BS 3242 Aluminum Alloy Conductors for Overhead Power Transmission Fir
BS 3242 Aluminum Alloy Conductors for Overhead Power Transmission Fir image
Get Latest Price Request a quote
Quick Details
Product Details
AAAC (All Aluminum Alloy Conductor) referred to have higher strength but lower conductivity than pure aluminum. Being lighter, alloy conductors can sometimes be used to advantage in place of the more conventional ACSR;
Having lower breaking loads than the latter, their use becomes particularly favourable when ice and win loadings are low.
We can supply this conductor according to different recognized standards, such as BS EN50182, IEC61089, ASTM B399DIN 48, customer special specification also can be satisfied.
2. Applications:
Used as bare overhead conductor for primary and secondary distribution. Designed utilizing a high-strength aluminum-alloy to achieve a high strength-to-weight ratio; affords good sag characteristics. Aluminum-alloy gives 6201-T81 gives AAAC higher resistance to corrosion than ACSR.
3. Standards&Specifications:
All Aluminium Alloy Conductor-AAAC (DIN 48201 Standard Sizes)
Nominal Area | Conductor Construction | Calculated Area | Overall Diameter | Weight | DC Resistance at 20 |
mm2 | No./mm | mm2 | mm | kg/km | Ω/km |
16 | 7/1.70 | 15.9 | 5.1 | 43.5 | 2.091 |
25 | 7/2.10 | 24.2 | 6.3 | 66.4 | 1.370 |
35 | 7/2.50 | 34.4 | 7.5 | 94.1 | 0.9669 |
50 | 7/3.00 | 49.5 | 9.0 | 135 | 0.6714 |
50 | 19/1.80 | 48.3 | 9.0 | 133 | 0.6905 |
70 | 19/2.10 | 65.8 | 10.5 | 181 | 0.5073 |
95 | 19/2.50 | 93.3 | 12.5 | 257 | 0.358 |
120 | 19/2.80 | 117 | 14 | 322 | 0.2854 |
150 | 37/2.25 | 147 | 15.7 | 406 | 0.2274 |
185 | 37/2.50 | 182 | 17.5 | 501 | 0.1842 |
240 | 61/2.25 | 243 | 20.2 | 671 | 0.1383 |
300 | 61/2.50 | 299 | 22.5 | 828 | 0.1120 |
400 | 61/2.89 | 400 | 26.0 | 1,106 | 0.0838 |
500 | 61/3.23 | 500 | 29.1 | 1382 | 0.06709 |
625 | 91/2.96 | 626 | 32.6 | 1,735 | 0.05367 |
800 | 91/3.35 | 802 | 36.9 | 2,222 | 0.0419 |
1000 | 91/3.74 | 1,000 | 41.1 | 2,770 | 0.03362 |
ALUMINIUM ALLOY CONDUCTOR ASTM B399 | |||||||||
Code Name | Area | Size&Stranding of ACSR with equal diameter | No. and diameter | Overall diameter | Weight | Nominal breaking load | MAX .DC resistance at 20ºC | ||
Nominal | Actual | AWG or MCM | Al/St | ||||||
MCM | mm2 | mm | mm | kg/km | kN | ohm/km | |||
AKRON | 30.58 | 15.48 | 6 | 6/1 | 7/1.68 | 5.04 | 42.7 | 4.92 | 0.3966 |
ALTON | 48.69 | 24.71 | 4 | 6/1 | 7/2.12 | 6.35 | 68 | 7.84 | 0.3811 |
AMES | 77.47 | 39.22 | 2 | 6/1 | 7/2.67 | 8.02 | 108 | 12.45 | 0.3671 |
AZUSA | 123.3 | 62.38 | 1/0 | 6/1 | 7/3.37 | 10.11 | 172 | 18.97 | 0.3524 |
ANAHEIM | 155.4 | 78.65 | 2/0 | 6/1 | 7/3.78 | 11.35 | 217 | 23.93 | 0.3448 |
AMHERST | 195.7 | 99.22 | 3/0 | 6/1 | 7/4.25 | 12.75 | 273 | 30.18 | 0.3375 |
ALLIANCE | 246.9 | 125.1 | 4/0 | 6/1 | 7/4.77 | 14.31 | 345 | 38.05 | 0.3306 |
BUTTE | 312.8 | 158.6 | 266.8 | 26/7 | 19/3.26 | 16.3 | 437 | 48.76 | 0.3196 |
CANTON | 394.5 | 199.9 | 366.4 | 26/7 | 19/3.66 | 18.3 | 551 | 58.91 | 0.3124 |
CAIRO | 465.4 | 235.8 | 397.5 | 26/7 | 19/3.98 | 19.88 | 650 | 69.48 | 0.3071 |
DARIEN | 559.5 | 283.5 | 477 | 26/7 | 19/4.36 | 21.79 | 781 | 83.52 | 0.3014 |
ELGIN | 652.4 | 330.6 | 556.5 | 26/7 | 19/4.71 | 23.54 | 911 | 97.42 | 0.2966 |
FLINT | 740.8 | 375.3 | 636 | 26/7 | 37/3.59 | 25.16 | 1035 | 108.21 | 0.2917 |
GREELY | 927.2 | 469.8 | 795 | 26/7 | 37/4.02 | 28.14 | 1295 | 135.47 | 0.2846 |
Area | Stranding and wire diameter | Approx. overall diameter | Weight | Nominal Breaking Load | MAX .DC resistance at 20ºC | |
Nominal | Actual | |||||
AWGorMCM | (mm2) | (mm) | (mm) | (kg/km) | (kN) | (ohm/km) |
6 | 13.30 | 7/1.554 | 4.67 | 37 | 4.22 | 2.5199 |
4 | 21.15 | 1/1.961 | 5.89 | 58 | 6.71 | 1.5824 |
2 | 33.63 | 7/2.474 | 7.42 | 93 | 10.68 | 0.9942 |
1/0 | 53.48 | 7/3.119 | 9.36 | 148 | 16.97 | 0.6256 |
2/0 | 67.42 | 7/3.503 | 10.51 | 186 | 20.52 | 0.4959 |
3/0 | 85.03 | 7/3.932 | 11.8 | 234 | 25.86 | 0.3936 |
4/0 | 107.23 | 7/4.417 | 13.26 | 296 | 32.63 | 0.3119 |
250 | 126.66 | 19/2.913 | 14.57 | 349 | 38.93 | 0.2642 |
300 | 152.1 | 19/3.193 | 15.97 | 419 | 46.77 | 0.2199 |
350 | 177.35 | 19/3.447 | 17.24 | 489 | 52.25 | 0.1887 |
400 | 202.71 | 19/3.686 | 18.43 | 559 | 59.74 | 0.1650 |
450 | 228 | 19/3.909 | 19.55 | 629 | 67.19 | 0.1467 |
500 | 253.35 | 19/4.120 | 20.60 | 698 | 74.64 | 0.1321 |
550 | 278.60 | 37/3.096 | 21.67 | 768 | 83.80 | 0.1202 |
600 | 303.80 | 37/3.233 | 22.63 | 838 | 91.38 | 0.1102 |
650 | 329.25 | 37/3.366 | 23.56 | 908 | 97.94 | 0.1016 |
700 | 354.55 | 37/3.493 | 24.45 | 978 | 102.20 | 0.0944 |
750 | 380.20 | 37/3.617 | 25.32 | 1049 | 109.60 | 0.0880 |
800 | 405.15 | 37/3.734 | 26.14 | 1117 | 116.80 | 0.0826 |
900 | 456.16 | 37/3.962 | 27.73 | 1258 | 131.50 | 0.0733 |
1000 | 506.71 | 37/4.176 | 29.23 | 1399 | 146.10 | 0.0660 |
1100 | 557 | 61/3.41 | 30.69 | 1537 | 162.16 | 0.0589 |
1200 | 608 | 61/3.56 | 32.04 | 1677 | 176.75 | 0.0541 |
1300 | 659 | 61/3.71 | 33.39 | 1816 | 191.95 | 0.0498 |
1400 | 709 | 61/3.85 | 34.65 | 1955 | 206.72 | 0.0463 |
1500 | 760 | 61/3.98 | 35.82 | 2095 | 220.90 | 0.0441 |
1600 | 811 | 61/4.12 | 37.08 | 2236 | 235.57 | 0.0405 |
1700 | 861 | 61/4.24 | 38.16 | 2374 | 250.72 | 0.0382 |
1800 | 912 | 61/4.36 | 39.28 | 2514 | 265.11 | 0.03693 |
1900 | 963 | 91/3.67 | 40.37 | 2655 | 277.10 | 0.03411 |
2000 | 1013 | 91/3.76 | 41.4 | 2793 | 292.41 | 0.03243 |
ALUMINIUM ALLOY CONDUCTOR BSEN50183 | |||||||
Code Name | Calculated Area | No. Of Wires | Diameter | Weight | Rated Strength | MAX .DC resistance at 20ºC | |
Wire | Cond. | ||||||
mm2 | mm | mm | kg/km | Kn | ohm/km | ||
Box | 18.8 | 7 | 1.85 | 5.55 | 51.4 | 5.55 | 1.748 |
Acacia | 23.8 | 7 | 2.08 | 6.24 | 64.9 | 7.02 | 1.3828 |
Almond | 30.1 | 7 | 2.34 | 7.02 | 82.2 | 8.88 | 1.0926 |
Cedar | 35.5 | 7 | 2.54 | 7.62 | 96.8 | 10.46 | 0.9273 |
Deodar | 42.2 | 7 | 2.77 | 8.31 | 115.2 | 12.44 | 0.7797 |
Fir | 47.8 | 7 | 2.95 | 8.85 | 130.6 | 14.11 | 0.6875 |
Hazel | 59.9 | 7 | 3.3 | 9.9 | 163.4 | 17.66 | 0.5494 |
Pine | 71.6 | 7 | 3.61 | 10.8 | 195.6 | 21.14 | 0.4591 |
Holly | 84.1 | 7 | 3.91 | 11.7 | 229.5 | 24.79 | 0.3913 |
Willow | 89.7 | 7 | 4.04 | 12.1 | 245 | 26.47 | 0.3665 |
Oak | 118.9 | 7 | 4.65 | 14 | 324.5 | 35.07 | 0.2767 |
Mulberry | 150.9 | 19 | 3.18 | 15.9 | 414.3 | 44.52 | 0.2192 |
Ash | 180.7 | 19 | 3.48 | 17.4 | 496.1 | 53.31 | 0.183 |
Elm | 211 | 19 | 3.76 | 18.8 | 579.2 | 62.24 | 0.1568 |
Poplar | 239.4 | 37 | 2.87 | 20.1 | 659.4 | 70.61 | 0.1387 |
Sycamore | 303.2 | 37 | 3.23 | 22.6 | 835.2 | 89.4 | 0.1095 |
Upas | 362.1 | 37 | 3.53 | 24.7 | 997.5 | 106.82 | 0.0917 |
Yew | 479 | 37 | 4.06 | 28.4 | 1319.6 | 141.31 | 0.0693 |
Totara | 498.1 | 37 | 4.14 | 29 | 1372.1 | 146.93 | 0.0666 |
Rubus | 586.9 | 61 | 3.5 | 31.5 | 1622 | 173.13 | 0.0567 |
Sorbus | 659.4 | 61 | 3.71 | 33.4 | 1822.5 | 194.53 | 0.0505 |
Araucaria | 821.1 | 61 | 4.14 | 37.3 | 2269.4 | 242.24 | 0.0406 |
Redwood | 996.2 | 61 | 4.56 | 41 | 2753.2 | 293.88 | 0.0334 |
ALUMINIUM ALLOY CONDUCTOR BS 3242 | |||||||
Code Name | Calculated Area | No. Of Wires | Diameter | Weight | Rated Strength | MAX .DC resistance at 20ºC | |
Wire | Cond. | ||||||
mm2 | mm | mm | kg/km | Kn | ohm/km | ||
Box | 15 | 7/1.85 | 18.82 | 5.55 | 51 | 537 | 1.7495 |
Acacia | 20 | 7/2.08 | 23.79 | 6.24 | 65 | 680 | 1.384 |
Almond | 25 | 7/2.34 | 30.1 | 7.02 | 82 | 861 | 1.0934 |
Cedar | 30 | 7/2.54 | 35.47 | 7.62 | 97 | 1014 | 0.9281 |
– | 35 | 7/2.77 | 42.18 | 8.31 | 115 | 1205 | 0.7804 |
Fir | 40 | 7/2.95 | 47.87 | 8.85 | 131 | 1367 | 0.688 |
Hazel | 50 | 7/3.30 | 59.87 | 9.9 | 164 | 1711 | 0.5498 |
Pine | 60 | 7/3.61 | 71.65 | 10.83 | 196 | 2048 | 0.4594 |
– | 70 | 7/3.91 | 84.05 | 11.73 | 230 | 2402 | 0.3917 |
Willow | 75 | 7/4.04 | 89.73 | 12.12 | 245 | 2565 | 0.3669 |
– | 80 | 7/4.19 | 96.52 | 12.57 | 264 | 2758 | 0.3441 |
– | 90 | 7/4.44 | 108 | 13.32 | 298 | 3112 | 0.3023 |
Oak | 100 | 7/4.65 | 118.9 | 13.95 | 325 | 3398 | 0.2769 |
– | 100 | 19/2.82 | 118.7 | 14.1 | 326 | 3393 | 0.2787 |
Mulbery | 125 | 19/3.18 | 150.9 | 15.9 | 415 | 4312 | 0.2192 |
Ash | 150 | 19/3.48 | 180.7 | 17.4 | 497 | 5164 | 0.1831 |
Elm | 175 | 19/3.76 | 211 | 18.8 | 580 | 6030 | 0.1568 |
Poplar | 200 | 37/2.87 | 239.4 | 20.09 | 659 | 8841 | 0.1385 |
– | 225 | 37/3.05 | 270.3 | 21.35 | 744 | 7724 | 0.1227 |
Sycamore | 250 | 37/3.22 | 303.2 | 22.54 | 835 | 8664 | 0.1093 |
Upas | 300 | 37/3.53 | 362.1 | 24.71 | 997 | 10350 | 0.09156 |
Walnut | 350 | 37/3.81 | 421.8 | 26.67 | 1162 | 12053 | 0.0786 |
Yew | 400 | 37/4.06 | 479 | 28.42 | 1319 | 13685 | 0.06921 |
Totara | 425 | 37/4.14 | 498.1 | 28.98 | 1372 | 14233 | 0.06656 |
Rubus | 500 | 61/3.50 | 586.9 | 31.5 | 1620 | 16771 | 0.05662 |
Araucaria | 700 | 61/4.14 | 821.1 | 37.26 | 2266 | 23450 | 0.04047 |
4.FAQ
(1).When can I get the price?
We usually quote within 6 hours after we get your inquiry. If you are very urgent to get the price, please
call us or tell us in your e-mail so that we will regard your inquiry priority.
(2).How can I get a sample to check your quality?
After price confirmation, you can require for samples to check our quality. Sample is free, but the freight
charge should be paid.
(3).How long can I expect to get the sample?
After you pay the freight charge and send us confirmed files, the samples will be ready for delivery in 3-7
days. The samples will be sent to you via express and arrive in 3~5 days. You can use your own express account orprepay us if you do not have an account.
(4).What about the lead time for mass production?
Honestly, it depends on the order quantity and the season you place the order.The best record we keep is
delivering 10 kilometers cable within a week. Generally speaking, we suggest that you start inquiry two months
before the date you would like to get the products at your country.
We are China BS 3242 Aluminum Alloy Conductors for Overhead Power Transmission Fir manufacture and supplier,You can get more details with Email,you will get cheap price or factory price.
Get Latest Price Request a quote
Popular AAAC Conductor Products
Best Quality Lowest Price AAAC All Aluminum Alloy Conductor
German Sizes DIN48201 All Aluminum Alloy Condcutor AAAC 16mm2
Cable Amelec AAAC Conductor 54.4mm2 Aster
Overhead ACSR, AAC, AAAC, Acss/Tw, Accc, Aacsr, Acar Conductor
Overhead Conductor Stranded Bare Aluminum Alloy AAAC
AAAC Conductor All Aluminum Alloy Conductor Overhead AAAC
Popular Aluminum Alloy 6201-T81 Conductor Products
AAAC Conductor ASTM B399 Bare Aluminium Alloy 6201-T81 1000mcm
AAAC Conductor ASTM B399 Bare Aluminium Alloy 6201-T81 Anaheim
AAAC as 1531 Aluminium Alloy 6201 Jasper
Overhead ACSR, AAC, AAAC, Acss/Tw, Accc, Aacsr, Acar, Opgw Bare Conductor
BS 3242 Aluminum Alloy Conductors for Overhead Power Transmission Ash
AAAC as 1531 Aluminium Alloy 6201 Opal
Popular Aluminum Alloy Conductor AAAC Products
AAAC AS 1531 Aluminium Alloy 6201 Ruby
BS 3242 Aluminum Alloy Conductors for Overhead Power Transmission Ash
AAAC as 1531 Aluminium Alloy 6201 Diamond
AAAC Conductor ASTM B399 Bare Aluminium Alloy 6201-T81 500mcm
BS 3242 Aluminum Alloy Conductors for Overhead Power Transmission Cedar
AAAC Conductor ASTM B399 Aluminium Alloy 6201-T81 25mm2
Popular huatongcable Products
6.35/11kv Underground Single Core Copper Armored Electric Cable 70mm2
Factory Price Duplex Service Drop Cable ABC Cable 4 AWG Whippet
Stranded Conductor ABC Cable with AAC ACSR AAAC Neutral Message
ABC Cable AAC/XLPE+AAAC Shrimp
Bare Overhead Conductor Aluminum Alloy Wire for Transmsiion Line Use
Medium Voltage 3 Core Copper/Aluminum Conductor XLPE Insulated Armoured Power Cable
Tags: AAAC Conductor, Aluminum Alloy 6201-T81 Conductor, Aluminum Alloy Conductor AAAC, huatongcable