Low Smoke Zero Halogen Cable Lsoh Power Underground
Low Smoke Zero Halogen Cable Lsoh Power Underground image
Get Latest Price Request a quote
Quick Details
Product Details
For Medium Cable, we have UL certificate, TUV and KEMA type test report.
Advantages of Hebei Huatong Cables Group:
Top ten cable manufacturer in China
Largest manufacturer&exporter of UL listed cables in China
Annual export volume exceed USD300million
UL, CUL, CSA, TUV, KEMA, CE, BV, PSB, SABS, LLOYD’S, GL, NK, KR, ABS certificates
CNAS approved lab!
1 Application:
It is used to transmit and distribute power in power transmission and distribution system of 35kV or lower. It is generally applied to the fields including power, construction, mines, metallurgy, petrochemical industry and communication in complete replace of oil immersed paper insulated power cable and in partial replace of PVC insulated power cable. Power cables for power networks, underground, outdoors and in cable ducting
2 Construction
Standards: BS6622, BS EN/IEC 60228,IEC60502.2
Conductor: Class 2 stranded plain copper conductor to BS EN 60228:2005 (previously BS6360)
Conductor screen: Semi-conducting material
Insulation: XLPE (Cross-Linked Polyethylene) Type GP8 to BS7655
Insulation Screen: Semi-conducting material
Metallic Screen: Individual and overall copper tape screen to BS6622
Filler: PET (Polyethylene Terephthalate) fibres
Separator: Binding tape
Bedding: PVC (Polyvinyl Chloride) Type TM1 to BS7655
Armoring:
Single Core: Aluminum Wire Armored (AWA)
MultiCore: Steel Wire Armored (SWA)
Sheath: PVC (Polyvinyl Chloride) Type TM1 to BS7655
Color: Red or Black
3 Using features:
1.Rated voltage: Uo/U:3.6/6kV, 6/10kV(11kV), 12/20kV(24kV), 19/33kV, 26/35kV(35kV).
2. No. of core: Single core or three cores.
3. The highest allowed operating temperature of conductor for long-term working is 90oC. In short-circuit (Max. long-term is no more than 5 seconds). The highest temperature for conductor is no more than 250ºC.
4. D.C. resistance of the conductor complies with the stipulations of 3.6/6kV, 6/10kV(11kV), 12/20kV(24kV), 19/33kV, 26/35kV(35kV).
5. The environment temperature should be no lower than 0oC when lay. Otherwise it should be preheated.
6. The cable is laid without horizontal drop limit.
7. Working Frequency Voltage Test: 3.5Uo/5min without puncture.
8. Partial Discharge Test: The discharge volume should be no more than 10pC under 1.73Uo for the cable.
Company Introduction:
Hebei huatong wires&cables Group Co.,ltd.It was established in 1993, we are JV with Furukawa(Japanese company) for rubber serious cables and JV with Riken(Japanese company) for elevator cables.
Besides these,our submersible oil pump cable and shipboard cable are very influential in domestic, and, the traditional cables are also produced such as PVC powercables, XLPE power cables, ABC cables, wires, control cables, screened cables,communication cables, conductors.We areOEM for many USA, Europen, Australia cable company,70% of our products are exported, most customers are from developed countries. We got ISO,UL,TUV,
KEMA,CE and many other certifications.
We are China Low Smoke Zero Halogen Cable Lsoh Power Underground manufacture and supplier,You can get more details with Email,you will get cheap price or factory price.
Get Latest Price Request a quote
Popular Cable Lsoh Products
Popular Cable Power Underground Products
Popular huatongcables Products
0.6/1kv 240mm Aluminium Cable Single Multicore
Round Flame Retardant 600V Copper Thwn Solid Cu Cable Manufacturer UL Thhn Wire
Type 41 - Flexible Trailing Cable Sans 1520
Red Strip Industrial Primary XLPE Cable Medium Voltage Power Mv90, Mv105
150mm2 Copper Conductor Underground Power Cable
Class 5 Copper Conductor Rubber Insulation H07rn-F Cable 450/750V Cable
Popular Low Smoke Zero Halogen Cable Products
H07z-R Low Smoke Zero Halogen LSZH Cables
6491b Low Smoke Zero Halogen Cable
XLPE Insulated LSZH Low Smoke Zero Halogen Free Fire Retardent Cable
Tags: Cable Lsoh, Cable Power Underground, huatongcables, Low Smoke Zero Halogen Cable