Disconnecor Switch 33kv

China 
                        Disconnecor Switch 33kv
                      manufacture and supplier

Disconnecor Switch 33kv image

Get Latest Price Request a quote

Quick Details

Disconnecor Switch 33kv

IST-33/630

Oei Power

IEC IEEE

Manual

Ist

Turn the Horizontal

Three

Single Ground

Three Pole

Horizontal Rotary Type

Grounding

Manual

Outdoor High-voltage

Three-column Disconnector

High-voltage

OEIpower

Cartons Pallets Wooden Case

IEC IEEE

China Nanyang

8535309000

Product Details


 
Type IST off-load switchs are suitable for use in tropical zone, with a maximum ambient temperature of approximately 40
degrees Centigrade and an average temperature of approximately 28 degrees Centigrade with high humidity and heavy rainfall.
The preferred operational altitude is up to 1800 m above sea level.

S.No DESCRIPTION UNITS BIDDER OFFERED VALUE
1. Rated Voltage KV 12 KV
2. Frequency Hz 50 Hz
3 Rated continuous current A 630
4 Impulse withstand voltage to ground KV 95
5 Impulse withstand voltage across gaps KV 110
6 Dry one-minute power frequency withstand voltage to ground KV 35
 
7 Dry one minute power frequency withstand voltage across gap KV 45
8 Wet one minute power frequency withstand voltage to ground      KV 30
9 Limits of radio interference 10KV  and 1000 K.C/Sec   250  uV
10 Temperature rise at rated current (max.)        30oC at 50oC ambient
11 Dimensions and mechanical ,Electrical
values Of Polymer Insulator
   
12 Leaking distance  mm      508 (minimum)
13 Dry arcing distance    mm 210 (minimum)
14 Cantilever strength     kg 400 
15 Tensile strength kg 1000
16 Compressive strength  kg 5400
17 Tensile proof test load      kg 700
18 Dry power frequency flashover      KV 85 
19 Wet power frequency flashover      KV 55 
20 Dry one-minute power frequency withstand KV 70
21 Wet one-minute power frequency withstand KV 45
22 Impulse flash over positive      KV 115 
23 Impulse flashover negative      KV 140
24 Power frequency puncture voltage  KV 150  

1.0                       Scope & applications
 
1.1      The  pole-mounted Line Sectionalizer / Disconnector are open type, air insulated switch. The make and Break switching operation are performed at "zero system voltage." in "OFF LOAD"   condition, only for the isolation of the faulty circuits for the protection of 11 KV Distribution lines,   Transformers, Capacitors, Cables,  etc, from high transient lightening and surge Voltages.
 
1.2      The assembly of Gang operated three phase Pole Mounted Line Sectionalizer are supplied as a      single unit with single pole mounting arrangement. The unit are facilitate the installation of the   assembly on both sides (left or right) of the pole to operate and install the operating handle in      accordance with site conditions.    
 
2.0      System / conditions
 
i)                   Nominal system voltage                                    11 KV
ii)                 Highest system voltage                                     12 KV
iii)               Highest voltage for equipment                                 12 KV
iv)               BIL                                                     95 KV
v)                 Phases                                                 3 
vi)               Frequency                                           50 Hz
vii)             Rated Short circuit level of the system                     18 KA (1 second)
viii)           System Earthing: 11 KV Star point / Neutral solidly grounded at Pole / PMT:
 
3.0      Climatic conditions
 
i)                   Maximum ambient air temperature                          50oC
ii)                 Maximum daily average temperature                   45oC
iii)               Minimum ambient air temperature                           0oC
iv)               Maximum sun temperature on exposed Horizontal surface   60oC
v)                 Highest solar radiation intensity                               1000 W/m2
vi)               Maximum relative humidity                              95 %
vii)             Annual rain fall:                                                              20 to 60 mm in 2 to 4                                                           showers
viii)           Altitude                                                       Sea-level
ix)               Location                                                       Sea Coast (Interior is                                                   Semi-Desert).
x)                 Pollution                                           Severe marine pollution on                                                account of windblown                                                            sand and dust with salt                                                       content and salt laden                                                             spray and mist. Washing                                                 action by rain is negligible,                                                as rainfall is scanty.
 
4.0     Ratings and characteristics for line Sectionalizer
 
4.1      The Gang Operated pole mounted 11 kv Line Sectionalizer have the following ratings and characteristics based on 50 deg. C ambient temperature:
 
i)                               Nominal voltage                                               11 KV
ii)                             Maximum design voltage                                                 12 KV
iii)                           Rated continuous current                                              630  Amps
iv)                           Impulse withstand voltage to ground                              95 KV
v)                             Impulse withstand voltage across gaps                              110 KV
vi)                           Dry one-minute power frequency withstand voltage to ground       35 KV
vii)                         Dry one minute power frequency withstand voltage across gap          45 KV
viii)  Wet one minute power frequency withstand voltage to ground        30 KV
ix)                           Limits of radio interference 10KV  and 1000 K.C/Sec                250  uV
x)                             Temperature rise at rated current (max.)                                      30oC at 50oC ambient
 
 
4.2      Polymer insulator
 
The mechanical and electrical characteristics of the Polymeric insulator are as under:
 
 
 
 
 
4.2.1   Dimensions and mechanical values
 
i)                   Leaking distance                                        508 mm  (minimum)
ii)                 Dry arcing distance                                    210 mm  (minimum)
iii)               Cantilever strength                                     400  kg
iv)               Tensile strength                                          1000 kg
v)                 Compressive strength                                        5400 kg
vi)               Tensile proof test load                                      700  kg
                
4.2.2   Electrical values
 
i)                   Dry power frequency flashover                               85  KV
ii)                 Wet power frequency flashover                              55  KV
iii)               Dry one-minute power frequency withstand                   70  KV
iv)               Wet one-minute power frequency withstand                  45  KV
v)                 Impulse flash over positive                                   115  KV
vi)               Impulse flashover negative                               140  KV
vii)             Power frequency puncture voltage                          150  KV
 
 
5.0      Constructional features
The three pole disconnectors are mainly designed for a vertical mounting. The following elements could be changed or incorporated:
– Fuseholder.
– Earthing connection with locking device to prevent the connection to earth when the disconnector is closed or to close the device when the earth is connected.
– The earthing disconnector can be placed in the entrance or exit of the main switch.
– The earth disconnector is operating by means of an independent control.
– The operating axis could be placed at left or  right side.
– The operating axis could be extending until 250, 420,500, 750 or 1000mm, these extensions includes a support to avoid it bend down.
– The outdoor units are provided with different drills to permit the direct fixing to a post or to a frame previously fix to a post.
1.0                       Scope & applications
 
1.1      The  pole-mounted Line Sectionalizer / Disconnector are open type, air insulated switch. The make and Break switching operation are performed at "zero system voltage." in "OFF LOAD"   condition, only for the isolation of the faulty circuits for the protection of 11 KV Distribution lines,   Transformers, Capacitors, Cables,  etc, from high transient lightening and surge Voltages.
 
1.2      The assembly of Gang operated three phase Pole Mounted Line Sectionalizer are supplied as a      single unit with single pole mounting arrangement. The unit are facilitate the installation of the   assembly on both sides (left or right) of the pole to operate and install the operating handle in      accordance with site conditions.    
 
2.0      System / conditions
 
i)                   Nominal system voltage                                    11 KV
ii)                 Highest system voltage                                     12 KV
iii)               Highest voltage for equipment                                 12 KV
iv)               BIL                                                     95 KV
v)                 Phases                                                 3 
vi)               Frequency                                           50 Hz
vii)             Rated Short circuit level of the system                     18 KA (1 second)
viii)           System Earthing: 11 KV Star point / Neutral solidly grounded at Pole / PMT:
 
3.0      Climatic conditions
 
i)                   Maximum ambient air temperature                          50oC
ii)                 Maximum daily average temperature                   45oC
iii)               Minimum ambient air temperature                           0oC
iv)               Maximum sun temperature on exposed Horizontal surface   60oC
v)                 Highest solar radiation intensity                               1000 W/m2
vi)               Maximum relative humidity                              95 %
vii)             Annual rain fall:                                                              20 to 60 mm in 2 to 4                                                           showers
viii)           Altitude                                                       Sea-level
ix)               Location                                                       Sea Coast (Interior is                                                   Semi-Desert).
x)                 Pollution                                           Severe marine pollution on                                                account of windblown                                                            sand and dust with salt                                                       content and salt laden                                                             spray and mist. Washing                                                 action by rain is negligible,                                                as rainfall is scanty.
 
4.0     Ratings and characteristics for line Sectionalizer
 
4.1      The Gang Operated pole mounted 11 kv Line Sectionalizer have the following ratings and characteristics based on 50 deg. C ambient temperature:
 
i)                               Nominal voltage                                               11 KV
ii)                             Maximum design voltage                                                 12 KV
iii)                           Rated continuous current                                              630  Amps
iv)                           Impulse withstand voltage to ground                              95 KV
v)                             Impulse withstand voltage across gaps                              110 KV
vi)                           Dry one-minute power frequency withstand voltage to ground       35 KV
vii)                         Dry one minute power frequency withstand voltage across gap          45 KV
viii)  Wet one minute power frequency withstand voltage to ground        30 KV
ix)                           Limits of radio interference 10KV  and 1000 K.C/Sec                250  uV
x)                             Temperature rise at rated current (max.)                                      30oC at 50oC ambient
 
 
4.2      Polymer insulator
 
The mechanical and electrical characteristics of the Polymeric insulator are as under:
 
 
 
 
 
4.2.1   Dimensions and mechanical values
 
i)                   Leaking distance                                        508 mm  (minimum)
ii)                 Dry arcing distance                                    210 mm  (minimum)
iii)               Cantilever strength                                     400  kg
iv)               Tensile strength                                          1000 kg
v)                 Compressive strength                                        5400 kg
vi)               Tensile proof test load                                      700  kg
                
4.2.2   Electrical values
 
i)                   Dry power frequency flashover                               85  KV
ii)                 Wet power frequency flashover                              55  KV
iii)               Dry one-minute power frequency withstand                   70  KV
iv)               Wet one-minute power frequency withstand                  45  KV
v)                 Impulse flash over positive                                   115  KV
vi)               Impulse flashover negative                               140  KV
vii)             Power frequency puncture voltage                          150  KV
 
 
5.0      Constructional features
The three pole disconnectors are mainly designed for a vertical mounting. The following elements could be changed or incorporated:
– Fuseholder.
– Earthing connection with locking device to prevent the connection to earth when the disconnector is closed or to close the device when the earth is connected.
– The earthing disconnector can be placed in the entrance or exit of the main switch.
– The earth disconnector is operating by means of an independent control.
– The operating axis could be placed at left or  right side.
– The operating axis could be extending until 250, 420,500, 750 or 1000mm, these extensions includes a support to avoid it bend down.
– The outdoor units are provided with different drills to permit the direct fixing to a post or to a frame previously fix to a post.

We are China Disconnecor Switch 33kv manufacture and supplier,You can get more details with Email,you will get cheap price or factory price.

Get Latest Price Request a quote

Popular Disconnector Products

Three Phase High Voltage Switch Isolators

China Factory Gw4 Series Outdoor AC Isolating Switch

33kv High Voltage Isolating Switch Gang Insulator Porcelain Cutout Fuse Ceramic Dropout Fuse Fuse Cutout Gang Insulator Isolating Switch 11kv15kv 22kv 36kv

Gw9 Outdoor High Voltage Pole Mounted Disconnector Switch Isolating Switch

by Pass Switch

Manufacturer Supply Disconnector Switch 132kv Isolator

Popular Disconnector Switch Products

Grounding Switch 145 Kv, 31.5 Ka

Gw4 Outdoor Hv Disconnector/Disconnecting Switch

12kv~36kv Load Isolators

Load Break Switch 15kv Rh-B

Preformed Guy Grip 7/8 Swg Dead Ends

Strain Composite Epoxy Resin Polymer Long Rod Insulators

Popular jgtrade1 Products

Hy10W-30, 30kv10ka Surge Arrester

Square Flat Washer

Factory Price High Voltage AC 12kv Outdoor Disconnect Switch

High Quality 11kv 33kv Outdoor High Voltage Switches Polymer Fuse Cutout

PP Clear/Anti-Fog

Insulating Clamp

Popular Switch Products

Gw4 Series Outdoor AC Isolating Switch

End-Caps for Tubular Bus-Bar Type Mgf

Indoor Use High Voltage Load Switch and Fuse Combined Switch

Sgld Series 380V Automatic Change-Over Switch (ATS) From 100A to 3200A

Low-Voltage Fuse Switch for Cable Distribution and Power Supply Systems

Sgl 160A Solar System Electric Manual Changeover Switch

Tags: , , ,

FAST AND RELIABLE SERVICE FOR YOUR PROJECT

Contact our trained experts today to find your perfect power solution.

ASK A QUESTION