38/66kv Cable Accessory Composite Bushing Outdoor Termination
38/66kv Cable Accessory Composite Bushing Outdoor Termination image
Get Latest Price Request a quote
- Overview
- Company Profile
- FAQ
Basic Info.
Packaging & Delivery
Product Description
66-220kV High Voltage Cable Accessories
Our company provides the voltage level of 48/66kV, 64/110kV, 127/220kV and other series of cable accessories are all in accordance with IEC 60502, IEC 60840, IEC 62067, IEC 60859, IEC 62271-209, GB/T 11017, GB/T 18890, GB/T 12706, GB 311, GB 772, DL508, DL509, JB/T8144 and other standards, and have passed the stringent factory test, type test, pre-qualification test.
Termination with composite insulator
Scope of application
For cross linked polyethylene insulated power cables 240-3000mm2.
Suitable for large-scale chemical industry, iron and steel, power substations, coastal areas.
Features
Made of epoxy fiberglass insulated tube covered with liquid silicone rubber, remarkable safety and explosion-proof.
The stress cone is made of imported liquid silicone rubber injection molding, with a long and stable holding force and electric field uniformity.
Composite sleeve for the size of the umbrella structure, the whole outside the formation of a cone, has a very good anti-fouling flash, Weather resistance, anti-leakage marks, anti-electro-etching and water-repellent ability.
The terminal adopts multiple sealing structure to prevent water seepage and oil leakage during operation. water seepage and oil leakage phenomenon.
Structure & Size
1,wire clip (optional)
2,equalizing cover
3,core insulation
4,insulating oil
5,composite set
6,stress cone
7,fixed plate
8,support insulator
9,tail pipe
10,cable
| Size /mm | 48/66kV | 64/110kV | 80/138kV | 127/220kV |
| H | 1270 | 1500 | 1750 | 2500 |
| A | 1510 | 1935 | 2085 | 3100 |
| B | 1925 | 2155 | 2400 | 3600 |
| C | 450 | 450 | 450 | 650 |
| D | 200 | 200 | 200 | 300 |
| E | Φ22 | Φ22 | Φ22 | Φ32 |
| creepage distance | ≥2248 | ≥3906 | ≥4495 | ≥7812 |
Test Specification
All test classifications and codes:
| No.# | Test Name | Code |
| 1 | Routine test | R |
| 2 | Sample test | S |
| 3 | Type test | T |
| 4 | Pre-qualification test | P |
| 5 | Additional test | A |
The following routine tests are performed on stress cones, epoxy bushings of GIS terminals and prefabricated intermediate joints of each product at 66kV and above.
| Item | Voltage | ||||
| 38/66kV | 50/66kV | 64/110kV | 76/132kV | 127/220kV | |
| Partial discharge | 54kV, no detectable local discharge over background | 72kV, no detectable local discharge over background | 96kV, no detectable local discharge over background | 114kV, no detectable local discharge over background | 190kV, no detectable local discharge over background |
| The power frequency withstand voltage | 90kV/30min | 125kV/30min | 160kV/30min | 190kV/30min | 318kV/30min |
| Sealing | Seal fittings, porcelain bushings, composite bushings for 0.25±0.01MPa/1h, no leakage | ||||
| The epoxy casing was subjected to 0.6~0.7MPa/1h with no leakage. | |||||
| Appearance | The products are free of damage, cracks, and other defects that may affect the quality and appearance of the products. | ||||
66-220kV Main Test Parameters
| Item | Standard | Test Category | Product Category | ||||||
| 48/66kV | 64/110kV | 127/220kV | Porcelain Sleeve Terminal | Composite Sleeve Terminal | GIS terminal | Straight / Insulated Joint | flexible terminal | ||
| Sealing Fittings, Porcelain, Composite Sleeves | 0.25±0.01MPa/1h, no leakage | R | yes | yes | yes | – | – | ||
| Epoxy Sleeve | 0.6~0.7MPa/1h, no leakage | ||||||||
| Partial discharge of prefabricated parts | 72kV | 96kV | 190kV | R | yes | yes | yes | yes | yes |
| Detects no more than background discharge | |||||||||
| Frequency withstand voltage of prefabricated parts | 120kV | 160kV | 318kV | R | yes | yes | yes | yes | yes |
| 30min,no flashover, no breakdown | |||||||||
| Partial discharge at room temperature | 72kV | 96kV | 190kV | T | yes | yes | yes | yes | yes |
| Detects no more than background discharge | |||||||||
| Thermal cycling voltage test | 96kV | 128kV | 254kV | T | yes | yes | yes | yes | yes |
| 20 cycles, no flashover, no breakdown | |||||||||
| Partial discharge test at high temperature | 72kV | 96kV | 190kV | T | yes | yes | yes | yes | yes |
| Detects no more than background discharge | |||||||||
| Lightning impact test and subsequent frequency withstand voltage test | 450kV | 550kV | 1050kV | T | yes | yes | yes | yes | yes |
| 10 times for each positive and negative polarity | |||||||||
| 120kV | 160kV | 318kV | |||||||
| 15min, no flashover, no breakdown | |||||||||
| Directly buried joint outer protective layer immersion voltage test | Two ends impact among the 60/75kV,an end of hit 30/37.5kV | Two ends impact among the 60/95kV,an end of hit 30/47.5kV | T | – | – | – | yes | – | |
| Sealing test after assembly of accessories | 0.25±0.01MPa/1h, no leakage | T | yes | yes | yes | yes | yes | ||
| Outdoor terminal rain frequency voltage test | 140kV | 185kV | 460kV | T | yes | yes | – | – | yes |
| 1min, no flashover, no breakdown | |||||||||
| Pillar insulator voltage test | 20kV/1min, no flashover, no breakdown | T | yes | yes | – | – | – | ||
| Radio interference test for outdoor terminals | 61kV | 81kV | 140kV | A | yes | yes | – | – | yes |
| 1MHz radio interference, voltage ≤ 450μV | 1MHz radio interference, voltage ≤ 500μV | ||||||||
| Accessory specimen test | Visual inspection of accessory systems containing cables with no signs of deterioration that could affect the normal operation of the system | T | yes | yes | yes | yes | yes | ||
| DC voltage test | / | No breakdown between conductor and metal shield in connector, 20kV/1min. | T | – | – | – | yes | – | |
| Performance test of crimped connectors for conductor connecting rods | The total area after crimping is not more than 1.2 times the resistance of an equal length of conductor of the same cross-section. | T | yes | yes | yes | yes | yes | ||
/* January 22, 2024 19:08:37 */!function(){function s(e,r){var a,o={};try{e&&e.split(“,”).forEach(function(e,t){e&&(a=e.match(/(.*?):(.*)$/))&&1
We are China 38/66kv Cable Accessory Composite Bushing Outdoor Termination manufacture and supplier,You can get more details with Email,you will get cheap price or factory price.
Get Latest Price Request a quote
Popular 38/66kv Cable Accessory Composite Bushing Outdoor Termination Products
Popular composite bushing Products
12KV 250A DIN42531 medium voltage composite silicone Transformer bushing
52KV 1250A-P4 EN 50180 High voltage composite silicone Transformer bushing
12kv 250A DIN 42531 composite silicone Transformerr bushing
1kv 3150A EN50386 low voltage composite silicone Transformer bushing
12-250/P1 composite silicone Transformerr Bushing EN50180
D 1KV 250A composite silicone Transformerr bushing EN50386
Popular jiuweielectric Products
High Voltage 35kv Silicone Rubber Cable Accessories Cold Shrink Straight Joint Kit
Manufacturer Sells Excellent Wire Protection Cover Electrical Joint Box
Professional Manufacturer Cable Joint Box Insulation Busbar Transformer Cover
Hot Selling Low Voltage Heat Shrink Cable Protection Sleeve
Cable Terminal Vinyl Wire Black End Caps
10/15kv Indoor and Outdoor Silicone Rubber Joints
Popular Outdoor Termination Products
138kv Soft Dry Type Outdoor Termination
High Voltage 66kv Sofy-Dry Type Outdoor Termination
76/132kv Composite Bushing Outdoor Termination
76/132kv Soft Dry Type Outdoor Termination
64/110kv Porcelain Bushing Outdoor Termination
110kv Porcelain Bushing Outdoor Termination
Tags: 38/66kv Cable Accessory Composite Bushing Outdoor Termination, composite bushing, jiuweielectric, Outdoor Termination
