High Quality 33kv ABC Cable for Overhead Use
High Quality 33kv ABC Cable for Overhead Use image
Get Latest Price Request a quote
Quick Details
Product Details
33 KV ABC Cable according to GB, IEC, ASTM, BS, DIN standards or customer’s requirements. High Quality with Competitive price
ABC Aluminium 3 Core Type B (Unarmoured) Steel Catenary
Aluminum conductor or coper conductor, PVC or PE or XLPE insulatedd cable is used for overhead electrictity transmission
MV aerial bundled cable
CONSTRUCTION
Conductor
Stranded compacted circular copper or aluminium conductors.
All internal interstices of trie conductor rilled with water blocking compound which is specified to prevent ingress of water through conductor during storage, handling, installation and operating of the cable.
Conductor Screen
Extruded Semi-conducting compound. Minimum thickness 0.5 mm and the maximum volume resistivity of 5000 ohm-cn
At 20° C and 25000 ohm-cm at 90° C.
Insulation
Extruded XLPE with high degree of cross-linking, free from contaminants, air voids and heat resistant by dry cured process.
Nominal Voltage:
3.6/6 ( 7.2 ) kV
6/10 ( 12 ) kV
8.7/15 ( 17.5 ) kV
12/20 ( 24 ) kV
18/30 ( 36 ) kV
Insulation Screen
Extruded Semi-conducting compound. Minimum thickness 0.5 mm and the maximum volume resistivity of 5000 ohm-cm at 20° C and 25000 ohm-cm at WC The screen is tightly fitted to insulation to exdude all air voids and can be easily hand stripped on site.
Conduction Water Blocking Layer
Semi-conductive water blocking tape provided over the insulation screen which will swell up under the influence ofmoisture or water.
Metallic Screen
Copper wires applied over the conducting water blocking layer. Minimum cross section of concentric conductor as shown in table 2. Copper tape with minimum thickness 0.1 mm and maximum 0.3mm applied over copper wires.
Water Blocking Layer
Non-conducting water blocking tape provided the metallic screen which will swellup under ihe influence of moisture or water.
Inner Sheath
Extruded black PVC, capable for operating continuously maximum temperature of the cable. Thickness of inner sheath as shown in table 3.
Outer Sheath
Extruded red PVC, suitable tar exposure to sun-light or other local atmospheric environments and for the operating temperature of the cable.
Specification:
(1)Self-supporting
| Phase | Phase | Phase | Approx.Overall Diameter | Max. D.C. Resistance of Conductor at 20ºC | |||
| AAC+UV-XLPE | Compact Conductor | UV-XLPE Insulation | |||||
| No.X Normal Cross Section of Cores | No.of Al Wires | Overall Diameter | Normal Thickness | Min. | Diameter | ||
| No. X mm2 | – | mm | mm | mm | mm | mm | ohm/km |
| 1 X 10 | 7 | 4.05 | 1.0 | 0.8 | 6.05 | 6.05 | 3.08 |
| 1 X 16 | 7 | 4.8 | 1.2 | 0.98 | 7.2 | 7.20 | 1.91 |
| 1 X 25 | 7 | 6 | 1.2 | 0.98 | 8.4 | 8.40 | 1.20 |
| 1 X 35 | 7 | 7.0 | 1.4 | 1.16 | 9.8 | 9.80 | 0.868 |
| 1 X 50 | 7 | 8.3 | 1.4 | 1.16 | 11.1 | 11.10 | 0.641 |
| 1 X 70 | 19 | 9.8 | 1.4 | 1.16 | 12.6 | 12.60 | 0.443 |
| 1 X 95 | 19 | 11.6 | 1.6 | 1.34 | 14.8 | 14.80 | 0.320 |
| 1 X 120 | 19 | 13 | 1.6 | 1.34 | 16.2 | 16.20 | 0.253 |
| 1 X 150 | 19 | 14.6 | 1.8 | 1.52 | 18.2 | 18.20 | 0.206 |
| 1 X 185 | 36 | 16.2 | 2.0 | 1.70 | 20.2 | 20.20 | 0.164 |
| 1 X 240 | 36 | 18.4 | 2.2 | 1.88 | 22.8 | 22.80 | 0.125 |
| 2 X 10 | 7 | 4.05 | 1.0 | 0.8 | 6.05 | 12.10 | 3.08 |
| 2 X 16 | 7 | 4.8 | 1.2 | 0.98 | 7.2 | 14.40 | 1.91 |
| 2 X 25 | 7 | 6 | 1.2 | 0.98 | 8.4 | 16.80 | 1.20 |
| 2 X 35 | 7 | 7.0 | 1.4 | 1.16 | 9.8 | 19.60 | 0.868 |
| 2 X 50 | 7 | 8.3 | 1.4 | 1.16 | 11.1 | 22.20 | 0.641 |
| 2 X 70 | 19 | 9.8 | 1.4 | 1.16 | 12.6 | 25.20 | 0.443 |
| 2 X 95 | 19 | 11.6 | 1.6 | 1.34 | 14.8 | 29.60 | 0.320 |
| 2 X 120 | 19 | 13 | 1.6 | 1.34 | 16.2 | 32.40 | 0.253 |
| 2 X 150 | 19 | 14.6 | 1.8 | 1.52 | 18.2 | 36.40 | 0.206 |
| 2 X 185 | 36 | 16.2 | 2.0 | 1.70 | 20.2 | 40.40 | 0.164 |
| 2 X 240 | 36 | 18.4 | 2.2 | 1.88 | 22.8 | 45.60 | 0.125 |
| 3 X 10 | 7 | 4.05 | 1.0 | 0.8 | 6.05 | 13.07 | 3.08 |
| 3 X 16 | 7 | 4.8 | 1.2 | 0.98 | 7.2 | 15.55 | 1.91 |
| 3 X 25 | 7 | 6 | 1.2 | 0.98 | 8.4 | 18.14 | 1.20 |
| 3 X 35 | 7 | 7.0 | 1.4 | 1.16 | 9.8 | 21.17 | 0.868 |
| 3 X 50 | 7 | 8.3 | 1.4 | 1.16 | 11.1 | 23.98 | 0.641 |
| 3 X 70 | 19 | 9.8 | 1.4 | 1.16 | 12.6 | 27.22 | 0.443 |
| 3 X 95 | 19 | 11.6 | 1.6 | 1.34 | 14.8 | 31.97 | 0.320 |
| 3 X 120 | 19 | 13 | 1.6 | 1.34 | 16.2 | 34.99 | 0.253 |
| 3 X 150 | 19 | 14.6 | 1.8 | 1.52 | 18.2 | 39.31 | 0.206 |
| 3 X 185 | 36 | 16.2 | 2.0 | 1.70 | 20.2 | 43.63 | 0.164 |
| 3 X 240 | 36 | 18.4 | 2.2 | 1.88 | 22.8 | 49.25 | 0.125 |
| 4 X 10 | 7 | 4.05 | 1.0 | 0.8 | 6.05 | 14.64 | 3.08 |
| 4 X 16 | 7 | 4.8 | 1.2 | 0.98 | 7.2 | 17.42 | 1.91 |
| 4 X 25 | 7 | 6 | 1.2 | 0.98 | 8.4 | 20.33 | 1.20 |
| 4 X 35 | 7 | 7.0 | 1.4 | 1.16 | 9.8 | 23.72 | 0.868 |
| 4 X 50 | 7 | 8.3 | 1.4 | 1.16 | 11.1 | 26.86 | 0.641 |
| 4 X 70 | 19 | 9.8 | 1.4 | 1.16 | 12.6 | 30.49 | 0.443 |
| 4 X 95 | 19 | 11.6 | 1.6 | 1.34 | 14.8 | 35.82 | 0.320 |
| 4 X 120 | 19 | 13 | 1.6 | 1.34 | 16.2 | 39.20 | 0.253 |
| 4 X 150 | 19 | 14.6 | 1.8 | 1.52 | 18.2 | 44.04 | 0.206 |
| 4 X 185 | 36 | 16.2 | 2.0 | 1.70 | 20.2 | 48.88 | 0.164 |
| 4 X 240 | 36 | 18.4 | 2.2 | 1.88 | 22.8 | 55.18 | 0.125 |
(2) Phase + Neutral
| Phase | Neutral | Phase | Neutral | Approx.Overall Diameter | Max. D.C. Resistance of Conductor at 20ºC | ||||
| AAC+UV-XLPE | AAAC | Compact Conductor | UV-XLPE Insulation | Conductor | |||||
| Phase | Neutral | ||||||||
| No.X Normal Cross Section of Cores | No.X Normal Cross Section of Cores | No.of Al.Wire | Overall Dia. | Normal Thickness | Min. | No./Dia. of Al Alloy Wire | |||
| No. X mm2 | No. X mm2 | – | mm | mm | Min. | No./mm | mm | ohm/km | ohm/km |
| 1 X 16 | 1 X 16 | 7 | 4.8 | 1.2 | 0.98 | 7/1.70 | 12.30 | 1.91 | 2.217 |
| 1 X 25 | 1 X 25 | 7 | 6 | 1.2 | 0.98 | 7/2.10 | 14.70 | 1.20 | 1.393 |
| 1 X 35 | 1 X 35 | 7 | 7.0 | 1.4 | 1.16 | 7/2.50 | 17.30 | 0.868 | 1.007 |
| 1 X 50 | 1 X 50 | 7 | 8.3 | 1.4 | 1.16 | 7/3.00 | 20.10 | 0.641 | 0.744 |
| 1 X 70 | 1 X 70 | 19 | 9.8 | 1.4 | 1.16 | 7/3.50 | 23.10 | 0.443 | 0.514 |
| 1 X 95 | 1 X 95 | 19 | 11.6 | 1.6 | 1.34 | 19/2.50 | 27.30 | 0.320 | 0.371 |
| 1 X 120 | 1 X 120 | 19 | 13 | 1.6 | 1.34 | 19/2.80 | 30.20 | 0.253 | 0.294 |
| 1 X 150 | 1 X 150 | 19 | 14.6 | 1.8 | 1.52 | 37/2.25 | 33.95 | 0.206 | 0.239 |
| 1 X 185 | 1 X 185 | 36 | 16.2 | 2.0 | 1.70 | 37/2.50 | 37.70 | 0.164 | 0.190 |
| 1 X 240 | 1 X 240 | 36 | 18.4 | 2.2 | 1.88 | 61/2.25 | 43.05 | 0.125 | 0.145 |
| 2 X 16 | 1 X 16 | 7 | 4.8 | 1.2 | 0.98 | 7/1.70 | 14.04 | 1.91 | 2.217 |
| 2 X 25 | 1 X 25 | 7 | 6 | 1.2 | 0.98 | 7/2.10 | 16.63 | 1.20 | 1.393 |
| 2 X 35 | 1 X 35 | 7 | 7.0 | 1.4 | 1.16 | 7/2.50 | 19.51 | 0.868 | 1.007 |
| 2 X 50 | 1 X 50 | 7 | 8.3 | 1.4 | 1.16 | 7/3.00 | 22.46 | 0.641 | 0.744 |
| 2 X 70 | 1 X 70 | 19 | 9.8 | 1.4 | 1.16 | 7/3.50 | 25.70 | 0.443 | 0.514 |
| 2 X 95 | 1 X 95 | 19 | 11.6 | 1.6 | 1.34 | 19/2.50 | 30.31 | 0.320 | 0.371 |
| 2 X 120 | 1 X 120 | 19 | 13 | 1.6 | 1.34 | 19/2.80 | 33.41 | 0.253 | 0.294 |
| 2 X 150 | 1 X 150 | 19 | 14.6 | 1.8 | 1.52 | 37/2.25 | 37.55 | 0.206 | 0.239 |
| 2 X 185 | 1 X 185 | 36 | 16.2 | 2.0 | 1.70 | 37/2.50 | 41.69 | 0.164 | 0.190 |
| 2 X 240 | 1 X 240 | 36 | 18.4 | 2.2 | 1.88 | 61/2.25 | 47.41 | 0.125 | 0.145 |
| 3 X 16 | 1 X 16 | 7 | 4.8 | 1.2 | 0.98 | 7/1.70 | 16.15 | 1.91 | 2.217 |
| 3 X 25 | 1 X 25 | 7 | 6 | 1.2 | 0.98 | 7/2.10 | 19.06 | 1.20 | 1.393 |
| 3 X 35 | 1 X 35 | 7 | 7.0 | 1.4 | 1.16 | 7/2.50 | 22.32 | 0.868 | 1.007 |
| 3 X 50 | 1 X 50 | 7 | 8.3 | 1.4 | 1.16 | 7/3.00 | 25.59 | 0.641 | 0.744 |
| 3 X 70 | 1 X 70 | 19 | 9.8 | 1.4 | 1.16 | 7/3.50 | 29.22 | 0.443 | 0.514 |
| 3 X 95 | 1 X 95 | 19 | 11.6 | 1.6 | 1.34 | 19/2.50 | 34.42 | 0.320 | 0.371 |
| 3 X 120 | 1 X 120 | 19 | 13 | 1.6 | 1.34 | 19/2.80 | 37.87 | 0.253 | 0.294 |
| 3 X 150 | 1 X 150 | 19 | 14.6 | 1.8 | 1.52 | 37/2.25 | 42.56 | 0.206 | 0.239 |
| 3 X 185 | 1 X 185 | 36 | 16.2 | 2.0 | 1.70 | 37/2.50 | 47.25 | 0.164 | 0.190 |
| 3 X 240 | 1 X 240 | 36 | 18.4 | 2.2 | 1.88 | 61/2.25 | 53.63 | 0.125 | 0.145 |
(3) Phase + Neutral + Service Connection
| Phase | Neutral | Service Connection | Phase | Neutral | Service Connection | Approx.Overall Diameter of Bundled Cable | |||||
| AAC+UV-XLPE | AAAC+UV-XLPE | AAC+UV-XLPE | Conductor | UV-XLPE | Conductor | UV-XLPE | Compact Conductor | UV-XLPE | |||
| No.X Normal Cross Section of Cores | No.X Normal Cross Section of Cores | No.X Normal Cross Section of Cores | No. of Al. Wire | Overall Dia. | Normal Thickness |
No./Dia. of Al. Wire | Normal Thickness |
No. of Al. Wire | Overall Dia. | Normal Thickness |
|
| No. X mm2 | No. X mm2 | No. X mm2 | – | mm | mm | mm | mm | No./mm | mm | mm | mm |
| 3 X 16 | 1 X 50 | 1 X 16 | 7 | 4.8 | 1.2 | 7/3.0 | 1.4 | 7 | 4.8 | 1.2 | 26.2 |
| 3 X 25 | 1 X 50 | 1 X 16 | 7 | 6 | 1.2 | 7/3.0 | 1.4 | 7 | 4.8 | 1.2 | 28.6 |
| 3 X 35 | 1 X 50 | 1 X 16 | 7 | 7.0 | 1.4 | 7/3.0 | 1.4 | 7 | 4.8 | 1.2 | 31.4 |
| 3 X 50 | 1 X 50 | 1 X 16 | 7 | 8.3 | 1.4 | 7/3.0 | 1.4 | 7 | 4.8 | 1.2 | 34 |
| 3 X 70 | 1 X 50 | 1 X 16 | 19 | 9.8 | 1.4 | 7/3.0 | 1.4 | 7 | 4.8 | 1.2 | 37 |
| 3 X 95 | 1 X 50 | 1 X 16 | 19 | 11.6 | 1.6 | 7/3.0 | 1.4 | 7 | 4.8 | 1.2 | 41.4 |
| 3 X 120 | 1 X 50 | 1 X 16 | 19 | 13 | 1.6 | 7/3.0 | 1.4 | 7 | 4.8 | 1.2 | 44.2 |
| 3 X 16 | 1 X 50 | 2 X 16 | 7 | 4.8 | 1.2 | 7/3.0 | 1.4 | 7 | 4.8 | 1.2 | 26.2 |
| 3 X 25 | 1 X 50 | 2 X 16 | 7 | 6 | 1.2 | 7/3.0 | 1.4 | 7 | 4.8 | 1.2 | 28.6 |
| 3 X 35 | 1 X 50 | 2 X 16 | 7 | 7.0 | 1.4 | 7/3.0 | 1.4 | 7 | 4.8 | 1.2 | 31.4 |
| 3 X 50 | 1 X 50 | 2 X 16 | 7 | 8.3 | 1.4 | 7/3.0 | 1.4 | 7 | 4.8 | 1.2 | 34 |
| 3 X 70 | 1 X 50 | 2 X 16 | 19 | 9.8 | 1.4 | 7/3.0 | 1.4 | 7 | 4.8 | 1.2 | 37 |
| 3 X 95 | 1 X 50 | 2 X 16 | 19 | 11.6 | 1.6 | 7/3.0 | 1.4 | 7 | 4.8 | 1.2 | 41.4 |
| 3 X 120 | 1 X 50 | 2 X 16 | 19 | 13 | 1.6 | 7/3.0 | 1.4 | 7 | 4.8 | 1.2 | 44.2 |
We are China High Quality 33kv ABC Cable for Overhead Use manufacture and supplier,You can get more details with Email,you will get cheap price or factory price.
Get Latest Price Request a quote
Popular 33kv ABC Cable Products
Mv 33kv 3X150+50 Sqmm Overhead Insulated Cable ABC Aerial Bundle Cable
Service Drop Cable Aerial Bundled Cable Twisted Aluminum ABC Cable
Aluminum Conductor XLPE Insulation 33kv ABC Aerial Bundle Cable
Factory Price Low Voltage Al Conductor XLPE Insulated Aerial Bundled Cable
19/33kV Aluminium Conductor AL ABC 3Cx150+50mm2 XLPE Insulated Aerial Bundled Cable
Popular ABC Cable Products
Service Drop ABC Cable Aluminum Overhead Cable with PE PVC or XLPE Insulation 35mm2 Aluminum Cable
Aerial Bundle Cable (JKLV-1KV)
Various Sizes Aluminum (Al) Power ABC Cable Aerial Bundled Cable
Spacer Cable Tree Wire ABC Cable
Twisted Aluminium Aerial XLPE Insulation ABC Cable
4*10 Aluminum Insulated XLPE/PE ABC Cable Service Aluminum Cable
Popular Aerial Cable Products
11kv ABC Cable by Jinshui Manumfactory
3X35mm2+E Aluminium Conductor XLPE Insulation ABC Aerial Bundled Cable
Low Voltage Aluminium Conductor XLPE Insulation Service Drop ABC Aerial Bundled Cable
Factory Overhead Twisted Aerial Bundled Cable ABC Cable
0.6/1kv Overhead Twisted Aerial Cable with / Without XLPE Insulated Public Lighting Caai Caai-S
ASTM PVC Insulation Aluminum Conductor ABC Aerial Cable
Popular jpcable99 Products
CSA C49 Standard AAC Conductor
Mv Voltage XLPE Insulated Swa Armoured Electric Cable, Power Cable
(Stranded) Galvanized Steel Wire
12/20kv Medium Voltage XLPE/Swa/PVC Power Cable 1*50 1*70
50mm PVC Insulated and Sheathed Power Cable
ASTM B549-88 Standard ACSR/Aw Conductor
Tags: 33kv ABC Cable, ABC Cable, Aerial Cable, jpcable99