Overhead Conductor Power Transmission Line ACSR
Overhead Conductor Power Transmission Line ACSR image
Get Latest Price Request a quote
Quick Details
Product Details
(1),Brief Description
ACSR conductor consists of a solid or stranded steel core surrounded by strands of aluminium (E.C.GRADE).
(2),Application
Widely used in power transmission lines with various voltage levels, because they have such good characteristics as simple structure, convenient installation and maintenance, low cost large transmission capacity. And they are also suitable for laying across rivers valleys and the places where special geographical features exist.
(3),Package
Wooden drum or Iron drum.
Service Performance
(1). The permissible long-time operating temperature for aerial conductor is 70oC.
(2). Under the circumstance that rare climate is occuring and ice coverage rate low in heavy ice area, the biggest stress of cable at the lowest point of the sag should not exceed 60% of the short-time destructive power.
(3). When connecting conductors, the conductor beside the connecting tube cant be prominent. Otherwise, the force on the operating conductors will be unbalanced. After connectors are install, the connecting tube should be painted by moisture-proof varnish in order to protect it from corrosion.
(4). Under installaion, the arc downing stress of all the conductors should be the same. With in the permissible distance of crossing buildings or dropping to the ground, the stress can be 10-15% higher than regular stress.
Product Performance
(1). The electrical performance of AAC and ACSR is indicated in DCΩ /km(20oC). The resistivity of the hard aluminum wire for stranded wires is not greater than 28.264 nΩ . M of international standard value.
(2). The rated tensile strength of AAC is denoted with the result of total cross-section of all aluminum conductors multiplied by min. Tensile of corresponding size specified in the standard for aluminum wire.
(3). The rated tensile strengh of ACSR is denoted with sum of all aluminum conductorstensile strength and steels tensile strength.
A. The tensile strength of all aluminum conductors is denoted with the result of all cross-sections of aluminum conductors multiplied by min. Tensile strength of corresponding size specified in the standard for aluminum wire.
B. The tensile strength of all steel wire is denoted with the result of all cross-sections of steel wires multiplied by the stress at 1% elongation of corresponding size specified in the standard for steel wire.
Execute Standards
(1). ASTM B 232/B 232M:Concentric-Lay-Stranded Aluminum Conductors, Coated-Steel Reinforced (ACSR)
(2). AS 3607:Conductors-Bare overhead, aluminium and aluminium alloy-Steel reinforced
(3). IEC 61089:Round wire concentric lay overhead electrical conductors
(4). DIN 48.204:Steel reinforced aluminium stranded conductor
(5). BS 215-2:Aluminium conductors and aluminium conductors, steel-reinforced-For overhead power transmission-Part 2:Aluminium conductors, steel-reinforced
(6). BS EN 50182:Conductors for overhead lines-Round wire concentric lay stranded conductors
(7). Production can be arranged according to customers requirements’ for material standard, etc.
Bare Conductor Types
(1) all aluminum conductor (AAC)
(2) all aluminum alloy conductor(AAAC)
(3) aluminum conductor steel reinforced (ACSR)
(4) anti-corrosion type ACSR
(5) aluminum conductor aluminum clad steel reinforced(ACSR/AW)
(6)rear earth aluminum conductor steel reinforced(ACSR/RE)
(7)aluminum conductor aluminum alloy reinforced(ACAR)
Huatong Cable Inc.
(1) ,More than 30 years experience.
(2) ,100,000m² factory,200 staffs,annual output 100,000 metic tons.
(3) ,Sound Quality Control
– Material inspection;
– manufacturing inspection;
– Finished products inspection;
– Inspection before delivery.
– Third party inspection.
– Inspection of storage at port of departure.
(4),ISO Certificated.
(5),Plenty of material and lobor gurantee the delivery prompt and price competitive.
(6),24/7 service.
| Code Name | Size | No./Dia.of Stranding Wires | Approx. Overall Dia. | Approx. Weight | Code Name | Size | No./Dia.of Stranding Wires | Approx. Overall Dia. | Approx. Weight | ||
| AWG or MGM | Alum. | ST. | AWG or MGM | Alum. | ST. | ||||||
| No./mm | No./mm | mm | kg/km | No./mm | No./mm | mm | kg/km | ||||
| Swanate | 4 | 7/1.96 | 1/2.61 | 6.53 | 93 | Tern | 795 | 45/3.38 | 7/2.25 | 27.03 | 1300 |
| Sparrow | 2 | 6/2.67 | 1/2.67 | 8.01 | 129 | Condor | 795 | 54/3.08 | 7/3.08 | 27.72 | 1461 |
| Sparate | 2 | 7/2.47 | 1/3.30 | 8.24 | 148 | Cuckoo | 795 | 24/4.62 | 7/3.08 | 27.74 | 1461 |
| Robin | 1 | 6/3.00 | 1/3.00 | 9.00 | 163 | Drake | 795 | 26/4.44 | 7/3.45 | 28.11 | 1550 |
| Raven | 1/0 | 6/3.37 | 1/3.37 | 10.11 | 206 | Coot | 795 | 36/3.77 | 1/3.77 | 26.41 | 1184 |
| Quail | 2/0 | 6/3.78 | 1/3.78 | 11.34 | 259 | Mallard | 795 | 30/4.14 | 19/2.48 | 28.96 | 1728 |
| Pigeon | 3/0 | 6/4.25 | 1/4.25 | 12.75 | 327 | Ruddy | 900 | 45/3.59 | 7/2.40 | 28.73 | 1472 |
| Penguin | 4/0 | 6/4.77 | 1/4.77 | 14.31 | 412 | Canary | 900 | 54/3.28 | 7/3.28 | 29.52 | 1554 |
| Waxwing | 266.8 | 18/3.09 | 1/3.09 | 15.45 | 422 | Rail | 954 | 45/3.70 | 7/2.47 | 29.61 | 1560 |
| Merlin | 336.4 | 18/3.47 | 1/3.47 | 17.35 | 532 | Catbird | 954 | 36/4.14 | 1/4.14 | 28.95 | 1421 |
| Linnet | 336.4 | 26/2.89 | 7/2.25 | 18.31 | 656 | Cardinal | 954 | 54/3.38 | 7/3.38 | 30.42 | 1753 |
| Oriole | 336.4 | 30/2.69 | 7/2.69 | 18.83 | 737 | Ortlan | 1033.5 | 45/3.85 | 7/2.57 | 30.81 | 1690 |
| Chickadee | 397.5 | 18/3.77 | 1/3.77 | 18.85 | 629 | Tanager | 1033.5 | 36/4.30 | 1/4.30 | 30.12 | 1539 |
| Ibis | 397.5 | 26/3.14 | 7/2.44 | 19.88 | 775 | Curlew | 1033.5 | 54/3.52 | 7/3.52 | 31.66 | 1900 |
| Lark | 397.5 | 30/2.92 | 7/2.92 | 20.44 | 871 | Bluejay | 1113 | 45/4.00 | 7/2.66 | 31.86 | 1821 |
| Pelican | 477 | 18/4.14 | 1/4.14 | 20.70 | 754 | Bunting | 1192.5 | 45/4.14 | 7/2.76 | 33.12 | 1949 |
| Flicker | 477 | 24/3.58 | 7/2.39 | 21.49 | 877 | Grackle | 1192.5 | 54/3.77 | 19/2.27 | 33.97 | 2190 |
| Hawk | 477 | 26/3.44 | 7/2.67 | 21.80 | 931 | Bittern | 1272 | 45/4.27 | 7/2.85 | 34.17 | 2080 |
| Hen | 477 | 30/3.20 | 7/3.20 | 22.40 | 1044 | Pheasant | 1272 | 54/3.90 | 19/2.34 | 35.10 | 2335 |
| Osprey | 556.5 | 18/4.47 | 1/4.47 | 22.35 | 880 | Skylark | 1272 | 36/4.78 | 1/4.78 | 33.42 | 1895 |
| Parakeet | 556.5 | 24/3.87 | 7/2.58 | 23.22 | 1023 | Dipper | 1351.5 | 45/4.40 | 7/2.92 | 35.16 | 2210 |
| Dove | 556.5 | 26/3.72 | 7/2.89 | 23.55 | 1085 | Martin | 1351.5 | 54/4.02 | 19/2.41 | 36.17 | 2481 |
| Eagle | 556.5 | 30/3.46 | 7/3.46 | 24.21 | 1219 | Bobolink | 1431 | 45/4.53 | 7/3.02 | 36.24 | 2342 |
| Peacock | 605 | 24/4.03 | 7/2.69 | 24.20 | 1112 | Plover | 1431 | 54/4.14 | 19/2.48 | 37.24 | 2628 |
| Squab | 605 | 26/3.87 | 7/3.01 | 24.51 | 1180 | Nuthatch | 1510.5 | 45/4.65 | 7/3.10 | 37.20 | 2470 |
| WoodDuck | 605 | 30/3.61 | 7/3.61 | 25.25 | 1325 | Parrot | 1510.5 | 54/4.25 | 19/2.55 | 38.25 | 2773 |
| Kingbird | 636 | 18/4.78 | 1/4.78 | 23.88 | 1007 | Lapwing | 1590 | 45/4.77 | 7/3.18 | 38.16 | 2599 |
| Rook | 636 | 24/4.14 | 7/2.76 | 24.84 | 1170 | Falcon | 1590 | 54/4.36 | 19/2.62 | 39.26 | 2920 |
| Grosbeak | 636 | 26/3.97 | 7/3.09 | 25.15 | 1240 | Grouse | 80.0 | 8/2.54 | 1/4.242 | 9.32 | 204 |
| Scoter | 636 | 30/3.70 | 7/3.70 | 25.88 | 1393 | Petrel | 101.6 | 12/2.339 | 7/2.339 | 11.7 | 342 |
| Swift | 636 | 36/3.38 | 1/3.38 | 23.62 | 947 | Minorca | 110.8 | 12/2.441 | 7/2.441 | 12.20 | 373 |
| Flamingo | 666.6 | 24/4.23 | 7/2.82 | 25.40 | 1226 | Leghorn | 134.6 | 12/2.69 | 7/2.69 | 13.45 | 453 |
| Gannet | 666.6 | 26/4.07 | 7/3.16 | 25.76 | 1300 | Guinea | 159.0 | 12/2.924 | 7/2.924 | 14.62 | 535 |
| Stilt | 715.5 | 24/4.39 | 7/2.92 | 26.31 | 1316 | Dotterel | 176.9 | 12/3.084 | 7/3.084 | 15.42 | 595 |
| Starling | 715.5 | 26/4.21 | 7/3.28 | 26.68 | 1396 | Dorking | 190.8 | 12/3.203 | 7/3.203 | 16.01 | 642 |
| Redwing | 715.5 | 30/3.92 | 19/2.35 | 27.43 | 1553 | Brahma | 203.2 | 16/2.863 | 19/2.482 | 18.13 | 900 |
| Cochin | 211.3 | 12/3.371 | 7/3.371 | 16.85 | 711 | ||||||
We are China Overhead Conductor Power Transmission Line ACSR manufacture and supplier,You can get more details with Email,you will get cheap price or factory price.
Get Latest Price Request a quote
Popular Cable Products
ABC Aluminum Conductor XLPE Insulation Aerial Bunded ABC Cable
Low Smoke Halogen Free 4 Core Cu / Mica Tape / XLPE / Lsoh Fire Retardant Cable
Primary Shielded and Concentric Neutral Power Cable Manufacturer
450/750V Yq/Yqw Light Model Rubber Sheath Flexible Cable
Popular 0.6/1kv Copper Core XLPE/PVC Insulated Steel Amoured Cable Power Cable for Underground Cable
ASTM Standard ACSR Aluminum Moose Bare Conductor 300mm2
Popular Conductor Products
Aluminum Alloy Bare Conductor Overhead AAAC Conductor
Wholesale Aluminum Alloy Bare AAAC Conductor Price
ABC Electrical Cable Aluminium Cables
Hdbc, Stranded Bare Copper Conductor (AS 1746)
ASTM Standard Overhead Cable Robin ACSR Conductor
Popular huatongcable Products
Power Transmission Line Electrical Power Cable ABC Cable
China Acar Aluminium Conductor Acar 800 Mcm
Aluminum AAC Conductor Power Cable
Building Wire, PVC Insulated Single Core Wire, Electric Wire
Stranded Aluminum Clad Steel Wire 7 No 8AWG. (ACS)
IEC 60502-2 Three Core XLPE Insualted Armour 12.7/22kv Copper Cable
Popular Overhead Conductor Products
Bare Cable ACSR Aluminum Conductor Steel Reinforced ACSR Moose Conductor
AAAC Overhead Aluminum Bare Conductor AAC
ACSR Aluminum Conductor Steel Reinforced Conductor Arerial Cable
Wolf Zebra Fox Beaver Tiger Bear Moose ASTM ACSR Conductor ACSR Cable
USA Sizes ASTM B399 All Aluminum Alloy Condcutor AAAC Canton
Tags: Cable, Conductor, huatongcable, Overhead Conductor