Copper Conductor PVC Insulated Power Cable
Copper Conductor PVC Insulated Power Cable image
Get Latest Price Request a quote
Quick Details
Product Details
Application:
It is used to transmit and distribute power in power transmission and distribution system of 35kV or lower. It is generally applied to the fields including power, construction, mines, metallurgy, petrochemical industry and communication in complete replace of oil immersed paper insulated power cable and in partial replace of PVC insulated power cable.
Using features:
1. Rated voltage: Uo/U: 26/35kV, 21/35kV, 12/20 kV (24 kV), 8.7/10kV, 8.7/15kV, 6/6kV, 6/10kV and 0.6/1kV.
2. No. Of core: Single-core, Two-core, Three-core, Four-core, Five-core, Six-core.
3. The highest allowed operating temperature of conductor for long-term working is 90oC. In short-circuit (Max. Long-term is no more than 5 seconds). The highest temperature for conductor is no more than 250 degree.
4. D. C. Resistance of the conductor complies with the stipulations of international standar.
5. The environment temperature should be no lower than zero degree when lay. Otherwise it should be preheated.
6. The cable is laid without horizontal drop limit. The Min. Bending radius of cables should be no smaller than 12 times of cable outer diameter.
7. Working Frequency Voltage Test:
For cable with Uo of 3.6kV or lower: 2.5Uo+2kV/5min without puncture.
For cable with Uo of 3.6Kv~18kV: 3.5Uo/5min without puncture.
For cable with Uo of 21kV and 26 kV: 2.5Uo/30min without puncture.
8. Partial Discharge Test: The discharge volume should be no more than 10PC under 1.73Uo for the cable
Packing: Export wooden drums
| 1)3.6/6(7.2)kV,3.6/6.6(7.2)kV,Three Cores,Al or Cu/XLPE/CTS/STA/PVC Armoured Power Cable | |||||||||
| No.X Nominal Cross Section of Conductor | Nominal Diameter of Conductor | Nominal Thickness of Insulation | Nominal Thickness of Copper Tape Screen | Nominal Thickness of Inner Sheath | Nominal Thickness of Steel Tape Armouring | Nominal Thickness of PVC Sheath | Approx. Overall Diameter | Approx. Weight | |
| Al Conductor | Cu Conductor | ||||||||
| No. X mm 2 | mm | mm | mm | mm | mm | mm | mm | kg/m | kg/m |
| 3 X 25 | 6 | 2.5 | 0.1 | 1.2 | 0.2 | 1.9 | 37.9 | 1.87 | 2.32 |
| 3 X 35 | 6.9 | 2.5 | 0.1 | 1.3 | 0.5 | 2 | 41.5 | 2.1 | 2.73 |
| 3 X50 | 8.2 | 2.5 | 0.1 | 1.3 | 0.5 | 2 | 44.3 | 2.37 | 3.22 |
| 3 X 70 | 9.7 | 2.5 | 0.1 | 1.4 | 0.5 | 2.1 | 47.9 | 2.77 | 4 |
| 3 X 95 | 11.3 | 2.5 | 0.1 | 1.4 | 0.5 | 2.2 | 51.6 | 3.21 | 4.91 |
| 3 X 120 | 12.8 | 2.5 | 0.1 | 1.5 | 0.5 | 2.4 | 55.4 | 3.69 | 5.84 |
| 3 X 150 | 14.2 | 2.5 | 0.1 | 1.5 | 0.5 | 2.5 | 58.6 | 4.15 | 6.85 |
| 3 X 185 | 15.9 | 2.5 | 0.1 | 1.5 | 0.5 | 2.6 | 62.5 | 4.73 | 8.11 |
| 3 X 240 | 18.3 | 2.6 | 0.1 | 1.6 | 0.5 | 2.7 | 68.5 | 5.62 | 10.05 |
| 3 X 300 | 20.4 | 2.8 | 0.1 | 1.7 | 0.5 | 2.9 | 74.5 | 6.55 | 12.11 |
| 3 X 400 | 23.2 | 3 | 0.1 | 1.9 | 0.8 | 3.2 | 83.6 | 8.78 | 15.86 |
| 3 X 500 | 26.4 | 3.2 | 0.1 | 2.1 | 0.8 | 3.4 | 93 | 10.52 | 18.85 |
| 2)6/10(12)kV,6.35/11(12)kV,,Three Cores,Al or Cu/XLPE/CTS/STA/PVC Armoured Power Cable | |||||||||
| No.X Nominal Cross Section of Conductor | Nominal Diameter of Conductor | Nominal Thickness of Insulation | Nominal Thickness of Copper Tape Screen | Nominal Thickness of Inner Sheath | Nominal Thickness of Steel Tape Armouring | Nominal Thickness of PVC Sheath | Approx. Overall Diameter | Approx. Weight | |
| Al Conductor | Cu Conductor | ||||||||
| No. X mm 2 | mm | mm | mm | mm | mm | mm | mm | kg/m | kg/m |
| 3 X 25 | 6 | 3.4 | 0.1 | 1.3 | 0.5 | 2 | 43.4 | 2.16 | 2.61 |
| 3 X 35 | 6.9 | 3.4 | 0.1 | 1.3 | 0.5 | 2 | 45.4 | 2.36 | 2.99 |
| 3 X50 | 8.2 | 3.4 | 0.1 | 1.4 | 0.5 | 2.2 | 48.8 | 2.69 | 3.54 |
| 3 X 70 | 9.7 | 3.4 | 0.1 | 1.5 | 0.5 | 2.3 | 52.4 | 3.1 | 4.33 |
| 3 X 95 | 11.3 | 3.4 | 0.1 | 1.5 | 0.5 | 2.4 | 56.1 | 3.56 | 5.26 |
| 3 X 120 | 12.8 | 3.4 | 0.1 | 1.5 | 0.5 | 2.5 | 59.5 | 4.04 | 6.19 |
| 3 X 150 | 14.2 | 3.4 | 0.1 | 1.5 | 0.5 | 2.6 | 62.7 | 4.49 | 7.19 |
| 3 X 185 | 15.9 | 3.4 | 0.1 | 1.6 | 0.5 | 2.6 | 66.6 | 5.12 | 8.49 |
| 3 X 240 | 18.3 | 3.4 | 0.1 | 1.7 | 0.5 | 2.8 | 72.4 | 5.99 | 10.42 |
| 3 X 300 | 20.4 | 3.4 | 0.1 | 1.8 | 0.5 | 3 | 77.5 | 6.86 | 12.42 |
| 3 X 400 | 23.2 | 3.4 | 0.1 | 1.9 | 0.8 | 3.2 | 85.4 | 8.97 | 16.05 |
| 3 X 500 | 26.4 | 3.4 | 0.1 | 2 | 0.8 | 3.4 | 93.7 | 10.65 | 19.5 |
| 3)8.7/10(15)kV,Three Cores,Al or Cu/XLPE/CTS/STA/PVC Armoured Power Cable | |||||||||
| No.X Nominal Cross Section of Conductor | Nominal Diameter of Conductor | Nominal Thickness of Insulation | Nominal Thickness of Copper Tape Screen | Nominal Thickness of Inner Sheath | Nominal Thickness of Steel Tape Armouring | Nominal Thickness of PVC Sheath | Approx. Overall Diameter | Approx. Weight | |
| Al Conductor | Cu Conductor | ||||||||
| No. X mm 2 | mm | mm | mm | mm | mm | mm | mm | kg/m | kg/m |
| 3 X 25 | 6 | 4.5 | 0.1 | 1.4 | 0.5 | 2.1 | 48.6 | 2.53 | 2.98 |
| 3 X 35 | 6.9 | 4.5 | 0.1 | 1.4 | 0.5 | 2.2 | 50.7 | 2.76 | 3.39 |
| 3 X50 | 8.2 | 4.5 | 0.1 | 1.5 | 0.5 | 2.3 | 53.9 | 3.1 | 3.95 |
| 3 X 70 | 9.7 | 4.5 | 0.1 | 1.5 | 0.5 | 2.4 | 57.4 | 3.51 | 4.74 |
| 3 X 95 | 11.3 | 4.5 | 0.1 | 1.5 | 0.5 | 2.6 | 61.2 | 4.05 | 5.75 |
| 3 X 120 | 12.8 | 4.5 | 0.1 | 1.6 | 0.5 | 2.6 | 64.7 | 4.56 | 6.72 |
| 3 X 150 | 14.2 | 4.5 | 0.1 | 1.6 | 0.5 | 2.7 | 67.9 | 5.04 | 7.74 |
| 3 X 185 | 15.9 | 4.5 | 0.1 | 1.7 | 0.5 | 2.8 | 71.9 | 5.66 | 9.04 |
| 3 X 240 | 18.3 | 4.5 | 0.1 | 1.8 | 0.5 | 3 | 77.7 | 6.56 | 11 |
| 3 X 300 | 20.4 | 4.5 | 0.1 | 1.9 | 0.8 | 3.2 | 84.1 | 8.39 | 13.96 |
| 3 X 400 | 23.2 | 4.5 | 0.1 | 2 | 0.8 | 3.3 | 90.5 | 9.71 | 16.79 |
| 3 X 500 | 26.4 | 4.5 | 0.1 | 2.1 | 0.8 | 3.5 | 98.8 | 11.45 | 20.57 |
| 4)12/20(24)kV, 12.7/22(24)kV,Three Cores,Al or Cu/XLPE/CTS/STA/PVC Armoured Power Cable | |||||||||
| No.X Nominal Cross Section of Conductor | Nominal Diameter of Conductor | Nominal Thickness of Insulation | Nominal Thickness of Copper Tape Screen | Nominal Thickness of Inner Sheath | Nominal Thickness of Steel Tape Armouring | Nominal Thickness of PVC Sheath | Approx. Overall Diameter | Approx. Weight | |
| Al Conductor | Cu Conductor | ||||||||
| No. X mm 2 | mm | mm | mm | mm | mm | mm | mm | kg/m | kg/m |
| 3 X 25 | |||||||||
| 3 X 35 | 6.9 | 5.5 | 0.1 | 1.5 | 0.5 | 2.4 | 55.6 | 3.14 | 3.77 |
| 3 X50 | 8.2 | 5.5 | 0.1 | 1.5 | 0.5 | 2.5 | 58.6 | 3.49 | 4.34 |
| 3 X 70 | 9.7 | 5.5 | 0.1 | 1.5 | 0.5 | 2.6 | 62.1 | 3.93 | 5.16 |
| 3 X 95 | 11.3 | 5.5 | 0.1 | 1.6 | 0.5 | 2.6 | 65.7 | 4.46 | 6.16 |
| 3 X 120 | 12.8 | 5.5 | 0.1 | 1.7 | 0.5 | 2.7 | 69.4 | 5 | 7.15 |
| 3 X 150 | 14.2 | 5.5 | 0.1 | 1.7 | 0.5 | 2.8 | 72.6 | 5.49 | 8.19 |
| 3 X 185 | 15.9 | 5.5 | 0.1 | 1.8 | 0.5 | 3 | 76.9 | 6.16 | 9.53 |
| 3 X 240 | 18.3 | 5.5 | 0.1 | 1.9 | 0.8 | 3.2 | 83.9 | 7.87 | 12.31 |
| 3 X 300 | 20.4 | 5.5 | 0.1 | 2 | 0.8 | 3.2 | 88.6 | 8.96 | 14.52 |
| 3 X 400 | 23.2 | 5.5 | 0.1 | 2.1 | 0.8 | 3.5 | 95.4 | 10.35 | 17.43 |
| 3 X 500 | 26.4 | 5.5 | 0.1 | 2.2 | 0.8 | 3.7 | 103.7 | 12.45 | 20.23 |
| 5)18/30(36)kV,19/33(36)kV,Three Cores,Al or Cu/XLPE/CTS/STA/PVC Armoured Power Cable | |||||||||
| No.X Nominal Cross Section of Conductor | Nominal Diameter of Conductor | Nominal Thickness of Insulation | Nominal Thickness of Copper Tape Screen | Nominal Thickness of Inner Sheath | Nominal Thickness of Steel Tape Armouring | Nominal Thickness of PVC Sheath | Approx. Overall Diameter | Approx. Weight | |
| Al Conductor | Cu Conductor | ||||||||
| No. X mm 2 | mm | mm | mm | mm | mm | mm | mm | kg/m | kg/m |
| 3 X 25 | |||||||||
| 3 X 35 | |||||||||
| 3 X50 | 8.2 | 8 | 0.1 | 1.7 | 0.5 | 2.8 | 70.4 | 4.56 | 5.41 |
| 3 X 70 | 9.7 | 8 | 0.1 | 1.7 | 0.5 | 2.9 | 73.9 | 5.04 | 6.26 |
| 3 X 95 | 11.3 | 8 | 0.1 | 1.8 | 0.5 | 3 | 77.7 | 5.62 | 7.32 |
| 3 X 120 | 12.8 | 8 | 0.1 | 1.9 | 0.8 | 3.2 | 82.8 | 6.99 | 9.15 |
| 3 X 150 | 14.2 | 8 | 0.1 | 1.9 | 0.8 | 3.2 | 85.8 | 7.56 | 10.26 |
| 3 X 185 | 15.9 | 8 | 0.1 | 2 | 0.8 | 3.3 | 89.9 | 8.3 | 11.67 |
| 3 X 240 | 18.3 | 8 | 0.1 | 2.1 | 0.8 | 3.5 | 95.7 | 9.36 | 13.79 |
| 3 X 300 | 20.4 | 8 | 0.1 | 2.2 | 0.8 | 3.6 | 100.6 | 10.51 | 16.07 |
| 3 X 400 | 23.2 | 8 | 0.1 | 2.3 | 0.8 | 3.8 | 107.2 | 11.99 | 19.07 |
| 3 X 500 | 26.4 | 8 | 0.1 | 2.4 | 0.8 | 4 | 120.1 | 14.15 | 23.85 |
Workshop
Shipment
QA&QC
CUSTOMER VISIT
FAQ
1. How many years has Henan Jiapu Cable Group been in production?
Founded in October 1998 by Mr. Gu, our facility has three separate manufacturing workshops within its 100,000-sq.-ft. building. In 2012, we operates in a new 666,000 sq. foot state-of-the-art facility in Xiaodian Industry Park.,Xinxiang, Henan ,China
2. What kinds of products does Jiapu Cable manufacture?
1)Bare Conductor ,such as AAC,AAAC,ACSR,ACAR,AACSR,ACSR/AW and so on;
2)Aerial Bundled Cable (1kV-35kV ),such as Duplex,Triplex,Quadruplex Drop Wires and so on;
3)PVC Insulated (Flexible ) Wire ;
4) PVC Insulated and Sheathed (Armoured) Power Cable;
5)Low, Medium, High Voltage (1kV-220kV) XLPE Insulated (Armoured) Power Cable;
6)Welding Cable, Control Cable, Concentric Cable, Rubber Sheathed Cable and so on;
3. What kind of certifications do you have?
SABS, CE, ISO9001-2000, SGS
4.Which markets do you involve mainly in?
Our products have been exported mainly to Africa, Middle East, South-east Asia, South America,Central America,North America, Europe ,Australia, etc.
5. Which standards do you comply with when you produce the electrical wires and cables ?
We are able to produce electrical wires and cables based on GB, JB, IEC, BS, DIN, ASTM, JIS, NF, AS/NZS, CSA, etc. Meanwhile, we can design and manufacture the cables according to the samples and technical specification the customer supply.
6. What is the min.order quantity ?
It depends on the type and size of electrical wires and cables. For some small electrical wires, 100 meters can be accepted .But for the power cables with medium or high voltage, that should comply with the property of installed equipments. Anyhow,we will try our best to solve the problem and meet with the requirement If you have special request.
7. What is the production capacity per week or per month ?
For the bare conductor, we can finish 3000 tons within one month. For power cables, that depends on the type and size. The total output value per month is approx. USD3,000,000.00 for insulated aluminum cables and that is approx. USD8,000,000.00 for insulated copper cables.
8. Do you supply the customers with installation service in foreign country ?We don’t have professional installation teams in foreign country.But if that is necessary, we will recommend our partners to cooperate with you.
We are China Copper Conductor PVC Insulated Power Cable manufacture and supplier,You can get more details with Email,you will get cheap price or factory price.
Get Latest Price Request a quote
Popular Cable Products
Overhead Insulated ABC Cable Aerial Bundled Cable Aluminum Conductor
11kv 1 Core 2 Core 3 Core Copper Power Cable
25kv XLPE Power Cable 3 Core Copper Conductor XLPE Insulated Armored Power Cable
High Voltage Al/XLPE 11kv ABC Cable, Malemute
Cable Manufacturer Overhead Service Aerial Bundled Cable ABC Cable 33kv
Popular jpcable99 Products
High Quality PVC Insulated Wire
Good Performance AAAC Conductor (All Aluminum Alloy Conductor) for Sale
AAAC All Aluminium Alloy Conductor Bare Conductor
Las Especificaciones Tecnicas Del Conductor AAAC 120mm2
High Quality 0.3-0.6kv Low Voltage Electrical Wire
Single Core PVC Insulated Copper Wire
Popular PVC Cable Products
Hot Sale Copper PVC Insulated Electrical Cables and Wires
4X35mm2 4X95mm2 XLPE Armoured Copper Cable for Construction
Low voltage Control/Instrumentation CY LSZH Cable 19X2.5mm2 Flexible CU/XLPE/TCWB/LSZH
Good Quality Safety 2.5mm Electric Cable Flexible Wire
3 Core Copper Cable Flexible Electrical Wire
Flame Retardant PVC Insulated Power Transmission Cable
Popular PVC Insulated Cable Products
450/750V H07V-U Copper Conductor PVC Insulated PVC Sheath Electric Wire
PVC Insulated and PVC Sheated Wire or Cable
Cu/PVC/Sta /PVC Power Cable 4*50mm2
600 / 1000V Aluminum Conductor PVC Insulated PVC Sheathed Electrical Power Cable
Control Cable Multicore 7 Cores Cable PVC/PE/XLPE Insulation Electric Power Cable Wires
450/750V PVC Insulated Cable Used as Connecting Cables
Tags: Cable, jpcable99, PVC Cable, PVC Insulated Cable