Jszw 3kv 6kv 10kv 100va Indoor Potential Transformer PT for Electric Energy Measurement and Relay Protection

China 
                Jszw 3kv 6kv 10kv 100va Indoor Potential Transformer PT for Electric Energy Measurement and Relay Protection
              manufacture and supplier

Jszw 3kv 6kv 10kv 100va Indoor Potential Transformer PT for Electric Energy Measurement and Relay Protection image

Get Latest Price Request a quote

Basic Info.

Model NO.
JSZW

Insulating Medium
Epoxy Resin

Installation
Strut Type

Magnetic Circuit Structure
Single Stage Type

Voltage Transformation Principle
Electromagnetic Type

Rated Voltage Ratio
35000/√3/100/√3/100/3

Accuracy Level
0.5/6p 1/6p 3/6p

Rated Output
75-600va

Max Output
600-1000va

Rated Frequency
50/60Hz

Rated Voltage
3/6/10kv

Rated Insulation Level
12/42/75kv

Transport Package
Wooden Case

Specification
371*240*488mm

Trademark
CNKC

Origin
China

Production Capacity
5000PCS/Monthly

Product Description

Product Description
JSZW3-3, 6, 10 voltage transformers are indoor epoxy resin casting semi-closed structure, suitable for voltage, electric energy measurement and relay protection in AC 50HZ voltage 3, 6, 10KV neutral point non-effective grounding power system According to different installation methods, the product is divided into A type and B type.

Model Description

Product technical parameters and structure dimensions

Product features and scope of use 

This type of voltage transformer is a semi-casting type, with small size and strong climate adaptability. The core of the transformer adopts a core-type structure with a side iron yoke, and is made of high-quality cold-rolled silicon steel sheets stacked in a rectangle. The primary, secondary and residual voltage windings are concentrically wound together, cast and molded with epoxy resin, and the three-phase casting body is fixed together. The primary winding is fully insulated at the A end, and the other N end is not fully insulated. The wiring diagram is shown in Figure 1: According to the installation method, this product is divided into A type and B type. Type A products are installed on the side, and the mounting holes are on the iron core clip. Type B products have a mounting base, which is used to strengthen the product.
Conditions of Use:
1. The altitude does not exceed 3000 meters;
2. The ambient temperature is not higher than ten 40’C, not lower than one 5’C;
3. The relative humidity of the air in the weekly warehouse is not more than 85% (20 C);
4. There is no corrosive gas in the installation site

Precautions for product use

1. Before the voltage transformer is put into operation, the test and inspection shall be carried out according to the items specified in the regulations. For example, measuring polarity, connection group, shaking insulation, nuclear phase sequence, etc.
2. The wiring of the voltage transformer should ensure its correctness. The primary winding should be connected in parallel with the circuit under test, and the secondary winding should be connected in parallel with the voltage coil of the connected measuring instrument, relay protection device or automatic device. At the same time, attention should be paid to the correctness of the polarity. .
3. The capacity of the load connected to the secondary side of the voltage transformer should be appropriate, and the load connected to the secondary side of the voltage transformer should not exceed its rated capacity, otherwise, the error of the transformer will increase, and it is difficult to achieve the correctness of the measurement.
4. No short circuit is allowed on the secondary side of the voltage transformer. Since the internal impedance of the voltage transformer is very small, if the secondary circuit is short-circuited, a large current will appear, which will damage the secondary equipment and even endanger personal safety. The voltage transformer can be equipped with a fuse on the secondary side to protect itself from being damaged by a short circuit on the secondary side. If possible, fuses should also be installed on the primary side to protect the high-voltage power grid from endangering the safety of the primary system due to the failure of the transformer’s high-voltage windings or lead wires.
5. In order to ensure the safety of people when touching measuring instruments and relays, the secondary winding of the voltage transformer must be grounded at one point. Because after grounding, when the insulation between the primary and secondary windings is damaged, it can prevent the high voltage of the instrument and the relay from endangering personal safety.
6. Short circuit is not allowed on the secondary side of the voltage transformer.

Products real shot

A corner of the production workshop

Product packaging

Product application case

 

 
/* January 22, 2024 19:08:37 */!function(){function s(e,r){var a,o={};try{e&&e.split(“,”).forEach(function(e,t){e&&(a=e.match(/(.*?):(.*)$/))&&1

We are China Jszw 3kv 6kv 10kv 100va Indoor Potential Transformer PT for Electric Energy Measurement and Relay Protection manufacture and supplier,You can get more details with Email,you will get cheap price or factory price.

Get Latest Price Request a quote

Popular cnkcele Products

Hrw/Hrxwo 10-35kv 10A Outdoor Pollution Resistant Type Silicon Rubber High Voltage Current Limiting Fuse

Mgf 45-250mm Substation Fitting Dead-End Caps (Damper type) Electric Power Fittings

Kbsgzy 50-4000kVA Exp Explosion-Proof Mobile Substation for Mine Tunnel Dry-Type Explosion-Proof Transformer

Ybd 6-10kv 30-2000kVA Outdoor Prefabricated Underground Box Type Substation

Lw16-40.5 35kv 1600-2000A Outdoor Three-Phase AC Sulfur Hexafluoride Circuit Breaker

PGA 10-300mm² 34-133mm Energy-Saving Type Parallel Trench Wire Clamps for Overhead Cables

Popular Earthed Voltage Transformer Products

Jdj2 35kv 35000/100V 0.2/6p 80-500va Outdoor Hv Oil-Immersed Insulation Voltage Instrument Transformer Mutual Inductor

Jszw3-10 10000/√ 3/100/√ 3/100/3V 1000va Indoor Three-Phase Dry-Type High Voltage Voltage Transformer Potential Transformer

Popular Hv Instrument Transformer Products

Lzzb9 24/35kv 200-1250A Indoor Current Transformer for High Voltage Switchgear

La-10 5-40A 0.2-0.5/10p 10/15va Indoor Semi-Enclosed Through-Wall Type High Voltage Current Transformer

Jls-35kv/100V 5-300A 30/50va 10/20va Outdoor Oil-Immersed Combined Instrument Transformer High Voltage Power Metering Box

Jdj2 35kv 35000/100V 0.2/6p 80-500va Outdoor Hv Oil-Immersed Insulation Voltage Instrument Transformer Mutual Inductor

Jls 3/6/10kv 5A Outdoor Oil-Immersed High-Voltage Power Metering Box Three-Phase Three-Wire Combined Instrument Transformer

Jlszy-10kv 5-1000A 10va Outdoor Three-Phase Four-Wire Combined Instrument Transformer High Voltage Power Metering Box

Popular Jszw 3kv 6kv 10kv 100va Indoor Potential Transformer PT for Electric Energy Measurement and Relay Protection Products

  • No related articles
  • Tags: , , ,

    FAST AND RELIABLE SERVICE FOR YOUR PROJECT

    Contact our trained experts today to find your perfect power solution.

    ASK A QUESTION