Center Break Isolator and double Break Isolator
The following documents were referred to during the preparation of this specification. In case of conflict, the provisions of this specification shall take precedence.
IEC 129:1975: Alternating Current Disconnectors (Isolators) and Earthing Switches
IEC 60694:2002: Common Specifications for High Voltage Switchgear and Controlgear
BS 729: Hot dip galvanized coating on iron and steel articles
IEC62271-102
Isolator (Disconnector) – a mechanical switching device which provides, in the open position, an isolating distance in accordance with Electrical Safety requirements.
SERVICE CONDITIONS
The isolator shall be suitable for continuous operation outdoors in tropical areas at altitudes of up to 2200m above sea level, humidities of up to 90%, average ambient temperature of +30ºC with a minimum of -1ºC and a maximum of +40ºC and heavy saline conditions along the coast.
4.2. DESIGN AND CONSTRUCTION
4.2.1 The Isolator, Solid Link shall be designed and constructed in accordance with IEC 129 and IEC 60694.
4.2.2 The isolating link shall be of the vertical opening, designed for single phase manual operation. It shall be easily removed and replaced by using a portable operating rod.
4.2.3 The isolating link shall incorporate double porcelain insulators to suit voltage requirements and mounted on hot dipped galvanised steel under base suitable for vertical mounting.
4.2.4 The isolating link shall be arranged so that each unit is mounted independently on an angle bracket. It shall be supplied complete with the angle bracket and accessories suitable for mounting on ‘U’ type steel channel. The drawings to be submitted shall indicate all the applicable mounting positions.
4.2.5 The isolator shall be designed such that in fully open position, it shall provide adequate electrical isolation between the contacts on each phase. It shall conform to the requirement as single point isolation for safety.
4.2.6 All steel parts shall be hot dip galvanized to BS 729. The minimum coating of galvanizing required is 80 microns.
4.2.7 The solid link shall be removable from the mounting by use of operating rod.
4.2.8 All current carrying parts of the isolator shall be made of high conductivity material.
4.2.9 The isolator shall be fitted with clamp connectors for Aluminium (ACSR) conductor of Aluminium (ACSR)conductor of up to 18.2mm diameter.
The rating of the complete isolator shall be as follows: –
Rated voltage
36 kV
Rated frequency
50 Hz
Rated lightning impulse withstand voltage
200 kV
Rated power frequency withstand voltage, dry
95 kV
Rated normal current
400 Amps
Rated short time withstand current for 3 sec, min.
18.0 kA
Minimum creepage distance of insulators
900 mm
System Voltages | 132kV | ||
1 | System: | 50 Hz, 3phase | |
2 | Neutral Point Earthing | Solidly Earthed | Earthing Resistor |
3 | Nominal voltage of networks | 132kV | |
4 | Highest system voltage as defined by IEC – 38 | 145kV | |
5 | Short circuit not less than [MVA] | N/A | |
6 | Short circuit and earth fault current, symmetrical r.m.s. value not less than | N/A | |
7 | Thermal short circuit current, 1 second not less than | 31.5 kA | |
8 | Dynamic Peak current not less than | 80 kA | |
9 | Continuously rated currents of Isolating Switches: | 1 600 A | |
10 | Isolation Voltage according to IEC – 71 | ||
10 a | – Switching Surge withstand voltage | ||
Phase to earth | 275 kV | ||
– Longitudinal impulse component of combined test | 325 kV | ||
10 b | – Lightning Impulse withstand voltage 1.2/50 micro-s | ||
To earth and between phases | 650kVp | ||
Across the isolating distance of isolating switches | 750 kVp | ||
10 c | – Test voltage at power frequency 1 minute, dry and wet (at sea level) |
||
To earth and between phases (r.m.s.) | N/A | ||
Across the isolating distance of isolating switches | N/A | ||
11 | For the design and erection of the conductors in the switchyard the following minimum distance shall be observed: | ||
11a | Phasetoground [mm] | 1 500 | |
11b | – Phasetophase | 2 330 | |
11c | Busbars phasetophase | 3 500 | |
11d | Height to live parts above ground | 5 500 | |
11e | Height to live parts above ground at service/transportation strips [mm] |
5 500 | |
11f | – Lowest part of insulators above ground [mm] | 3 500 | |
12 | Maximum temperature rise of conductors above ambient temperature (45oC) |
40oC | |
13 | Maximum wind pressure on conductors and cylindrical objects | 430N/m2 | |
14 | Maximum wind pressure on flat surfaces | 820N/m2 | |
15 | Minimum nominal creepage distance as defined in IEC 815, Table II | 25 mm/kV |
We are China Interrupteur aé Rien à Commande Manuelle Rocking Disconnectors manufacture and supplier,You can get more details with Email,you will get cheap price or factory price.
Get Latest Price Request a quote
Popular Disconnect Switch Products
Gang Isolation Switch Disconnect AC Three Phase High Voltage Outdoor11kv
Outdoor Single Pole Fused Recloser by-Pass Switches 11kv
Hight-Voltage Gw4 10~252kv Disconnector Switch
12 Kv 3 Phase Gang Operated Air Load Break Switch
33kv High Voltage Gang Isolation Switch / Isolator Switches
Gw13 Series 126kv 1250A Lightning Protection High Voltage Disconnector
Popular Disconnector Products
Disconnect Switch V-Type Centre Breaker
Gw8 Neutral Point Disconnector 145kv
75kv Gw4 Outdoor Hv Disconnector/Disconnecting Switch
High -Voltage Isolate Switch 12kv
Double-Column High Voltage Centre Break Disconnector
High -Voltage Isolate Switch 126kv
Popular Isolator Switch Products
Load Break Switch Fuse Disconnector 24kv 200A
High -Voltage Isolate Switch 20kv
High Quality Disc Suspension Ceramic Insulator
High Voltage Indoor Isolator Disconnector Isolated Switch
Hkgwf-36 High Voltage Disconnect Switch Manufacturer Quality Disconnector
Popular jgtrade1 Products
Piercing Arc-Protection Connector (Piercing /Non-piercing)
Jla-3 Special Grounding Wire for Power Plant
T Connectors for Double Conductors Type Mg/Mr, Group B
Tags: Disconnect Switch, Disconnector, Isolator Switch, jgtrade1