Power cables with PVC insulation 0,66 kV – NYY, NYM, NYBY, NAYY, NAYBY
Cables are designated for power supply and distribution in fixed installations with rated AC voltage 0.66 kV at frequency 50 Hz at ambient temperature from -50 °C to +50 °C and relative humidity up to 98% at temperature up to 35 °C, cables are intended for laying in outdoors including. NYM and NAYY-J cables are designated for fixed connection to electric devices at nominal AC voltage up to 0.66 kV at frequency 50 Hz. Cables are used for connection to devices requiring input sealing.
Description
Cables are designated for power supply and distribution in fixed installations with rated AC voltage 0.66 kV at frequency 50 Hz at ambient temperature from -50 °C to +50 °C and relative humidity up to 98% at temperature up to 35 °C, cables are intended for laying in outdoors including. NYM and NAYY-J cables are designated for fixed connection to electric devices at nominal AC voltage up to 0.66 kV at frequency 50 Hz. Cables are used for connection to devices requiring input sealing.
CONDUCTORS
Copper or aluminum round single-wire or multicore conductors (class 1 in accordance with IEC 60228(2004).
INSULATION AND OVERSHEATH
Insulation and oversheath are made from polyvinylchloride (PVC) compound.
COVERING
IN ACCORDANCE WITH IEC 60229 Armour is made from 2 galvanized steel tapes and PVC compound oversheath is applied over wrapping.
Technical specifications
Number of conductors | Nominal conductor crosssection (mm²) | |
NYY | 1. 2. 3. 4 | 1,5 – 50 |
NYM | 2. 3. 4 | 1,5 – 50 |
NAYY | 1. 2. 3. 4 | 2,5 – 50 |
NAYM | 2. 3. 4 | 2,5 – 50 |
NYY | 5 | 1,5 – 25 |
NYBY,NAYBY | 2. 3. 4 | 4,0- 50 |
Insulation resistance calculated for 1 km at temperature 20 °C:
Nominal conductor cross-section (mm²) | IInsulation resistance, MOhm, no less |
---|---|
1 – 1.5 | 12 |
2.5 – 4 | 10 |
6 | 9 |
10 – 50 | 7 |
Insulation resistance calculated for 1 km at
temperature 20 °C indicated at protractedly
permissible temperature for the conductors
heating at operational period at least
0.005 MOhm.
Cables endure AC 3.0 kV test and 50 Hz
frequency during 10 minutes.
Cables are flame retardant with a single
laying.
Manufactured cable length:
– manufactured cable length must be min.
450 m for cables with main conductor crosssection
1.5-16 mm²;
– manufactured cable length must be min.
300 m for cables with main conductor crosssection
25-50 mm².
Minimal temperature of cable laying without
pre-heating: – 15 °C.
Minimum permissible bending radius of the
cable at installation and routing must equal
to min. 10 outer diameters of the cable for
single-core cable, and min.7.5 outer diameters
of the cable – for multicore cables.
Permissible current loads and permissible short-circuit currents for cables with copper conductors:
Nominal conductor cross-section(mm²) |
Permissible current loads (A) | Permissible shortcircuit currents (kA) |
|||||
---|---|---|---|---|---|---|---|
Single-core cables | Double-core cables | Three-core cables* | |||||
above ground |
under ground |
above ground |
under ground |
above ground |
under ground |
||
1.5 | 29 | 32 | 24 | 33 | 21 | 28 | 0.17 |
2.5 | 40 | 42 | 33 | 44 | 28 | 37 | 0.27 |
4 | 53 | 54 | 44 | 56 | 37 | 48 | 0.43 |
6 | 67 | 67 | 56 | 71 | 49 | 58 | 0.65 |
10 | 91 | 89 | 76 | 94 | 66 | 77 | 1.09 |
16 | 121 | 116 | 101 | 123 | 87 | 100 | 1.74 |
25 | 160 | 148 | 134 | 157 | 115 | 130 | 2.78 |
35 | 197 | 178 | 166 | 190 | 141 | 158 | 3.86 |
50 | 247 | 217 | 208 | 230 | 177 | 192 | 5.23 |
*The same and for four-core cables with neutral conductor lower cross-section. For determining of current loads (four-core cables) which are
equal to cross-section of four-wire networks in all loads in normal mode this loads must be multiplied by 0.93 coefficient.
Permissible current loads and permissible short-circuit currents for cables with aluminum conductors:
Nominal conductor cross-section(mm²) |
Permissible current loads (A) | Permissible shortcircuit currents (kA) |
|||||
---|---|---|---|---|---|---|---|
Single-core cables | Double-core cables | Three-core cables* | |||||
above ground |
under ground |
above ground |
under ground |
above ground |
under ground |
||
2,5 | 30 | 32 | 25 | 33 | 21 | 28 | 0,18 |
4 | 40 | 41 | 34 | 43 | 29 | 37 | 0,29 |
6 | 51 | 52 | 43 | 54 | 37 | 44 | 0,42 |
10 | 69 | 68 | 58 | 72 | 50 | 59 | 0,70 |
16 | 93 | 83 | 77 | 94 | 67 | 77 | 1,13 |
25 | 122 | 113 | 103 | 120 | 88 | 100 | 1,81 |
35 | 151 | 136 | 127 | 145 | 109 | 121 | 2,50 |
50 | 189 | 166 | 159 | 176 | 136 | 147 | 3,38 |
*The same and for four-core cables with neutral conductor lower cross-section. For determining of current loads (four-core cables) which are
equal to cross-section of four-wire networks in all loads in normal mode this loads must be multiplied by 0.93 coefficient.
More information and other cable inquiry, pls contact Vivian Yuan as follows:
Vivian Yuan
Mobile: +86 158 3829 0725
We are China Power Cables PVC Insulation 0, 66 Kv Cable Nyy, Nym, Nyby, Nayy, Nayby manufacture and supplier,You can get more details with Email,you will get cheap price or factory price.
Get Latest Price Request a quote
Popular Cu/PVC/PVC Products
0.6/1kv 7 Core 0.75mm2 Kvv Control Cable
Cu/PVC/PVC Cable 450/750V No. 7 Wire Strand Core Rvv Cable
0.6/1kv Flexible Control Cable 4 Sq. mm VV5-K Cable VV-K
Power Cables LV Svbt in Electrical Metropolitan Networks and Stations
0.6/1 Kv Cu PVC PVC Power Cable Nyy Kabel 3X185+95
IEC 60502-1 600/1000V Cu/PVC/PVC Insulated PVC Sheathed Single Core Nyy Power Cable
Popular Nyy Cable Products
0.6/1kv 3*35mm2 PVC Insulation PVC or PE Sheath Nyy Cable
Cu PVC PVC 4 Core Nyy Nym Cable 35mm 50mm 95mm 120mm
Nyy Electric Cable PVC Insulated PVC Sheath
Nyy, Cu/PVC/PVC Power Cable, 0.6/1kv, IEC/VDE,
Nyy, Nyy-J, Nyy-O Copper PVC Insulation PVC Sheath Power Cable
Nyy Nayy-J -O PVC PVC 0.6/1kv Direct Burial Underground Cable
Popular Power Cable Products
Electric Power Cable, Copper Conductor XLPE Insulated PVC Sheathed Power Cable.
Indoor PVC Sheathed Copper Core 2.5sqmm Electric Wire
1-35kv Copper Core XLPE Insulated PE Sheathed Unarmoured Power Cable
PVC Insulated PVC Sheath Electric Nyy Power Cable
All New Aluminum Conductor (AAC)
Fire Resistant Cable Made in Jinshui
Popular zzhongdacable Products
Double Solar Cable 2X6 mm DC Solar Cable Xlpo Insulated XLPE Jacket Wire
Low Voltage NFC 33209 Standard 5 Core Aerial Bundle ABC Cable 3X70+70+50 Overhead Insulated Cable
336.4-336.4-336.4-336.4 Bronco Quadruplex Overhead Aluminum Conductor Service Drop Cable
Copper Stranded Wire Electrical Cable Prices for Philippines 8mm2 14mm2 30mm2
AAAC All Aluminum Alloy Conductor Bare Overhead Conductor Cable
2*4AWG+4AWG Triplex Service Drop Cable Aluminum Conductor ABC Cable
Tags: Cu/PVC/PVC, Nyy Cable, Power Cable, zzhongdacable