6 | 680 | 15.3 | 230 |
| 3×25 RM | 19.0 | 310 | 8.8 | 97 |
| 3×35 RM | 21.1 | 410 | 9.8 | 120 |
| 3×50 RM | 24.6 | 550 | 11.4 | 140 |
| 4×16 RM | 18.1 | 290 | 8.8 | 74 |
| 4×25 RM | 21.2 | 410 | 14.0 | 97 |
| 4×35 RM | 23.7 | 550 | 19.6 | 120 |
| 4×50 RM | 27.5 | 740 | 28.0 | 140 |
| 4×70 RM | 31.9 | 1000 | 39.2 | 175 |
| 4×95 RM | 36.9 | 1370 | 53.2 | 215 |
| 4×120 RM | 40.6 | 1690 | 67.2 | 250 |
| 4×150 RM | 43.9 | 2020 | 84.0 | 280 |
Other cross-sections can be offered upon request.
We are China Cu (Al) 4 Core XLPE Insulated PVC Sheathed 16mm Armoured Cable manufacture and supplier,You can get more details with Email,you will get cheap price or factory price.
Get Latest Price Request a quote
Popular 1kv Armored Cable Products
Low Voltage XLPE Cable with Steel Tape Armored and Multi Cores
1kv Copper Cable 3X70mm with Steel Tape Armored
0.6/1kv Armored Cable 3X120mm Aluminum Cable with Steel Tape Armored
0.6/1kv Type Mv PVC/Swa/PVC 2.5mm 4 Core Copper Power Cable with Armored
3X95mm Aluminum Conductor XLPE Insulated Cable with Steel Tape Armored
0.6/1kv PVC Insulated PVC Sheated 2.5mm 3 Core Copper Power Cable with Swa Armored
Popular Insulated Cable Products
450/750V Copper Conductor Steel-Tape Armored Control Cable
Electric Single Core Insulated Copper Wire Shield Aluminum Power Cable
Yjv Insulated Underground Electrical Wire Power Cable
Low Voltage Al Conductor XLPE Insulated Aerial Bundled Cable
Copper Conductor Kvv32/Kvv22/Zr-Kvv22/Zr-Kvv32 Control Cable
Electric PVC Conductor PVC XLPE Insulated Overhead Wire Cable
Popular jytopcable Products
Mv 6.35/11kv Single Core Copper Conductor XLPE Insulated Power Cable
Factory Wholesale Prices! ! High Purity AAC CSA C49
12/20kv Copper Cable with XLPE Insulated
7/8 Galvanized (Zinc-coated) Steel Stay Wire
600V PVC Insulated Copper Wire with CE Certificate
0.6/1kv Multicore Nyy Electric Cable
Popular Steel Wire Armoured Cable Products
0.6/1kv 16mm 4 Core Copper PVC Insulated Swa Armored Cable
Underground Cable Steel Wire / Tape Armoured Copper Power Cable
0.6/1kv Copper Conductor 185mm 240mm XLPE 4 Core Armoured Cable
33kv/22kv/11kv Cu/XLPE/Swa/PVC Armoured Power Cables
4 Core Aluminium Conductor Steel Wire Swa Armoured Power Cable
Tags: 1kv Armored Cable, Insulated Cable, jytopcable, Steel Wire Armoured Cable