J- Hook
J- Hook image
Get Latest Price Request a quote
Quick Details
Product Details
Features
Performance Data
Porcelain housed for outdoor application
CONSTRUCTION & OPERATING PRINCIPLE
11kV
No. | DETAIL | UNITS | DATA |
Type | 11kV gapless type metal oxide surge arrester – Distribution class |
||
1. | Nominal system voltage | kV | 11 |
2. | Highest system voltage | kV | 12 |
3. | Basic Insulation Level (BIL) | kV | 95 |
3. Ratings and type of surge arrester |
|||
4. | Specification to which surge arrester complies | IEC 60099–4 |
|
5. | Rated voltage of surge arrester | kV | 10 |
6. | Nominal, 8/20 µs, discharge current rating of surge arrester |
kA | 10 |
7. | Maximum continuous operating voltage of surge arrester |
kV | 7.3 |
8. | Gapless or gapped type metal–oxide surge arrester |
Gapless | |
9. | Material of insulation | High temperature vulcanised silicon rubber |
|
10. | Rated frequency of surge arrester | Hz | 50 |
11. | Design altitude of surge arrester (above sea level) |
m | 1 400m |
12. | Design ambient temperature of surge arrester | oC | –1 to40 |
13. | Specific creepage distance of surge arrester | .mm/kV | 25 |
Automatic earth lead disconnectors requirements |
|||
14. | Automatic earth lead disconnectors to be fitted | Yes/No | YES |
15. | Corrosion protection of metal and alloy parts: galvanising specification and/or stainless steel grade |
To SABS 763, 316 | |
Tests | |||
16. | Previous type test results/certificate to be provided with bid |
Yes/No | Yes |
17. | Routine test results/certificate to be provided on delivery |
Yes/No | Yes |
18. | Drawing showing dimensions of the arrestor to be provided with the bid |
Yes/No | Yes |
19. | Minimum one minute wet power frequency withstand voltage of external insulation of surge arrester housing |
kV | 28 |
20. | Maximum steep current impulse residual voltage for a 10 kA, 1/20 µs, discharge current |
kV | 50 |
21. | Maximum lightning impulse residual voltage for a 10 kA, 8/20 µs, discharge current |
kV | 40 |
22. | Lightning, 1,2/50 µs, impulse withstand level of external insulation of surge arrester housing |
kV | 95 |
23. | Line discharge class rating | 1 | |
24. | Long duration current, 2 000 µs, impulse withstand |
A | 250 A |
25. | High current, 4/10 µs, impulse withstand | kA | 100 kA |
26. | Automatic earth lead disconnector to be tested in accordance with IEC 60099–4 |
Yes/No | Yes |
33kV
S/N | TECHNICAL DETAILS | UNITS | DATA | |
1. | Type | 33kV gapless type metal oxide surge arrester – Distribution class |
||
2. | Nominal system voltage | kV | 33 | |
3. | Highest system voltage | kV | 36 | |
4. | Power frequency | Hz | 50 | |
5. | Basic Insulation Level (BIL) | kV | 170 | |
3. Ratings and type of surge arrester |
||||
6. | Specification to which surge arrester complies | IEC 60099 | ||
7. | Rated voltage of surge arrester | kV | 29 | |
8. | Nominal, 8/20 µs, discharge current rating of surge arrester | kA | 10 | |
9. | Maximum continuous operating voltage of surge arrester | kV | 22 | |
10. | Gapless or gapped type metal–oxide surge arrester | Gapless | ||
11. | Insulation Material | Silicon rubber | ||
12. | Cantilever strength of surge arrester | Nm | 300 | |
13. | Rated frequency of surge arrester | Hz | 50 | |
14. | Design altitude of surge arrester (above sea level) | m | 1 400m | |
15. | Design ambient temperature of surge arrester | oC | –1 to 40 | |
16. | Minimum phase–to–ground specific creepage distance of surge arrester |
.mm/kV | 25 | |
Automatic earth lead disconnectors requirements | ||||
17. | Automatic earth lead disconnectors fitted | Yes/No | Yes | |
18. | Corrosion protection of metal and alloy parts: galvanising | To SABS 763, 316 | ||
specification and/or stainless steel grade | |||
Tests | |||
19. | Previous Type Test reports/certificate from recognized authority to be provided with bid |
Yes/No | Yes |
20. | Minimum one minute wet power frequency withstand voltage of external insulation of surge arrester housing |
kV | 70 |
21. | Maximum steep current impulse residual voltage for a 10 kA, 1/20 µs, discharge current |
kV | 99.7 |
22. | Maximum lightning impulse residual voltage for a 10 kA, 8/20 µs, discharge current |
kV | 91.8 |
23. | Lightning, 1,2/50 µs, impulse withstand level of external insulation of surge arrester housing |
kV | 170 |
24. | Line discharge class rating | Class | 1 |
25. | Long duration current, 2 000 µs, impulse withstand | A | 250 A |
26. | High current, 4/10 µs, impulse withstand | kA | 100 kA |
27. | Is the automatic earth lead disconnector tested in accordance with IEC 60099–4? |
Yes/No | Yes |
66kV
S/N | TECHNICAL DETAILS | UNITS | DATA |
1. | Description | Station type lightning arrestor complete with steel support structures. |
|
2. | Type | Zinc oxide gapless lightning arrestor |
|
System parameters | |||
3. | Nominal system voltage | kV | 66 |
4. | Highest system voltage | kV | 72.5 |
5. | Power frequency | Hz | 50 |
6. | Type of system earthing | Effective/Non effective | |
7. | Type of arrestor connection to system | Line to ground | |
3. Ratings and type of surge arrester |
|||
8. | Rated voltage of surge arrester | kV rms | 54 |
9. | Nominal, 8/20 µs, discharge current rating of surge arrester | kA peak | 10 |
10. | Maximum continuous operating voltage of surge arrester | kV | 43 |
11. | Minimum one minute wet power frequency withstand voltage | kVrms | 140 |
151
of external insulation of surge arrester housing | |||
12. | Maximum steep current impulse residual voltage for a 2 kA, 30/60 µs, discharge current |
kVpeak | 104 |
13. | Maximum lightning impulse residual voltage for a 10 kA, 8/20 µs, discharge current |
kVpeak | 127 |
14. | Minimum lightning, 1,2/50 µs, impulse withstand level of external insulation of surge arrester housing |
325 | |
15. | Line discharge class rating | 2 | |
16. | Lighting arrestor counter, leakage current meter and their accessories to be provided |
Yes/No | Yes |
17. | Gapless or gapped type metal–oxide surge arrester | Gapless | |
18. | Insulation Material | Porcelain | |
19. | Cantilever strength of surge arrester | Nm | 3000 |
20. | Rated frequency of surge arrester | Hz | 50 |
21. | Maximum angle from vertical at which surge arrester is fully functional |
Deg | 45 |
22. | Design altitude of surge arrester (above sea level) | m | 1400 m |
23. | Design ambient temperature of surge arrester | oC | –1 to 40 |
24. | Humidity | % | 85 |
25. | Specific phase–to–ground creepage of surge arrester | .mm/kV | 25 |
26. | Corrosion protection of metal and alloy parts: galvanising specification and/or stainless steel grade |
to SABS 763 or 316 stainless steel |
|
27. | Previous type test results/certificate to be provided with bid | Yes/No | Yes |
28. | Design drawings showing dimensions including foundations and brochures to be provided with bid |
Yes/No | Yes |
29. | Quality Assurance certification to be provided with the bid | Yes/No | Yes |
30. | Routine test results/certificate to be provided on delivery | Yes/No | Yes |
31. | Galvanized steel support structures complete with bolts & washers to be provided on delivery |
Yes/No | Yes |
32. | Applicable standard | IEC60099 |
152
88Kv
S/N | TECHNICAL DETAILS | UNITS | DATA |
33. | Description | Station type lightning arrestor complete with steel support structures. |
|
34. | Type | Zinc oxide gapless lightning arrestor |
|
System parameters | |||
35. | Nominal system voltage | kV | 88 |
36. | Highest system voltage | kV | 100 |
37. | Power frequency | Hz | 50 |
38. | Type of system earthing | Effective/Non effective | |
39. | Type of arrestor connection to system | Line to ground | |
3. Ratings and type of surge arrester |
|||
40. | Rated voltage of surge arrester | kV rms | 84 |
41. | Nominal, 8/20 µs, discharge current rating of surge arrester | kA peak | 10 |
42. | Maximum continuous operating voltage of surge arrester | kV | 67 |
43. | Minimum one minute wet power frequency withstand voltage of external insulation of surge arrester housing |
kVrms | 185 |
Maximum steep current impulse residual voltage for a 2 kA, | kVpeak | 188 | |
30/60 µs, discharge current | |||
45. | Maximum lightning impulse residual voltage for a 10 kA, 8/20 µs, discharge current |
kVpeak | 218 |
46. | Minimum lightning, 1,2/50 µs, impulse withstand level of external insulation of surge arrester housing |
450 | |
47. | Line discharge class rating | 2 | |
48. | Lighting arrestor counter, leakage current meter and their accessories to be provided |
Yes/No | Yes |
49. | Gapless or gapped type metal–oxide surge arrester | Gapless | |
50. | Insulation Material | Porcelain | |
51. | Cantilever strength of surge arrester | Nm | 3000 |
52. | Rated frequency of surge arrester | Hz | 50 |
53. | Maximum angle from vertical at which surge arrester is fully functional |
Deg | 45 |
54. | Design altitude of surge arrester (above sea level) | m | 1400 m |
55. | Design ambient temperature of surge arrester | oC | –1 to 40 |
56. | Humidity | % | 85 |
57. | Specific phase–to–ground creepage of surge arrester | .mm/kV | 25 |
58. | Corrosion protection of metal and alloy parts: galvanising specification and/or stainless steel grade |
to SABS 763 or 316 stainless steel |
|
59. | Previous type test results/certificate to be provided with bid | Yes/No | Yes |
60. | Design drawings showing dimensions including foundations and brochures to be provided with bid |
Yes/No | Yes |
61. | Quality Assurance certification to be provided with the bid | Yes/No | Yes |
62. | Routine test results/certificate to be provided on delivery | Yes/No | Yes |
63. | Galvanized steel support structures complete with bolts & washers to be provided on delivery |
Yes/No | Yes |
64. | Applicable standard | IEC60099 |
Recommended for You
Not exactly what you want?
Post Sourcing Request
Hot Searches
Protective Device
Power Surge
Surge Protection
Arrester
Surge Protector
We are China J- Hook manufacture and supplier,You can get more details with Email,you will get cheap price or factory price.
Get Latest Price Request a quote
Popular jgtrade1 Products
Terminal, Aluminium Compression-Cableto Flat-4 Hole: Acf 400c
Polymer Fuse Cutout, Drop out Fuses 12 Kv 200A
Cut Resistance Gloves, Nitrile Sandy Finishhppe + Dyneema + Tprblack 7-11
24-27kv 100A Silicon Rubber Drop-out Fuse Cutout
Yh10W-48, Sharp Head 48kv 10ka Surge Arrester
Popular Lightning Arrester Products
Yh5w-11, Lighting Arrester Surge Arrester
10kv Porcelain Housed Lightning Arrester
Al-Cu Transition Connectors Type Syg, Compression Type, Group a
132kv Porcelain / Ceramic Surge Lighting Arrester
0.25~500kv 10ka Hv Polymeric Zinc Oxide Surge Arrestor with Kema
Popular Lightning Arrestors Products
Hy5w-3.8/17 Zinc-Oxide Arrester
Yh10W-21, 21kv 10ka Surge Arrester
Type “ +” Earthwire to Earthwire
Popular Surge Arrester Products
24kv Porcelain Type Surge Arrester Y10W-18
Trading 110kv High Voltage Substation Porcelain Surge Arrester with Kema
High Voltage 12kv 15kv Lightning Protection System, Lighting Arrester
27kv Zinc Oxide Compound Surge Arrester 10ka
5kv Gapped Lightning Arrester Surge Arrester
Tags: jgtrade1, Lightning Arrester, Lightning Arrestors, Surge Arrester