3D Delta Core Dry-Type Transformer29 Power Transmission
3D Delta Core Dry-Type Transformer29 Power Transmission image
Get Latest Price Request a quote
Quick Details
Product Details
Suzhou Silverstone Electric Co., Ltd
1. General
(1) Application:
>> 12, 24,36KV~220kv class transformers
are widely used in power transmission and distribution stations,
industry plants, Generation Setup Unit (GSU).
>> They have the characteristic of high efficiency, low loss and maintenance free.
(2) Type and Rating
**Capacity range :50-50000KVA.
**Secondary voltage: 415V ,400V etc.
**Frequency :50Hz ,60Hz.
**Type: Single phase, three phase.
**No-load tap changer and on-load tap changer.
**ONAN and ONAF.
**Set-up and set-down type.
(3) Standard: IEC60076-1, IEC60076-2, IEC60076-5, IEC60317, ANSI, IEEE, AS, etc.
2. Conditions of service
(1) Altitude: Up to 1,000m above sea level.
(2) Ambient temperature:
**Max: +40ºC.
**Average (daily, Max.): +30ºC.
**Average (yearly, Max.): +20ºC.
**Min: -45ºC.
(3) Environment: Outdoor.
(4) Special conditions:
It may be consulted between manufacturer and customer.
3. Structural Features
(1) Iron core
The iron core is made of cold rolled grain oriented silicon steel sheet. Laminations are cut to length
on GEORG cut to- length line with step lap cut and automatic stacking functions.
The multistep lamination structure can reduce the loss and noise.
The steel sheet in the core limbs and yokes are clamped together by glass-epoxy bonds.
(2) Winding
High quality enameled or paper covered copper is used as conductor, the winding was made as
drum type, spiral type, improved spiral type, continuous type and interleaved type to ensure the insulation strength. Standard tapings are ±2*2.5%of the HV winding.
(3) Tank
The tank, cover and the conservator are made by corrugated steel plate. For the small transformers,
we use a deep tank and a cover, but for larger transformers, we manufacture bell type. The corrugated construction is a effective way for oil cooling.
(4) Insulation oil
The tanks are filled with high quality grade mineral oil as per IEC296 and it is PCB and PCT free.
The oil is used to help cooling the transformer. It is also used provide part of the electrical insulation between internal live parts.
(5) Tap changer
Tap changers are used to regulate the output voltage of the transformers to required levels. We
achieve this by changing the ratios of the transformer on the system by altering the number of turns in the HV winding. Tap changers can be on load (OLTC) or off load(OCTC).
(6) Assembly
The core and the windings assembled together from the active part of the transformer. The active
body assembled with multi-windings and identical pressure dry method adopted, effectively improved
the electrical strength and the ability to short circuit withstanding.
4. Test equipment
Strict test should be done according to IEC standard, by high technical equipment to ensure the
quality and the reliable of every transformer.
5. Technical Data of Typical Products
>S9, S10 series 10KV three phase off -load tap changer distribution transformer
Type | Rating KVA |
On-load loss (w) |
Load loss (w) |
I (%) |
UK (%) |
Dimension (mm) | Weight (kg) |
||
a | b | c | |||||||
S9-M-50/11 | 50 | 170 | 870 | 2.0 | 4.0 | 1215 | 660 | 1170 | 430 |
S9-M-250/11 | 250 | 560 | 3050 | 1.2 | 4.0 | 1190 | 815 | 1370 | 1115 |
S9-M-400/11 | 400 | 800 | 4300 | 1.0 | 4.0 | 1515 | 770 | 1580 | 1380 |
S9-M-500/11 | 500 | 960 | 5050 | 1.0 | 4.0 | 1635 | 840 | 1610 | 1600 |
S9-M-1000/11 | 1000 | 1700 | 10300 | 0.7 | 4.5 | 1960 | 1095 | 1960 | 2860 |
S9-M-2500/11 | 2500 | 3300 | 23000 | 0.55 | 5.5 | 2230 | 2305 | 2445 | 5660 |
S10-M-30/10 | 30 | 110 | 600 | 1.8 | 4.0 | 870 | 645 | 1025 | 310 |
S10-M-50/10 | 50 | 140 | 870 | 1.7 | 4.0 | 1090 | 650 | 1080 | 395 |
S10-M-80/10 | 80 | 200 | 1250 | 1.6 | 4.0 | 1140 | 675 | 1110 | 490 |
S10-M-100/10 | 100 | 240 | 1500 | 1.5 | 4.0 | 1185 | 690 | 1130 | 560 |
S10-M-125/10 | 125 | 280 | 1800 | 1.4 | 4.0 | 1205 | 710 | 1180 | 670 |
S10-M-160/10 | 160 | 340 | 2200 | 1.3 | 4.0 | 1255 | 720 | 1200 | 780 |
S10-M-200/10 | 200 | 400 | 2600 | 1.2 | 4.0 | 1295 | 740 | 1215 | 875 |
S10-M-250/10 | 250 | 470 | 3050 | 1.1 | 4.0 | 1340 | 755 | 1260 | 1115 |
S10-M-315/10 | 315 | 560 | 3650 | 1.0 | 4.0 | 1400 | 770 | 1320 | 1280 |
S10-M-400/10 | 400 | 680 | 4300 | 0.9 | 4.0 | 1500 | 860 | 1400 | 1490 |
S10-M-500/10 | 500 | 810 | 5150 | 0.9 | 4.0 | 1575 | 895 | 1430 | 1740 |
S10-M-630/10 | 630 | 1020 | 6200 | 0.8 | 4.5 | 1660 | 930 | 1545 | 2110 |
S10-M-800/10 | 800 | 1190 | 7500 | 0.7 | 4.5 | 1830 | 1070 | 1590 | 2625 |
S10-M-1000/10 | 1000 | 1450 | 10300 | 0.6 | 4.5 | 1935 | 1175 | 1685 | 2860 |
S10-M-1250/10 | 1250 | 1650 | 12000 | 0.6 | 4.5 | 1960 | 1170 | 1730 | 3330 |
S10-M-1600/10 | 1600 | 2040 | 14500 | 0.5 | 4.5 | 2325 | 1220 | 2120 | 3765 |
S10-M-2000/10 | 2000 | 2140 | 17820 | 0.5 | 4.5 | 2395 | 1260 | 2225 | 4530 |
>>S11 series 20KV three phase off -load tap changer distribution transformer
TYPE | Voltage ratio(kV) | Connection | No load Loss (W) |
Load loss (W) |
Io (%) |
UK (%) |
Dimensions (mm) | Weight (Kg) | |||||
a | b | c | d | e | f | ||||||||
S11-M-30/20 | 20(10) ±5%/0.4 |
Yyn0 Dyn11 |
100 | 690/ 660 |
2.1 | 5.5 |
1100 | 700 | 1240 | 14 | 400 | 400 | 640 |
S11-M-50/20 | 130 | 1010/ 960 |
2.0 | 1130 | 710 | 1260 | 14 | 400 | 450 | 710 | |||
S11-M-63/20 | 150 | 1200/1150 | 1.9 | 1160 | 740 | 1270 | 14 | 400 | 450 | 780 | |||
S11-M-80/20 | 180 | 1440/1370 | 1.8 | 1200 | 770 | 1280 | 14 | 400 | 450 | 860 | |||
S11-M-100/20 | 200 | 1730/ 1650 |
1.6 | 1220 | 800 | 1300 | 14 | 400 | 450 | 900 | |||
S11-M-125/20 | 240 | 2080/ 1980 |
1.5 | 1270 | 840 | 1330 | 19 | 550 | 450 | 970 | |||
S11-M-160/20 | 290 | 2540/ 2420 |
1.4 | 1320 | 870 | 1350 | 19 | 550 | 550 | 1100 | |||
S11-M-200/20 | 340 | 3000/ 2860 |
1.3 | 1360 | 900 | 1380 | 19 | 550 | 550 | 1240 | |||
S11-M-250/20 | 400 | 3520/ 3350 |
1.2 | 1430 | 910 | 1430 | 19 | 550 | 650 | 1420 | |||
S11-M-315/20 | 480 | 4210/ 4010 |
1.1 | 1460 | 920 | 1450 | 19 | 550 | 650 | 1570 | |||
S11-M-400/20 | 570 | 4970/ 4730 |
1.0 | 1490 | 940 | 1470 | 19 | 660 | 750 | 1740 | |||
S11-M-500/20 | 680 | 5940/ 5660 |
1.0 | 1570 | 970 | 1540 | 19 | 660 | 750 | 1950 | |||
S11-M-630/20 | 810 | 6820 | 0.9 | 6.0 |
1650 | 1000 | 1580 | 19 | 660 | 850 | 2290 | ||
S11-M-800/20 | 980 | 8250 | 0.8 | 1750 | 1070 | 1650 | 19 | 820 | 850 | 2690 | |||
S11-M-1000/20 | 1150 | 11330 | 0.7 | 1830 | 1170 | 1690 | 19 | 820 | 850 | 2880 | |||
S11-M-1250/20 | 1380 | 13200 | 0.7 | 1900 | 1200 | 1790 | 19 | 820 | 850 | 3400 | |||
S11-M-1600/20 | 1660 | 15950 | 0.6 | 1950 | 1250 | 1850 | 19 | 820 | 900 | 4100 |
>>>>S9 series 35kV three phase Off-load tap changer power transformer
Capacity KVA |
Voltage and tap range | Connection | No-load loss (kW) |
Load loss (KW) |
NO-load current (%) |
Impedance (%) |
Dimensions (mm) LxWxH |
||
HV (kV) | MV (kV) | LV (kV) | |||||||
50 | 35 | ± 5 | 0.4 | Dyn11 Yyn0 |
0.21 | 1.27/1.21 | 2.00 | 6.5 | 1100x845x1715 |
100 | 0.29 | 2.12/2.02 | 1.80 | 1190x915x1780 | |||||
125 | 0.34 | 2.50/2.38 | 1.70 | 1220x1040x1780 | |||||
160 | 0.36 | 2.97/2.83 | 1.60 | 1240x1070x1810 | |||||
200 | 0.43 | 3.50/3.33 | 1.50 | 1380x780x1875 | |||||
250 | 0.51 | 4.16/3.96 | 1.40 | 1540x880x1820 | |||||
315 | 0.61 | 5.01/4.77 | 1.40 | 1440x800x1975 | |||||
400 | 0.73 | 6.05/5.76 | 1.30 | 1660x825x1995 | |||||
500 | 0.86 | 7.28/6.93 | 1.20 | 1710x865x2030 | |||||
630 | 1.04 | 8.28 | 1.10 | 1630x1235x2070 | |||||
800 | 1.23 | 9.90 | 1.00 | 1655x1415x2120 | |||||
1000 | 1.44 | 12.15 | 1.00 | 1860x1435x2220 | |||||
1250 | 1.76 | 14.67 | 0.90 | 1890x1640x2260 | |||||
1600 | 2.12 | 17.55 | 0.80 | 2050x1720x2390 | |||||
630 | 3.15 6.3 10.5 |
Yd11 | 1.04 | 8.28 | 1.10 | 1630x1235x2070 | |||
800 | 1.23 | 9.90 | 1.00 | 1655x1415x2120 | |||||
1000 | 1.44 | 12.15 | 1.00 | 1860x1435x2220 | |||||
1250 | 1.76 | 14.67 | 0.90 | 1890x1640x2260 | |||||
1600 | 2.12 | 17.55 | 0.80 | 2050x1720x2390 | |||||
2000 | 2.72 | 19.35 | 0.70 | 2400x1900x2410 | |||||
2500 | 3.20 | 20.70 | 0.60 | 2500x1930x2700 | |||||
3150 | 35~ 38.5 |
± 5 | 3.15 6.3 10.5 |
3.80 | 24.30 | 0.56 | 7.0 | 2600x2100x2800 | |
4000 | 4.52 | 28.80 | 0.56 | 2830 x2350x2855 | |||||
5000 | 5.40 | 33.03 | 0.48 | 2930x2480x2930 | |||||
6300 | 6.56 | 36.90 | 0.48 | 7.5 | 3150x2330x3220 | ||||
8000 | ± 2 x 2.5 | 3.15 3.3 6.3 6.6 10.5 11 |
YNd11 | 9.00 | 40.50 | 0.42 | 3295x3110x3345 | ||
10000 | 10.88 | 47.70 | 0.42 | 3450x3210x3440 | |||||
12500 | 12.60 | 56.70 | 0.40 | 8.0 | 3620x3255x3500 | ||||
16000 | 15.20 | 69.30 | 0.40 | 3980x3420x3650 | |||||
20000 | 18.00 | 83.70 | 0.40 | 4030x3470x3690 | |||||
25000 | 21.28 | 99.00 | 0.32 | 5050x4640x3930 | |||||
31500 | 25.28 | 118.8 | 0.32 | 5120x4800x4030 |
>>>>S9 series 35kV three phase on-load tap changer power transformer
Type | Voltage compose and Tapping range (kV) | Connection |
No-load Loss (kW) |
Load loss (kW) |
No- load current (I%) |
Impedance voltage (%) | Transport weight (t) | Gross weight (t) | Dimensions L×W×H (mm) |
|
HV | LV | |||||||||
SZ9-2000/35 | 35 ±3×2.5% |
6.3 10.5 |
Yd11 | 2.88 | 18.7 | 1.00 | 6.5 | 4.93 | 5.97 | 3010×2070×2540 |
SZ9-2500/35 | 3.40 | 21.7 | 1.00 | 6.5 | 5.68 | 6.95 | 3040×2270×2610 | |||
SZ9-3150/35 | 4.04 | 26.0 | 0.90 | 7.0 | 6.08 | 7.90 | 3160×2300×2640 | |||
SZ9-4000/35 | 35 38.5 ±3×2.5% |
6.3 10.5 |
4.84 | 30.7 | 0.90 | 7.0 | 7.10 | 9.11 | 3300×2330×2890 | |
SZ9-5000/35 | 5.80 | 36.0 | 0.85 | 7.0 | 8.47 | 10.86 | 3350×2520×3000 | |||
SZ9-6300/35 | 7.04 | 38.7 | 0.85 | 7.5 | 9.87 | 12.30 | 3680×2650×3050 | |||
SZ9-8000/35 | 9.84 | 42.8 | 0.75 | 7.5 | 12.55 | 15.30 | 4190×2930×3280 | |||
SZ9-10000/35 | 35 38.5 ±3×2.5% |
6.3 6.6 10.5 11 |
Ynd11 |
11.6 | 50.6 | 0.75 | 7.5 | 14.70 | 17.86 | 4620×3160×3400 |
SZ9-12500/35 | 13.7 | 60.0 | 0.70 | 8.0 | 17.35 | 20.05 | 4740×3200×3540 | |||
SZ9-16000/35 | 16.0 | 73.0 | 0.70 | 8.0 | 19.45 | 23.74 | 4810×3360×3790 | |||
SZ9-20000/35 | 18.9 | 88.3 | 0.70 | 8.0 | 27.50 | 34.95 | 4880×3540×4150 | |||
SZ9-25000/35 | 22.4 | 104.4 | 0.65 | 8.0 | 32.51 | 40.22 | 4920×3920×4200 | |||
SZ9-31500/35 | 26.6 | 125.3 | 0.65 | 8.0 | 37.73 | 45.53 | 5010×4270×4460 |
We are China 3D Delta Core Dry-Type Transformer29 Power Transmission manufacture and supplier,You can get more details with Email,you will get cheap price or factory price.
Get Latest Price Request a quote
Popular Oil Transformet Products
Single-Phase Overhead Self Protected Pole Mounted Distribution Transformer
Dry Type 33kv Power Transformers with on-Load Tap Changer
30~1000kVA 11kv Dimensions with Protection Enclosure
Manufacturer 11kv 630~2500kVA Distribution Transformers
132kv Three Phase Tap Changer Power Transformers
Oil Immersed Distribution Transformer 20kv IEC Standard
Popular Power Transformer Products
132kv 126kv Tap Changing Oltc Traction Transformer
Manufacture 11-24kv Dry-Type Power Transformer
33kv and Above Rectifier Special Transformer Power Transformer
Medium Voltage Dry Type Distribution Transformer
Type Sc (B) 11-33kv Dry-Type Transformer
Three Phase Overhead Pole Mounted Distribution Transformer 11kv
Popular Rectifier Transformer Products
Oil-Immersed Power Transformer 33kv 11kv
Intelligent Capacity Regulate and Tap Change Oil Immersed Transformer
Vacuum Resin Cast Dry-Type Transformer Power Transmission
Oil Immersed Distribution Transformer 11kv IEC Standard
11kv Dry Type Distribution Transformer
Low Loss Oil-Immersed Power Transformer 132kv 126kv 110kv
Popular silverstone-electric Products
Steel Square Washer with HDG Stainless Steel Carbon Steel
Vintage Manufacturer Cast Epoxy Resin Bushing Insulator IEC Certificate
Heavy Duty Galvanized Steel Embrace Hoop for Poles and Towers
230kv and Below Rectifier Special Transformer
Vintage Brown Ceramic 38kv Transformer Porcelain Bus Support Bushing
Factory Supply Metal-Oxide Surge Arrester
Tags: Oil Transformet, Power Transformer, Rectifier Transformer, silverstone-electric