Mv Voltage XLPE Insulated Swa Armoured Power Cable
Mv Voltage XLPE Insulated Swa Armoured Power Cable image
Get Latest Price Request a quote
- Overview
- Product Description
- Product Parameters
- Company Profile
Basic Info.
Packaging & Delivery
Product Description
Application:
Media Voltage XLPE Insulated power cable is used to transmit and distribute power in power transmission and distribution system of 35kV or lower. It is generally applied to the fields including power, construction, mines, metallurgy, petrochemical industry and communication in complete replace of oil immersed paper insulated power cable.
Prpperty:
1.The highest allowed operating temperature of conductor for long-term working is 90 degrees.
2.In short circuit (Max long term is no more than 5 seconds). The highest temperature for conductor is no more than 250 degrees.
3.The cable is laid without horizontal drop limit. The environment temperature should be no lower than 0 when lay. Otherwise it should be preheated.
4.Excellent electrical performance, resistance to chemical corrosion.
5.They can stand advisable traction when laid.They can stand traction from Outside.Left low smoke halogen-free after burned.Retard the burning of the cable.
Specification:
IEC60502,designing and manufacturing special power cable according to the other standards required by the customers.
1)3.6/6(7.2)kV,3.6/6.6(7.2)kV,Three Cores,Al or Cu/XLPE/CTS/STA/PVC Armoured Power Cable
| No.X Nominal Cross Section of Conductor | Nominal Diameter of Conductor | Nominal Thickness of Insulation | Nominal Thickness of Copper Tape Screen | Nominal Thickness of Inner Sheath | Nominal Thickness of Steel Tape Armouring | Nominal Thickness of PVC Sheath | Approx. Overall Diameter | Approx. Weight | |
| Al Conductor | Cu Conductor | ||||||||
| No. X mm2 | mm | mm | mm | mm | mm | mm | mm | kg/m | kg/m |
| 3 X 25 | 6.0 | 2.5 | 0.1 | 1.2 | 0.2 | 1.9 | 37.9 | 1.87 | 2.32 |
| 3 X 35 | 6.9 | 2.5 | 0.1 | 1.3 | 0.5 | 2.0 | 41.5 | 2.10 | 2.73 |
| 3 X50 | 8.2 | 2.5 | 0.1 | 1.3 | 0.5 | 2.0 | 44.3 | 2.37 | 3.22 |
| 3 X 70 | 9.7 | 2.5 | 0.1 | 1.4 | 0.5 | 2.1 | 47.9 | 2.77 | 4.00 |
| 3 X 95 | 11.3 | 2.5 | 0.1 | 1.4 | 0.5 | 2.2 | 51.6 | 3.21 | 4.91 |
| 3 X 120 | 12.8 | 2.5 | 0.1 | 1.5 | 0.5 | 2.4 | 55.4 | 3.69 | 5.84 |
| 3 X 150 | 14.2 | 2.5 | 0.1 | 1.5 | 0.5 | 2.5 | 58.6 | 4.15 | 6.85 |
| 3 X 185 | 15.9 | 2.5 | 0.1 | 1.5 | 0.5 | 2.6 | 62.5 | 4.73 | 8.11 |
| 3 X 240 | 18.3 | 2.6 | 0.1 | 1.6 | 0.5 | 2.7 | 68.5 | 5.62 | 10.05 |
| 3 X 300 | 20.4 | 2.8 | 0.1 | 1.7 | 0.5 | 2.9 | 74.5 | 6.55 | 12.11 |
| 3 X 400 | 23.2 | 3.0 | 0.1 | 1.9 | 0.8 | 3.2 | 83.6 | 8.78 | 15.86 |
| 3 X 500 | 26.4 | 3.2 | 0.1 | 2.1 | 0.8 | 3.4 | 93.0 | 10.52 | 18.85 |
2)6/10(12)kV,6.35/11(12)kV,,Three Cores,Al or Cu/XLPE/CTS/STA/PVC Armoured Power Cable
| No.X Nominal Cross Section of Conductor | Nominal Diameter of Conductor | Nominal Thickness of Insulation | Nominal Thickness of Copper Tape Screen | Nominal Thickness of Inner Sheath | Nominal Thickness of Steel Tape Armouring | Nominal Thickness of PVC Sheath | Approx. Overall Diameter | Approx. Weight | |
| Al Conductor | Cu Conductor | ||||||||
| No. X mm2 | mm | mm | mm | mm | mm | mm | mm | kg/m | kg/m |
| 3 X 25 | 6.0 | 3.4 | 0.1 | 1.3 | 0.5 | 2.0 | 43.4 | 2.16 | 2.61 |
| 3 X 35 | 6.9 | 3.4 | 0.1 | 1.3 | 0.5 | 2.0 | 45.4 | 2.36 | 2.99 |
| 3 X50 | 8.2 | 3.4 | 0.1 | 1.4 | 0.5 | 2.2 | 48.8 | 2.69 | 3.54 |
| 3 X 70 | 9.7 | 3.4 | 0.1 | 1.5 | 0.5 | 2.3 | 52.4 | 3.10 | 4.33 |
| 3 X 95 | 11.3 | 3.4 | 0.1 | 1.5 | 0.5 | 2.4 | 56.1 | 3.56 | 5.26 |
| 3 X 120 | 12.8 | 3.4 | 0.1 | 1.5 | 0.5 | 2.5 | 59.5 | 4.04 | 6.19 |
| 3 X 150 | 14.2 | 3.4 | 0.1 | 1.5 | 0.5 | 2.6 | 62.7 | 4.49 | 7.19 |
| 3 X 185 | 15.9 | 3.4 | 0.1 | 1.6 | 0.5 | 2.6 | 66.6 | 5.12 | 8.49 |
| 3 X 240 | 18.3 | 3.4 | 0.1 | 1.7 | 0.5 | 2.8 | 72.4 | 5.99 | 10.42 |
| 3 X 300 | 20.4 | 3.4 | 0.1 | 1.8 | 0.5 | 3.0 | 77.5 | 6.86 | 12.42 |
| 3 X 400 | 23.2 | 3.4 | 0.1 | 1.9 | 0.8 | 3.2 | 85.4 | 8.97 | 16.05 |
| 3 X 500 | 26.4 | 3.4 | 0.1 | 2.0 | 0.8 | 3.4 | 93.7 | 10.65 | 19.50 |
3)8.7/10(15)kV,Three Cores,Al or Cu/XLPE/CTS/STA/PVC Armoured Power Cable
| No.X Nominal Cross Section of Conductor | Nominal Diameter of Conductor | Nominal Thickness of Insulation | Nominal Thickness of Copper Tape Screen | Nominal Thickness of Inner Sheath | Nominal Thickness of Steel Tape Armouring | Nominal Thickness of PVC Sheath | Approx. Overall Diameter | Approx. Weight | |
| Al Conductor | Cu Conductor | ||||||||
| No. X mm2 | mm | mm | mm | mm | mm | mm | mm | kg/m | kg/m |
| 3 X 25 | 6.0 | 4.5 | 0.1 | 1.4 | 0.5 | 2.1 | 48.6 | 2.53 | 2.98 |
| 3 X 35 | 6.9 | 4.5 | 0.1 | 1.4 | 0.5 | 2.2 | 50.7 | 2.76 | 3.39 |
| 3 X50 | 8.2 | 4.5 | 0.1 | 1.5 | 0.5 | 2.3 | 53.9 | 3.10 | 3.95 |
| 3 X 70 | 9.7 | 4.5 | 0.1 | 1.5 | 0.5 | 2.4 | 57.4 | 3.51 | 4.74 |
| 3 X 95 | 11.3 | 4.5 | 0.1 | 1.5 | 0.5 | 2.6 | 61.2 | 4.05 | 5.75 |
| 3 X 120 | 12.8 | 4.5 | 0.1 | 1.6 | 0.5 | 2.6 | 64.7 | 4.56 | 6.72 |
| 3 X 150 | 14.2 | 4.5 | 0.1 | 1.6 | 0.5 | 2.7 | 67.9 | 5.04 | 7.74 |
| 3 X 185 | 15.9 | 4.5 | 0.1 | 1.7 | 0.5 | 2.8 | 71.9 | 5.66 | 9.04 |
| 3 X 240 | 18.3 | 4.5 | 0.1 | 1.8 | 0.5 | 3.0 | 77.7 | 6.56 | 11.00 |
| 3 X 300 | 20.4 | 4.5 | 0.1 | 1.9 | 0.8 | 3.2 | 84.1 | 8.39 | 13.96 |
| 3 X 400 | 23.2 | 4.5 | 0.1 | 2.0 | 0.8 | 3.3 | 90.5 | 9.71 | 16.79 |
| 3 X 500 | 26.4 | 4.5 | 0.1 | 2.1 | 0.8 | 3.5 | 98.8 | 11.45 | 20.57 |
4)12/20(24)kV, 12.7/22(24)kV,Three Cores,Al or Cu/XLPE/CTS/STA/PVC Armoured Power Cable
| No.X Nominal Cross Section of Conductor | Nominal Diameter of Conductor | Nominal Thickness of Insulation | Nominal Thickness of Copper Tape Screen | Nominal Thickness of Inner Sheath | Nominal Thickness of Steel Tape Armouring | Nominal Thickness of PVC Sheath | Approx. Overall Diameter | Approx. Weight | |
| Al Conductor | Cu Conductor | ||||||||
| No. X mm2 | mm | mm | mm | mm | mm | mm | mm | kg/m | kg/m |
| 3 X 25 | |||||||||
| 3 X 35 | 6.9 | 5.5 | 0.1 | 1.5 | 0.5 | 2.4 | 55.6 | 3.14 | 3.77 |
| 3 X50 | 8.2 | 5.5 | 0.1 | 1.5 | 0.5 | 2.5 | 58.6 | 3.49 | 4.34 |
| 3 X 70 | 9.7 | 5.5 | 0.1 | 1.5 | 0.5 | 2.6 | 62.1 | 3.93 | 5.16 |
| 3 X 95 | 11.3 | 5.5 | 0.1 | 1.6 | 0.5 | 2.6 | 65.7 | 4.46 | 6.16 |
| 3 X 120 | 12.8 | 5.5 | 0.1 | 1.7 | 0.5 | 2.7 | 69.4 | 5.00 | 7.15 |
| 3 X 150 | 14.2 | 5.5 | 0.1 | 1.7 | 0.5 | 2.8 | 72.6 | 5.49 | 8.19 |
| 3 X 185 | 15.9 | 5.5 | 0.1 | 1.8 | 0.5 | 3.0 | 76.9 | 6.16 | 9.53 |
| 3 X 240 | 18.3 | 5.5 | 0.1 | 1.9 | 0.8 | 3.2 | 83.9 | 7.87 | 12.31 |
| 3 X 300 | 20.4 | 5.5 | 0.1 | 2.0 | 0.8 | 3.2 | 88.6 | 8.96 | 14.52 |
| 3 X 400 | 23.2 | 5.5 | 0.1 | 2.1 | 0.8 | 3.5 | 95.4 | 10.35 | 17.43 |
| 3 X 500 | 26.4 | 5.5 | 0.1 | 2.2 | 0.8 | 3.7 | 103.7 | 12.45 | 20.23 |
5)18/30(36)kV,19/33(36)kV,Three Cores,Al or Cu/XLPE/CTS/STA/PVC Armoured Power Cable
| No.X Nominal Cross Section of Conductor | Nominal Diameter of Conductor | Nominal Thickness of Insulation | Nominal Thickness of Copper Tape Screen | Nominal Thickness of Inner Sheath | Nominal Thickness of Steel Tape Armouring | Nominal Thickness of PVC Sheath | Approx. Overall Diameter | Approx. Weight | |
| Al Conductor | Cu Conductor | ||||||||
| No. X mm2 | mm | mm | mm | mm | mm | mm | mm | kg/m | kg/m |
| 3 X 25 | |||||||||
| 3 X 35 | |||||||||
| 3 X50 | 8.2 | 8.0 | 0.1 | 1.7 | 0.5 | 2.8 | 70.4 | 4.56 | 5.41 |
| 3 X 70 | 9.7 | 8.0 | 0.1 | 1.7 | 0.5 | 2.9 | 73.9 | 5.04 | 6.26 |
| 3 X 95 | 11.3 | 8.0 | 0.1 | 1.8 | 0.5 | 3.0 | 77.7 | 5.62 | 7.32 |
| 3 X 120 | 12.8 | 8.0 | 0.1 | 1.9 | 0.8 | 3.2 | 82.8 | 6.99 | 9.15 |
| 3 X 150 | 14.2 | 8.0 | 0.1 | 1.9 | 0.8 | 3.2 | 85.8 | 7.56 | 10.26 |
| 3 X 185 | 15.9 | 8.0 | 0.1 | 2.0 | 0.8 | 3.3 | 89.9 | 8.30 | 11.67 |
| 3 X 240 | 18.3 | 8.0 | 0.1 | 2.1 | 0.8 | 3.5 | 95.7 | 9.36 | 13.79 |
| 3 X 300 | 20.4 | 8.0 | 0.1 | 2.2 | 0.8 | 3.6 | 100.6 | 10.51 | 16.07 |
| 3 X 400 | 23.2 | 8.0 | 0.1 | 2.3 | 0.8 | 3.8 | 107.2 | 11.99 | 19.07 |
| 3 X 500 | 26.4 | 8.0 | 0.1 | 2.4 | 0.8 | 4.0 | 120.1 | 14.15 | 23.85 |
We are China Mv Voltage XLPE Insulated Swa Armoured Power Cable manufacture and supplier,You can get more details with Email,you will get cheap price or factory price.
Get Latest Price Request a quote
Popular Cable Products
ASTM Standard Peachbell/Rose/Iris Bare Conductor AAC Conductor
Cable CCA Duplex XLPE Insulated ABC Overhead Cable
Low Loss 40% Aluminum-Clad Steel Strand Power Cable for Smart Grid with CE
Aerial Bundle Cable ABC Cable Size Type Overhead
Control Cable with Cooper Core and Plastic Insulation
0.6/1kv AAC Aluminum Aerial Bundled Cable Overhead Cable Electrical Wire Cable
Popular jpcable99 Products
High Quality Stranded Galvanized Steel Wire
16 mm 2 Core Aluminium Cable AAC/XLPE
Aluminium Clad Stainless Steel Tube Opgw Fiber Optic Cable
Super Thermal Resistant High Strength Stacir Aluminium Clad Invar Wire
High Quality XLPE Insulated Power Cable
Popular Mv Voltage XLPE Insulated Swa Armoured Power Cable Products
Popular Power Cable Products
1kv 3+1 Core or 4 Core PVC Insualted PVC Sheathed Copper Core Electrical Cable Nyy
Yjv Yjlv 0.6/1kv Cu/XLPE/PVC Electrical Power Cable
Voltage 1000V AC Overhead Al/Cu Conductor XLPE ABC Cable with Standards
0.6/1kv Multi-Core Copper Conductor PVC Insulated Power Cable
CV-Awa, Power Cable, 0.6/1 Kv, 1/C, Cu/XLPE/PVC/Awa/PVC (IEC 60502-1)
Tags: Cable, jpcable99, Mv Voltage XLPE Insulated Swa Armoured Power Cable, Power Cable