Construction:
Conductors are concentric stranded, compressed conductors of aluminum 1350-H19, Insulated with either polyethylene or XLP cross-linked polyethylene, ,Neutral messengers are concentrically stranded 6201, AAC or ACSR .
Applications:
triplex Service Drop is to supply power from the utility’s lines to the consumer’s weatherhead. For service at 600 volts or less (phase to phase) at a conductor temperature of 75°C maximum for polyethylene insulation or 90°C maximum for cross-linked polyethylene (XLP) insulated
Standards:
Triplex service drop cable meets or exceeds the following ASTM specifications:
ASTM B-230 Aluminum Wire, 1350-H19 for Electrical Purposes.
ASTM B-231 Aluminum Conductors, Concentric-Lay-Stranded.
ASTM B-232 Aluminum Conductors, Concentric-Lay-Stranded, Coated Steel Reinforced (ACSR).
ASTM B-399 Concentric-Lay-Stranded Aluminum Alloy Conductors 6201-T81.
Service drop cable meets or exceeds all applicable requirement of ANSI/ ICEA-S-76-474:
Technical date :
| Code Word | Phase conductor | Bare Neutral Messenger | Weight Per 1000 ft. (lbs.) | Allowable Ampacity+ | |||||||
| Size (AWG) | Stranding | Insul. Thick. (mils) | Size (AWG) | Size (kcmil) | Strand- ing | Rated Strength (lbs.) | XLP | POLY | XLP | POLY | |
| AAAC 6201 ALLOY FULL NEUTRAL MESSENGER | |||||||||||
| Minex | 6 | 1 | 45 | 6 | 30.58 | 7 | 1110 | 101 | 101 | 85 | 70 |
| Hippa | 6 | 7 | 45 | 6 | 30.58 | 7 | 1110 | 107 | 107 | 85 | 70 |
| Prawn | 4 | 1 | 45 | 4 | 48.69 | 7 | 1760 | 152 | 152 | 115 | 90 |
| Barnacle | 4 | 7 | 45 | 4 | 48.69 | 7 | 1760 | 160 | 160 | 115 | 90 |
| Shrimp | 2 | 7 | 45 | 2 | 77.47 | 7 | 2800 | 243 | 243 | 150 | 120 |
| Gammarus | 1/0 | 7 | 60 | 1/0 | 123.3 | 7 | 4460 | 390 | 390 | 205 | 160 |
| Leda | 1/0 | 9 | 60 | 1/0 | 123.3 | 7 | 4460 | 384 | 384 | 205 | 160 |
| Dunganese | 2/0 | 7 | 60 | 2/0 | 155.4 | 7 | 5390 | 474 | 474 | 235 | 185 |
| Cyclops | 2/0 | 11 | 60 | 2/0 | 155.4 | 7 | 5390 | 474 | 474 | 235 | 185 |
| Flustra | 3/0 | 17 | 60 | 3/0 | 195.7 | 7 | 6790 | 587 | 587 | 275 | 215 |
| Lepas | 4/0 | 18 | 60 | 4/0 | 246.9 | 7 | 8560 | 728 | 728 | 315 | 245 |
| *Code words for XLP insulated products are formed by adding "/XLP" to the conventional code words above (e.g.-Haiotis/XLP).+Conductor temperature of 90°C for XLP, 75°C for Poly; ambient temperature of 40°C; emissivity 0.9; 2 ft./sec. wind in sun.++Designated sizes are: ACSR 6/1 diameter equivalent and AAC with equivalent resistivity per ASTM B-399 for 6201. | |||||||||||
| Code Word | Phase conductor | Bare Neutral Messenger | Weight Per 1000 ft. (lbs.) | Allowable Ampacity+ | |||||||
| Size (AWG) | Stranding | Insul. Thick. (mils) | Size (AWG) | Size (kcmil) | Strand- ing | Rated Strength (lbs.) | XLP | POLY | XLP | POLY | |
| AAAC 6201 ALLOY REDUCED NEUTRAL MESSANGER | |||||||||||
| Artemia | 4 | 1 | 45 | 6 | 30.58 | 7 | 1110 | 135 | 135 | 115 | 90 |
| Crab | 4 | 7 | 45 | 6 | 30.58 | 7 | 1110 | 143 | 143 | 115 | 90 |
| Solaster | 2 | 7 | 45 | 4 | 48.69 | 7 | 1760 | 216 | 216 | 150 | 120 |
| Sandcrab | 1/0 | 7 | 60 | 2 | 77.47 | 7 | 2800 | 347 | 347 | 205 | 160 |
| Echinus | 1/0 | 9 | 60 | 2 | 77.47 | 7 | 2800 | 341 | 341 | 205 | 160 |
| Crayfish | 2/0 | 7/w | 60 mls | 2/0 | — | 7 | 2510 | 485.8 | 455.3 | 235 Amps | 185 Amps |
| Sipho | 2/0 | 7/w | 60 mls | 2/0 | — | 7 | 2510 | 485.8 | 455.3 | 235 Amps | 185 Amps |
| Fulgar | 3/0 | 17 | 60 | 1/0 | 123.3 | 7 | 4460 | 519 | 519 | 275 | 215 |
| Arca | 4/0 | 18 | 60 | 2/0 | 155.4 | 7 | 5390 | 643 | 643 | 315 | 245 |
| *Code words for XLP insulated products are formed by adding "/XLP" to the conventional code words above (e.g.-Haiotis/XLP).+Conductor temperature of 90°C for XLP, 75°C for Poly; ambient temperature of 40°C; emissivity 0.9; 2 ft./sec. wind in sun.++Designated sizes are: ACSR 6/1 diameter equivalent and AAC with equivalent resistivity per ASTM B-399 for 6201. | |||||||||||
| Code Word | Phase conductor | Bare Neutral Messenger | Weight Per 1000 ft. (lbs.) | Allowable Ampacity+…………… | ||||||
| Size (AWG) | Stranding | Insul. Thick. (mils) | Size (AWG) | Strand- ing | Rated Strength (lbs.) | XLP | POLY | XLP | POLY | |
| AAC NEUTRAL-MESSENGER | ||||||||||
| Haiotis | 6 | 7/w | 45 mls | 6 | 7 | 563 | 109.1 | 101.6 | 85 Amps | 70 Amps |
| Patella | 6 | 7 | 45 | 6 | 7 | 563 | 103 | 103 | 85 | 70 |
| Fusus | 4 | 7/w | 45 mls | 4 | 7 | 881 | 161.8 | 151.7 | 115 Amps | 90 Amps |
| Oyster | 4 | 7 | 45 | 4 | 7 | 881 | 154 | 154 | 115 | 90 |
| Clam | 2 | 7 | 45 | 2 | 7 | 1350 | 233 | 233 | 150 | 120 |
| Murex | 1/0 | 7 | 60 | 1/0 | 7 | 1990 | 374 | 374 | 205 | 160 |
| Purpura | 1/0 | 9 | 60 | 1/0 | 7 | 1990 | 368 | 368 | 205 | 160 |
| Nassa | 2/0 | 7 | 60 | 2/0 | 7 | 2510 | 462 | 462 | 235 | 185 |
| Melita | 3/0 | 17 | 60 | 3/0 | 19 | 3310 | 562 | 562 | 275 | 215 |
| Portunus | 4/0 | 18 | 60 | 4/0 | 19 | 4020 | 696 | 696 | 315 | 245 |
| Nannynose | 336.4 | 19 | 80 | 336.4 | 19 | 6146 | 1118 | 1118 | 420 | 325 |
| * Code words for XLP insulated products are formed by adding "/XLP" to the conventional code words above (e.g.-Haiotis/XLP).+ Conductor temperature of 90°C for XLP, 75°C for Poly; ambient temperature of 40°C; emissivity 0.9; 2 ft./sec. wind in sun. | ||||||||||
| Code Word | Phase conductor | Bare Neutral Messenger | Weight Per 1000 ft. (lbs.) | Allowable Ampacity+ | ||||||
| Size (AWG) | Stranding | Insul. Thick. (mils) | Size (AWG) | Strand- ing | Rated Strength (lbs.) | XLP | POLY | XLP | POLY | |
| ASCR NEUTRAL-MESSENGER | ||||||||||
| Paludina | 6 | 1 | 45 | 6 | 6/1 | 1190 | 109 | 109 | 85 | 70 |
| Voluta | 6 | 7 | 45 | 6 | 6/1 | 1190 | 114 | 114 | 86 | 70 |
| Whelk | 4 | 1 | 45 | 4 | 6/1 | 1860 | — | 164 | 115 | 90 |
| Periwinkle | 4 | 7 | 45 | 4 | 6/1 | 1860 | 172 | 172 | 115 | 90 |
| Conch | 2 | 7 | 60 | 1/0 | 6/1 | 4380 | 420 | 420 | 205 | 160 |
| Neritina | 1/0 | 7 | 60 | 1/0 | 6/1 | 4380 | 420 | 420 | 205 | 160 |
| Cenia | 1/0 | 9 | 60 | 1/0 | 6/1 | 4380 | 414 | 414 | 205 | 160 |
| Runcina | 2/0 | 7 | 60 | 2/0 | 6/1 | 5310 | 520 | 520 | 235 | 185 |
| Triton | 2/0 | 11 | 60 | 2/0 | 6/1 | 5310 | 512 | 512 | 235 | 185 |
| Mursia | 3/0 | 17 | 60 | 3/0 | 6/1 | 6620 | 635 | 635 | 275 | 215 |
| Zuzara | 4/0 | 18 | 60 | 4/0 | 6/1 | 8350 | 789 | 789 | 315 | 245 |
| Limpet | 336.4 | 19 | 80 | 336.4 | 18/1 | 8680 | 1167 | 1167 | 420 | 325 |
| *Code words for XLP insulated products are formed by adding "/XLP" to the conventional code words above (e.g.-Haiotis/XLP).+Conductor temperature of 90°C for XLP, 75°C for Poly; ambient temperature of 40°C; emissivity 0.9; 2 ft./sec. wind in sun. | ||||||||||
| Code Word | Phase conductor | Bare Neutral Messenger | Weight Per 1000 ft. (lbs.) | Allowable Ampacity+ | ||||||
| Size (AWG) | Stranding | Insul. Thick. (mils) | Size (AWG) | Strand- ing | Rated Strength (lbs.) | XLP | POLY | XLP | POLY | |
| ASCR REDUCED NEUTRAL-MESSENGER | ||||||||||
| Scallop | 4 | 1 | 45 | 6 | 6/1 | 1190 | — | 142 | 115 | 90 |
| Strombus | 4 | 7 | 45 | 6 | 6/1 | 1190 | 151 | 151 | 115 | 90 |
| Cockle | 2 | 7 | 45 | 4 | 6/1 | 1190 | 220 | 220 | 150 | 120 |
| Janthina | 1/0 | 7 | 60 | 2 | 6/1 | 2853 | 366 | 366 | 205 | 160 |
| Ranella | 1/0 | 9 | 60 | 2 | 6/1 | 2853 | 360 | 360 | 205 | 160 |
| Cavolinia | 2/0 | 7 | 60 | 1 | 6/1 | 3550 | 453 | 453 | 235 | 185 |
| Clio | 2/0 | 11 | 60 | 1 | 6/1 | 3550 | 444 | 444 | 235 | 185 |
| Sanddollar | 3/0 | 19/w | 60 mls | 1/0 | 6/1 | 4380 | 565 | 552 | 275 Amps | 215 Amps |
| Aega | 3/0 | 17 | 60 | 1/0 | 6/1 | 4380 | 549 | 549 | 275 | 215 |
| Cuttlefish | 4/0 | 19/w | 60 mls | 2/0 | 6/1 | 5310 | 699 | 684 | 315 Amps | 245 Amps |
| Cerapus | 4/0 | 18 | 60 | 2/0 | 6/1 | 5310 | 681 | 681 | 315 | 245 |
| Cowery | 336.4 | 19 | 80 mls | 336/4 | 18/1 | 8680 | 1209 | 1167 | 420 Amps | 325 Amps |
| *Code words for XLP insulated products are formed by adding "/XLP" to the conventional code words above (e.g.-Haiotis/XLP).+Conductor temperature of 90°C for XLP, 75°C for Poly; ambient temperature of 40°C; emissivity 0.9; 2 ft./sec. wind in sun. | ||||||||||
We are China Triplex Service Drop Overhaed Bundled Cable with XLPE Insulated AAC Conductor manufacture and supplier,You can get more details with Email,you will get cheap price or factory price.
Get Latest Price Request a quote
Popular Aerial Bundled Cable Products
Twist Aluminum Conductor PVC Jacket Aerial Bundle Cable ABC Cable
ASTM Standard 1/0 AWG Service Drop ABC Cable
High Quality XLPE, PE and PVC Insulated ABC Cable Aerial Bundled Cable
Caai Cable 2X25+ND25 Overhead XLPE Insulated Aluminum Conductor Caai Cable / Self-Supporting Cable
Medium Voltage Aerial Bundled Conductor ABC Cables
Sans 1418 Aerial Bundled Cable, ABC Cable, Aerial Cable, ABC Wire
Popular jytopcable Products
Bare Conductor ACSR/Aw Aluminum Conductor Steel Reinforced to ASTM Standard
Factory 11kv Swa Cable 3X150mm with Ce Certificate
Factory AAAC Conductor AAAC Cable for Overhead Transmission
All Aluminum Alloy Conductor AAAC Cal
Duplex Triplex Twisted Aluminum Conductor XLPE Insulated ABC Cable
Bare Aluminum Conducor ACSR for Overhead Transmission
Popular Overhead Aluminum Cable Products
ACSR Hawk, Raven, Swan, Merlin, Aluminum Conductor Steel Reinforced Bare Aluminum Conductor
6AWG XLPE Insulation Electric Aluminum Cable for Overhead
Overhead Aluminium Cable Bare Aluminium Conductor Steel Reinforced Overhead ACSR Conductor
Bare Aluminium Conductor Steel Reinforced ACSR Rabbit Conductor Overhead Aluminum Wire
Quadraplex Service Drop Overhead Aluminum Cable
Popular Triplex Service Drop Cable Products
600V Secondary Distribution Directly Buried Ud/Urd Aluminum Service Drop Cable
AAC/AAAC Conductor Triplex Service Drop Cable XLPE Electric Cables
0.6/1kv Triplex Service Drop Cable Gammarus 2X1/0wg+1X123.3 AAAC Neutral Messenger
3 Phase Conductor Aerial Bundled Cable 5 Core Excellent Corrosion Resistant
Outdoor Customized Aerial Bundled Cables Environmental Protection
Tags: Aerial Bundled Cable, jytopcable, Overhead Aluminum Cable, Triplex Service Drop Cable