Design Expulsion Fuse (PRW-15)

China 
                        Design Expulsion Fuse (PRW-15)
                      manufacture and supplier

Design Expulsion Fuse (PRW-15) image

Get Latest Price Request a quote

Quick Details

Design Expulsion Fuse (PRW-15)

PRW-15

IEC IEEE

Fuse Link

T K

Circle

High Voltage

Distribution

High

OEIpower

Cartons Pallets Wooden Case

IEC282-2 IEEEc37-41

China Nanyang

85351000

Product Details


DESIGN EXPULSION FUSEGEAR

 
The complete assemblies shall be rated 105°C for normal circuit conditions.  Further they shall meet the following electrical test requirements.

A.  Performance Characteristics
 
1.     Voltage
 
a. BIL:  170kV, 1.2 x 50 microsecond wave.
 
b.        AC Withstand: 70kV, 50Hz, 1 minute; dry and wet.
 
2.     Current
 
a. Continuous Operation:  100A minimum
 
b.        Rated interrupting current of Expulsion fusegear:
 
Prospective RMS symmetrical amperes: 4000A, i.e. 6 tests of test Series No. 1 from total series of 16 tests per Table IVA IEC 602822 at 4,000 amperes RMS symmetrical.
 
3.     Low Current Interruption
 
The Expulsion fusegear shall meet the requirements of IEC 602822 Clause 13, and shall be tested to interrupt down to 15 amperes applied to a 6K fuse link.
 
4.     Fuse Link Range and Class
 
The Expulsion fusegear shall be suitable in all respects for fuse links within the range 1 to 100 amps per IEC and NEMA standards.
 
B.  Interchangeability
 
The fuse holder (tube) of a fuse isolator shall be dimensionally compatible with a universal fuse link of corresponding rating and with a universal fuse tube.(e.g. fuse links manufactured by Hubbell Power Systems and S&C Electric Company of North America)
 
C.  Insulators
 
The insulators shall be of solid glazed porcelain type and be birdproof.  They shall meet the electrical and mechanical characteristics as shown in IEC Standard Publication 60383.  Insulators shall be based on rated voltage of 33kV.
 

 

1.        The support insulators must withstand dry and wet test voltages at 50Hz, sustained for one minute of not less than:
 
a.        70kV to earth and between poles and
b.        80kV across the isolating distances, re IEC 600602, Section 3
 
The Supplier shall also give the following information in the schedule.
 
c.        The minimum dry flashover voltage value
d. The minimum wet flashover voltage value
e. The puncture voltage at 50Hz.
 
2.     Radio Interference Voltage
 
The maximum radio interference voltage shall be 250 microvolts measured in accordance with IEC 60437.
 
D.  Clearance
 
The Supplier shall give the following information in the schedule:
 
1.     Minimum phase/phase clearance
 
2.     Minimum phase/earth clearance.
 
E.   Creepage Distance
 
Minimum leakage distance to ground shall be 900mm.
 
F.   Construction
 
1.     Main assembly
 
a.        The main assembly may be mounted on a 2 insulator channel base arrangement.  The insulators shall be porcelain and bird proof.
 
Top and bottom contact subassemblies and mounting fitting shall be potted into the porcelain insulators.  The upper fixed contacts shall positively latch.  (See Figures 1 and 2).
 
b.        All contacts shall be designed to give permanent current carrying capacity at rated current after exposure to marine climate for up to 20 years.  All current carrying components shall be of copper or copper alloy.  Terminals shall be suitable for conductor up to 265mm2 Al/Cu.
 

c.        Contacts shall be heavily silver clad on each side of each interface.  Embossed surfaces with wiping action are preferred.
 
d.        Ferrous components shall be stainless steel or galvanised.  The Supplier shall state weight/thickness of zinc coating on the attached Schedule.
 
e.        The Expulsion Fusegear shall be provided with a permanently fitted loadbreak device.                      
                                                             
f.         The assembly shall be designed such that the fuse tube can be closed without using undue care even when the closing force is applied from an angle.
 
g.        The angle of fuse tube relative to the vertical shall be filled in on the attached schedule.
 
h.        The insulator shall preferably be marked with the rated voltage and the minimum basic insulation level
 
IEEE/NEMA brackets shall be provided.
 
2.     Fuse Tube Assembly
 
a.        The fuse tube shall be capable of accepting IEC/NEMA fuse links up to a maximum continuous current rating of 100 amperes.
 
b.        The toggle mechanism shall provide locking action to protect the fuse link from shock.  A spring assisted flipper shall assist arc interruption by withdrawal of the fuse tail.
 
c.        The fuse tube cap may be the expendable type.
 
d.        A lifting eye shall be provided on the fuse tube and designed for use with hookstick.
 
e.        The fuse tube shall be permanently marked with the following:  Supplier/Manufacturer; model; maximum continuous current rating; rated maximum voltage phase to phase; rated symmetrical amperes interrupting per IEC requirements.
 
G.  Operating Gear
 
For Single Pole Units operation will be by means of the Purchaser’s standard operating hot-stick, and loadbreak tool to ensure existing practice can continue.      

We are China Design Expulsion Fuse (PRW-15) manufacture and supplier,You can get more details with Email,you will get cheap price or factory price.

Get Latest Price Request a quote

Popular Chave Fusivel Polimerica Products

Fuse Link, 30 AMP - K

Insulator 500kv 12.5kn_DSC3521--1

_DSC3521--1

Popular Interrupter Products

Porcelain Fuse Cutout ISO9001

Switch Disconnector Fuse Holder, 18 Kv - 200 AMP, Without Arc Chute

Fuse Cutout 36kv 200A

Polymer High-Voltge Expulsion Type Distribution Type Fuses

Switch Disconnector Fuse Holder, 27 Kv - 200 AMP, Without Arc Chute

Terminal Connectors Bolted Type, Type SL, Group C

Popular jgtrade1 Products

Gw4-126 Outdoor AC Disconnector Switch Manufacturer Horizontal Opening

Stepping Board (white palm rope)

OEM Accept High Voltage Outdoor Disconnect Switch Disconnector

Parallel Groove Clamp APG-C3

Polyester Lined Glove Coated with PU (black)

Various Types of Transformers Beams

Popular Loadbreak Cutout Products

Fixed Enclosed Switchgear

Surge Arresters 30kv Mounted on Crossarm

Fully Sealed and Fully Insulated Inflatable Ring Network Switchgear

Expulsion Fuses

Terminal Connectors Bolted Type, Type SL, Group C

Medium Voltage Fuse Cutouts

Tags: , , ,

FAST AND RELIABLE SERVICE FOR YOUR PROJECT

Contact our trained experts today to find your perfect power solution.

ASK A QUESTION