Thw 600V PVC Insulated Building Wire with Copper Conductor
Thw 600V PVC Insulated Building Wire with Copper Conductor image
Get Latest Price Request a quote
Quick Details
Product Details
1. APPLICATION:
General purpose wiring for lighting and power – residential,
Commercial, industrial buildings in accordance with the National Electrical
Code, maximum conductor temperature of 75° C in wet or dry locations,
For circuits not exceeding 600 volts
2. STANDARDS:
(1). Listed by UL as Type THW per Standard 83.
(2). All sizes carry the VW-1 flame test designation.
(3). Listed by UL as Oil Resistant I.
(4). Listed by UL as Sunlight Resistant (250 kcmil and larger, black only)
(5).250 kcmil and larger pass UL and IEEE-383 ribbon burner flame test
And are listed For CT Use.
(6). Conforms to Federal Specification J-C-30B.
3. CONSTRUCTION:
Annealed uncoated copper conductor, PVC insulation, surface printed.
4. SPECIFICATION:
(1). SCOPE
This specification describes single conductor THW, a general purpose building wire insulated with polyvinyl chloride (PVC) intended for lighting and power circuits at 600 volts or less, in residential, commercial and industrial buildings. The wire may be operated at 75° C maximum continuous conductor temperature in wet or dry locations and is listed by Underwriters Laboratories for use in accordance with Article 310 of the National Electrical Code.
(2). APPLICABLE SPECIFICATIONS
A. The following specifications form a part of this specification to the extent specified herein:
B. Underwriters Laboratories Standard 83 for Thermoplastic Insulated Wires.
C. Federal Specification J-C-30B.
(3). CONDUCTORS
Conductors shall be solid or Class B stranded, annealed uncoated copper per UL Standard 83.
(4). INSULATION
Each conductor shall be insulated with PVC complying with the physical and electrical requirements of UL Standard 83 for Type THW. In addition, the PVC insulation shall comply with the optional Oil Resistant I listing of UL Standard 83.
4.2 The average thickness of insulation, for a given conductor size, shall be as specified in UL Standard 83 for Type THW wire. The minimum thickness at any point shall be not less than 90% of the specified average thickness.
The insulation shall be applied tightly to the conductor and shall be free-stripping.
(5). IDENTIFICATION
The wire shall be identified by surface marking indicating manufacturer’s identification, conductor size and metal, voltage rating, UL Symbol, type designation and optional ratings.
(6) . TESTS
Wire shall be tested in accordance with the requirements of UL Standard 83 for Type THW wire and for the optional Oil Resistant listing.
(7). LABELS
The wire shall bear the Underwriters Laboratories label for Type THW.
KINDLY NOTE: If you want to know more details about this kind of products, please visit our website:jytopcable.en. for further information. Thanks.
Ampacity in accordance with NEC for not more than these conductors in raceway, 750C conductor temperature and 300C ambient in wet or dry locations.
Size AWG or kcmil |
No. of strands | Insulation thickness mils |
Nominal Diameter inch |
NEC Ampacity |
Approx. weight (lbs/1000ft) | |
copper | Net | |||||
14 | Solid | 30 | 0.13 | 20 | 12 | 19 |
12 | Solid | 30 | 0.15 | 25 | 20 | 26 |
10 | Solid | 30 | 0.17 | 35 | 31 | 39 |
14 | 7 | 30 | 0.14 | 20 | 13 | 19 |
12 | 7 | 30 | 0.16 | 25 | 20 | 28 |
10 | 7 | 30 | 0.18 | 35 | 32 | 41 |
8 | 7 | 45 | 0.24 | 50 | 50 | 67 |
6 | 7 | 60 | 0.30 | 65 | 81 | 105 |
4 | 7 | 60 | 0.35 | 85 | 129 | 160 |
3 | 7 | 60 | 0.38 | 100 | 163 | 195 |
2 | 7 | 60 | 0.41 | 115 | 205 | 245 |
1 | 19 | 80 | 0.49 | 130 | 258 | 315 |
1/0 | 19 | 80 | 0.53 | 150 | 326 | 390 |
2/0 | 19 | 80 | 0.57 | 175 | 411 | 480 |
3/0 | 19 | 80 | 0.62 | 200 | 518 | 595 |
4/0 | 19 | 80 | 0.68 | 230 | 653 | 735 |
250 | 37 | 95 | 0.75 | 255 | 772 | 880 |
300 | 37 | 95 | 0.81 | 285 | 926 | 1040 |
350 | 37 | 95 | 0.86 | 310 | 1081 | 1205 |
400 | 37 | 95 | 0.90 | 335 | 1235 | 1365 |
500 | 37 | 95 | 0.98 | 380 | 1544 | 1685 |
600 | 61 | 110 | 1.09 | 420 | 1853 | 2030 |
750 | 61 | 110 | 1.18 | 475 | 2316 | 2510 |
1000 | 61 | 110 | 1.34 | 545 | 3088 | 3305 |
We are China Thw 600V PVC Insulated Building Wire with Copper Conductor manufacture and supplier,You can get more details with Email,you will get cheap price or factory price.
Get Latest Price Request a quote
Popular jytopcable Products
Overhead Bare Aluminium ACSR Conductor for ASTM BS IEC Standards
Low Voltage Twisted ABC Cable for Overhead Transmission Line
15kv-35kv Medium Voltage XLPE Insulated Underground Urd Power Cable
BS6004 Standard 450/750V BV Single-Core PVC Insulated Non-Sheathed Wire Cables
0.6/1kv Low Voltage N2xby Electric Cable
Popular PVC Building Wire Products
450/750V Copper Core PVC Building Wire
450/750V Wires, Electrical Wire High Quality PVC Cover Building Wire
PVC Insulated Building and Electric Wire Professional Supplier with ISO, CE Certificate
Thw PVC Insulated Electric Building Wire
450/750V Copper/Aluminum Conductor PVC Insulated Electric Cable, Building Wire,
Popular PVC Insualted Building Wire Products
Popular PVC Wire Products
Copper/PVC Insulated Electric Wires/Building Wire House Wire 1.5 2.5 4 6
House Electrical Wiring Diagram Heat Resistant Insulation for Electrical Thhn Wire
Conductor Rigid DIN Cupru Fy 1.5 mm (culori diferite) Clasa De Flexibilitate 1 Izolatie PVC
PVC Sheathed Round Flexible Connector Cable Wire
PVC Insulated Stranded Wire for Grounding PVC Electrical Wire
Tags: jytopcable, PVC Building Wire, PVC Insualted Building Wire, PVC Wire