Aluminimum Conductor Aluminimum Alloy Reinforced (ACAR)

China 
                        Aluminimum Conductor Aluminimum Alloy Reinforced (ACAR)
                      manufacture and supplier

Aluminimum Conductor Aluminimum Alloy Reinforced (ACAR) image

Get Latest Price Request a quote

Quick Details

Aluminimum Conductor Aluminimum Alloy Reinforced (ACAR)

bare conductor

ISO, CCC

Bare

AC Cable

Low and Medium Voltage Cable

Construction, Overhead, Power Station

Qing Dao or as Request

Jin Shui

Iron-Wooden Drum. Iron Drum

ASTM, DIN. IEC or as request

Zhengzhou, Hean, China

Product Details

Bare conductor—–AAC/AAAC/ACSR conductor
AAC, AAAC, ACSR, AACSR&ACAR conductor widely used in power transmission lines with various voltage levels. Since they have such good characteristics as simple structure, convenient installation and maintenance, low cost for the line, large transmission capacity and are also suitable for laying across rivers and valleys where special geographical teatures exist.

1. Specification:
(1) all aluminium conductor (AAC)
(2) all aluminimum alloy conductor(AAAC)
(3) aluminum conductor steel reinforced (ACSR)
(4) anti-corrosion type ACSR
(5) aluminimum conductor aluminimum clad steel reinforced(ACSR/AW)
(6)rear earth aluminimum conductor steel reinforced(ACSR/RE)
(7)aluminimum conductor aluminimum alloy reinforced(ACAR)

2. Elative manufacturing standards:
1). Standard: IEC61089, BS215 part2, ASTM B232, DIN48204, BS EN50182.
2). Specification: ACSR is composed by bare concentric-lay-stranded galvanized steel wire(s) with aluminum wires surrounded by one or more layers of helically. Greased ACSR can also be supplied.
3). Application: ACSR is widely used in overhead electric power transmission and distribution lines with
Various voltage levels.

All Aluminum Conductor(AAC)& Aluminum Conductor Steel Reinforced(ACSR))for ASTM
(AAC, ACCR, AAAC, ACSR) Generally Confirming to IS 398 (Part-I, II, IV), IEC-228
(AAAC) Conductor as per ASTM-B-399-1992
(AAAC) Conductor as per BS-3242-1970
(AAAC) Conductor IS: 398-IV-1994
(ACSR) as per ASTM-B-233-1992
(AAC) as per BS-215-1-1970
(AAC) as per IS-398-1: 1976
(AAC) as per ASTM-B-231-1990
(ACSR) as per IS: 398-II: 1976 & IS: 398-V: 1992
(ACSR) BS-215-II-1970
(AACSR) as per IEC-1089-1191
AAC(All aluminum conductor) are suited for overhead power line.

We can supply this conductor according to different recognized standards, distribution and transmission lines for distributing power.

Applications:
Used as bare overhead transmission cable and as primary and secondary distribution cable. ACSR offers optimal strength for line design. Variable steel core stranding enables desired strength to be achieved without sacrificing ampacity.

Construction:
Aluminum alloy 1350-H-19 wires, concentrically stranded about a steel core. Core wire for ACSR is available with class A, B, or C galvanizing; ""aluminized"" aluminum coated (AZ); Or aluminum-clad (AW). Additional corrosion protection is available through the application of grease to the corrosion or infusion of the complete cable with grease.

Specifications:
ACSR bare conductor meets or exceeds the following ASTM specifications:
B-230 Aluminum Wire, 1350-H19 for Electrical Purposes
B-231 Aluminum Conductors, Concentric-Lay-Stranded
B-232 Aluminum Conductors, Concentric-Lay-Stranded, Coated Steel Reinforced (ACSR)
B-341 Aluminum-clad Steel Core Wire for Aluminum Conductors, Steel Reinforced (ACSR/AW)
B-498 Zinc-Coated Steel Core Wire for Aluminum Conductors, Steel Reinforced (ACSR/AZ)
B-500 Zinc Coated and Aluminum Coated Stranded Steel Core for Aluminum Conductors, Steel Reinforced (ACSR)

Notes:
Resistance is calculated using ASTM standard increments of stranding and metal conductivity of 61.2% IACS for EC (1350) and 8% IACS for steel. AC (60Hz) resistance includes current dependent hysteresis loss factor for 1 and 3 layer constructions.
Current ratings are based on 75oC conductor temperature, 25oC ambient, 2ft/s wind, 96/watts/sq. Ft sun, 0.5 coefficients of emissivity and absorption.

Nominal
Alum
mm 2
Number/Diameter
mm
Calculation Area  
mm 2
Approx.
Overall Diameter
mm
 
Max. D. C.
Resistance
At 20  degrees Celsius
≤ Ω /km
 
Nominal breaking load
KN
 
Weight
kg/km
 
Al
 
Steel
 
Al
 
Steel
 
Total
10 6/1.50 1/1.50 10.62 1.77 12.39 4.50 2.706 4.14 43
20 6/2.11 1/2.11 20.94 3.49 24.43 6.33 1.368 7.88 85
25 6/2.36 1/2.36 26.25 4.37 30.62 7.08 1.093 9.61 106
30 6/2.59 1/2.59 31.61 5.27 36.88 7.77 0.9077 11.45 128
35 6/2.79 1/2.79 36.66 6.11 42.70 8.37 0.7822 13.20 149
40 6/3.00 1/3.00 42.41 7.07 49.48 9.00 0.6766 15.20 172
50 6/3.35 1/3.35 52.88 8.82 61.70 10.05 0.5426 18.35 214
60 6/3.66 1/3.66 63.18 10.53 73.71 10.98 0.4545 21.80 255
60 12/2.59 7/2.59 63.27 36.93 100.30 12.95 0.4567 53.00 465
70 6/3.99 1/3.99 74.82 12.47 87.29 11.97 0.3825 25.70 302
70 12/2.79 7/2.79 73.37 42.80 116.17 13.95 0.3936 61.20 538
75 6/4.10 1/4.10 79.20 13.20 92.40 12.30 0.3622 27.20 320
80 6/4.22 1/4.22 83.88 13.98 97.86 12.66 0.3419 28.80 339
90 6/4.50 1/4.50 95.40 15.90 111.30 13.50 0.3007 32.70 386
100 6/4.72 1/4.72 105.00 17.50 122.50 14.16 0.2733 36.00 425
100 6/4.72 7/1.57 105.00 13.50 118.50 14.15 0.2733 32.70 394
100 7/4.39 7/1.93 105.80 20.44 126.20 14.57 0.2712 40.90 450
125 6/5.28 7/1.75 131.30 16.80 148.10 15.81 0.2184 40.70 492
125 26/2.54 7/1.91 132.10 20.10 152.20 15.89 0.2187 46.40 522
125 18/3.05 1/3.05 130.30 7.25 137.50 15.25 0.2189 29.80 419
125 30/2.36 7/2.36 131.10 30.60 161.70 16.52 0.2202 58.00 602
150 30/2.59 7/2.59 158.00 36.90 194.90 18.13 0.1828 69.20 726
150 18/3.35 1/3.35 158.70 8.80 167.50 16.57 0.1815 35.70 506
175 30/2.79 7/2.79 183.40 42.80 226.20 19.53 0.1576 79.80 842
175 18/3.61 1/3.61 184.20 10.30 194.50 18.05 0.1563 41.10 587
200 30/3.00 7/3.00 212.00 49.50 261.50 21.00 0.1363 92.25 974
225 30/3.18 7/3.18 238.50 55.60 294.20 22.26 0.1212 109.60 1095
250 30/3.35 7/3.35 264.00 61.60 325.60 23.45 0.1093 111.10 1213
300 30/3.71 7/3.71 324.30 75.70 400.00 25.97 0.0891 135.70 1489
350 30/3.99 7/3.99 374.10 87.30 461.40 27.93 0.07704 155.90 1718
350 54/2.97 7/2.97 373.10 48.40 421.50 26.73 0.07727 118.20 1411
350 54/3.00 7/3.00 381.80 49.50 431.30 27.00 0.07573 120.90 1444
200 18/3.86 1/3.86 210.60 11.70 222.30 19.30 0.013670 46.55 671
400 30/4.27 7/4.27 429.30 100.20 529.50 29.89 0.06726 178.50 1971
400 54/3.18 7/3.18 428.90 55.30 484.50 28.62 0.06740 131.90 1621
450 30/4.50 7/4.50 477.00 111.30 588.30 31.50 0.06056 198.20 2190
450 54/3.35 7/3.35 475.20 61.60 536.80 30.15 0.06073 145.70 1797
500 54/3.53 7/3.53 528.70 68.50 597.20 31.77 0.05470 161.10 1999

We are China Aluminimum Conductor Aluminimum Alloy Reinforced (ACAR) manufacture and supplier,You can get more details with Email,you will get cheap price or factory price.

Get Latest Price Request a quote

Popular AAAC Conductor Products

All Aluminium Conductor / AAC Overhead Conductor

Bare Aluminium/Aluminum AAC AAAC ACSR Tacsr Aacsr Acar Conductor for Overhead Power Transmission Line

Overhead ACSR, AAC, AAAC, Acss/Tw, Accc, Aacsr, Acar, Opgw Bare Conductor

High Quality ASTM B399 Standard AAAC Conductor

DIN 48201 95mm2 120mm2 150mm2 AAAC Overhead Bare Conductor

High Quality Bare AAAC Conductor Manufacturer

Popular ACSR Conductor Products

ACSR Overhead Conductor Aluminum Clad Steel Bare Conductor

Bare ACSR Aluminum Cable Conductor IEC/BS/DIN/ASTM/CSA, ACSR Stranded Conductor

ACSR Conductor IEC 61089 Wolf

USA Sizes ASTM B232 Aluminum Conductor Steel Reinforced ACSR Swan

ACSR Dog Conductor/AAC/AAAC ACSR Cables Power Cable

DIN 48204 380/50mm2 ACSR Bare Overhead Conductor

Popular Aluminum Conductor Products

ACSR Cable 95/15mm2 Overhead Application

Aluminum Conductor Steel Reinforced ACSR Bs 215 Skunk

Aluminum Condutor XLPE Insulation PVC Sheath 1X240mm2

Aluminium Alloy Conductor for African Country Used Overhead Cable with Good Quality

ACSR Cable 120 / 20mm2 Secondary Line Overhead Application

Stranded Steel Reinforced Bare Aluminium Conductor AAC/AAAC/ACSR

Popular jsgroup Products

Underground Application Mv Cable Al/XLPE 15kv

Uesd for Overhead Service Application Flexible Copper for Street Linghting

PVC Insulated Power Cable, Aluminum Conductor Fire Resistant Cable

Triplex Sevice Drop (ABC) Cable

3X2.5mm2 Yjv32 Power Electrical Cable

Aluminum Conductor PVC Insulated Outer Covered Power Cable

Tags: , , ,

FAST AND RELIABLE SERVICE FOR YOUR PROJECT

Contact our trained experts today to find your perfect power solution.

ASK A QUESTION