Power Cables PVC Insulation 0, 66 Kv Cable Nyy, Nym, Nyby, Nayy, Nayby
Power Cables PVC Insulation 0, 66 Kv Cable Nyy, Nym, Nyby, Nayy, Nayby image
Get Latest Price Request a quote
Quick Details
Product Details
Power cables with PVC insulation 0,66 kV – NYY, NYM, NYBY, NAYY, NAYBY
Cables are designated for power supply and distribution in fixed installations with rated AC voltage 0.66 kV at frequency 50 Hz at ambient temperature from -50 °C to +50 °C and relative humidity up to 98% at temperature up to 35 °C, cables are intended for laying in outdoors including. NYM and NAYY-J cables are designated for fixed connection to electric devices at nominal AC voltage up to 0.66 kV at frequency 50 Hz. Cables are used for connection to devices requiring input sealing.
Description
Cables are designated for power supply and distribution in fixed installations with rated AC voltage 0.66 kV at frequency 50 Hz at ambient temperature from -50 °C to +50 °C and relative humidity up to 98% at temperature up to 35 °C, cables are intended for laying in outdoors including. NYM and NAYY-J cables are designated for fixed connection to electric devices at nominal AC voltage up to 0.66 kV at frequency 50 Hz. Cables are used for connection to devices requiring input sealing.
CONDUCTORS
Copper or aluminum round single-wire or multicore conductors (class 1 in accordance with IEC 60228(2004).
INSULATION AND OVERSHEATH
Insulation and oversheath are made from polyvinylchloride (PVC) compound.
COVERING
IN ACCORDANCE WITH IEC 60229 Armour is made from 2 galvanized steel tapes and PVC compound oversheath is applied over wrapping.
Technical specifications
| Number of conductors | Nominal conductor crosssection (mm²) | |
| NYY | 1. 2. 3. 4 | 1,5 – 50 |
| NYM | 2. 3. 4 | 1,5 – 50 |
| NAYY | 1. 2. 3. 4 | 2,5 – 50 |
| NAYM | 2. 3. 4 | 2,5 – 50 |
| NYY | 5 | 1,5 – 25 |
| NYBY,NAYBY | 2. 3. 4 | 4,0- 50 |
Insulation resistance calculated for 1 km at temperature 20 °C:
| Nominal conductor cross-section (mm²) | IInsulation resistance, MOhm, no less |
|---|---|
| 1 – 1.5 | 12 |
| 2.5 – 4 | 10 |
| 6 | 9 |
| 10 – 50 | 7 |
Insulation resistance calculated for 1 km at
temperature 20 °C indicated at protractedly
permissible temperature for the conductors
heating at operational period at least
0.005 MOhm.
Cables endure AC 3.0 kV test and 50 Hz
frequency during 10 minutes.
Cables are flame retardant with a single
laying.
Manufactured cable length:
– manufactured cable length must be min.
450 m for cables with main conductor crosssection
1.5-16 mm²;
– manufactured cable length must be min.
300 m for cables with main conductor crosssection
25-50 mm².
Minimal temperature of cable laying without
pre-heating: – 15 °C.
Minimum permissible bending radius of the
cable at installation and routing must equal
to min. 10 outer diameters of the cable for
single-core cable, and min.7.5 outer diameters
of the cable – for multicore cables.
Permissible current loads and permissible short-circuit currents for cables with copper conductors:
| Nominal conductor cross-section(mm²) |
Permissible current loads (A) | Permissible shortcircuit currents (kA) |
|||||
|---|---|---|---|---|---|---|---|
| Single-core cables | Double-core cables | Three-core cables* | |||||
| above ground |
under ground |
above ground |
under ground |
above ground |
under ground |
||
| 1.5 | 29 | 32 | 24 | 33 | 21 | 28 | 0.17 |
| 2.5 | 40 | 42 | 33 | 44 | 28 | 37 | 0.27 |
| 4 | 53 | 54 | 44 | 56 | 37 | 48 | 0.43 |
| 6 | 67 | 67 | 56 | 71 | 49 | 58 | 0.65 |
| 10 | 91 | 89 | 76 | 94 | 66 | 77 | 1.09 |
| 16 | 121 | 116 | 101 | 123 | 87 | 100 | 1.74 |
| 25 | 160 | 148 | 134 | 157 | 115 | 130 | 2.78 |
| 35 | 197 | 178 | 166 | 190 | 141 | 158 | 3.86 |
| 50 | 247 | 217 | 208 | 230 | 177 | 192 | 5.23 |
*The same and for four-core cables with neutral conductor lower cross-section. For determining of current loads (four-core cables) which are
equal to cross-section of four-wire networks in all loads in normal mode this loads must be multiplied by 0.93 coefficient.
Permissible current loads and permissible short-circuit currents for cables with aluminum conductors:
| Nominal conductor cross-section(mm²) |
Permissible current loads (A) | Permissible shortcircuit currents (kA) |
|||||
|---|---|---|---|---|---|---|---|
| Single-core cables | Double-core cables | Three-core cables* | |||||
| above ground |
under ground |
above ground |
under ground |
above ground |
under ground |
||
| 2,5 | 30 | 32 | 25 | 33 | 21 | 28 | 0,18 |
| 4 | 40 | 41 | 34 | 43 | 29 | 37 | 0,29 |
| 6 | 51 | 52 | 43 | 54 | 37 | 44 | 0,42 |
| 10 | 69 | 68 | 58 | 72 | 50 | 59 | 0,70 |
| 16 | 93 | 83 | 77 | 94 | 67 | 77 | 1,13 |
| 25 | 122 | 113 | 103 | 120 | 88 | 100 | 1,81 |
| 35 | 151 | 136 | 127 | 145 | 109 | 121 | 2,50 |
| 50 | 189 | 166 | 159 | 176 | 136 | 147 | 3,38 |
*The same and for four-core cables with neutral conductor lower cross-section. For determining of current loads (four-core cables) which are
equal to cross-section of four-wire networks in all loads in normal mode this loads must be multiplied by 0.93 coefficient.
More information and other cable inquiry, pls contact Vivian Yuan as follows:
Vivian Yuan
Mobile: +86 158 3829 0725
We are China Power Cables PVC Insulation 0, 66 Kv Cable Nyy, Nym, Nyby, Nayy, Nayby manufacture and supplier,You can get more details with Email,you will get cheap price or factory price.
Get Latest Price Request a quote
Popular Cu/PVC/PVC Products
16 Cores 1mm2 2.5mm2 4mm2 Flexible PVC Control Cable
Low Voltage Power Cable with PVC Insulation Yby-O; Yby-J
Cu/PVC/PVC 300/500V PVC Insulated PVC Sheathed H05VV-F Flexible Electrical Cable
Cu/PVC/PVC Cable 450/750V No. 7 Wire Strand Core Rvv Cable
0, 6/1kv PVC Power Cable with Nyy Nym Rvv VV VV22
0.6/1kv 7 Core 0.75mm2 Kvv Control Cable
Popular Nyy Cable Products
Insulated Electrical Cable Wire Nyy Nyyhy 3X25mm Cu PVC Power Cable
0.6/1kv Cu XLPE Insulated Copper Aluminum Conductor PVC Armored Power Electrical Cable
600/1000V Low Voltage PVC Insualted 5 Cores Steel Tape Armored Electric Cable
Nyy Cable 10 Sqmm 3 Core Cable 3 Core 1.5mm2 Flexible Cable
N2xy, N2xy-O, N2xy-J Copper XLPE Insulated PVC Sheathed Al Wire Armour Power Cable
Waterproof 50mm2 XLPE Electrical Cables Prices
Popular Power Cable Products
3 Core Copper Cable Flexible Electrical Wire
Nyy LV Insulted Power Electrical Cable Wire
Cooper Conductor UV Resistant XLPE Cable 3X95mm2 3X120mm 3X240mm Low Voltage XLPE Underground Cable
Photovoltaic Cable, Power Cable, Al 8000/XLPE (UL 44/ICEA S-95-658/NEMA WC70)
11kv Power Cable Copper Conductor Galvanized Steel Wire Armour 3X150mm2
Low Voltage Aluminum Conductor Cable Bare Conductor ASTM B498
Popular zzhongdacable Products
Aluminum Conductor XLPE Insulated and Hffr Sheath Na2xh Power Cable
Bare Copper Wires 750 V PVC Insulated Bwf Flexible Cable
Self-Supporting Insulated Overhead Wire Cable SIP-4 2X16 4X16 4X25 4X35
16mm2 Concentric Aluminum Cables with 2 Core Copper Communication Cable
Customized Electric Copper Clad Steel Wire
Nyby Armored Cable Dsta Armored Cable Steel Tap Armored Cable
Tags: Cu/PVC/PVC, Nyy Cable, Power Cable, zzhongdacable