Hkgwf-36 35kv Disconnector Switch 33kv Isolators Disconnect
Hkgwf-36 35kv Disconnector Switch 33kv Isolators Disconnect image
Get Latest Price Request a quote
Quick Details
Product Details
The following documents were referred to during the preparation of this specification. In case of conflict, the provisions of this specification shall take precedence.
IEC 129:1975: Alternating Current Disconnectors (Isolators) and Earthing Switches
IEC 60694:2002: Common Specifications for High Voltage Switchgear and Controlgear
BS 729: Hot dip galvanized coating on iron and steel articles
IEC62271-102
Isolator (Disconnector) – a mechanical switching device which provides, in the open position, an isolating distance in accordance with Electrical Safety requirements.
SERVICE CONDITIONS
The isolator shall be suitable for continuous operation outdoors in tropical areas at altitudes of up to 2200m above sea level, humidities of up to 90%, average ambient temperature of +30ºC with a minimum of -1ºC and a maximum of +40ºC and heavy saline conditions along the coast.
4.2. DESIGN AND CONSTRUCTION
4.2.1 The Isolator, Solid Link shall be designed and constructed in accordance with IEC 129 and IEC 60694.
4.2.2 The isolating link shall be of the vertical opening, designed for single phase manual operation. It shall be easily removed and replaced by using a portable operating rod.
4.2.3 The isolating link shall incorporate double porcelain insulators to suit voltage requirements and mounted on hot dipped galvanised steel under base suitable for vertical mounting.
4.2.4 The isolating link shall be arranged so that each unit is mounted independently on an angle bracket. It shall be supplied complete with the angle bracket and accessories suitable for mounting on ‘U’ type steel channel. The drawings to be submitted shall indicate all the applicable mounting positions.
4.2.5 The isolator shall be designed such that in fully open position, it shall provide adequate electrical isolation between the contacts on each phase. It shall conform to the requirement as single point isolation for safety.
4.2.6 All steel parts shall be hot dip galvanized to BS 729. The minimum coating of galvanizing required is 80 microns.
4.2.7 The solid link shall be removable from the mounting by use of operating rod.
4.2.8 All current carrying parts of the isolator shall be made of high conductivity material.
4.2.9 The isolator shall be fitted with clamp connectors for Aluminium (ACSR) conductor of Aluminium (ACSR)conductor of up to 18.2mm diameter.
The rating of the complete isolator shall be as follows: –
Rated voltage
36 kV
Rated frequency
50 Hz
Rated lightning impulse withstand voltage
200 kV
Rated power frequency withstand voltage, dry
95 kV
Rated normal current
400 Amps
Rated short time withstand current for 3 sec, min.
18.0 kA
Minimum creepage distance of insulators
900 mm
We are China Hkgwf-36 35kv Disconnector Switch 33kv Isolators Disconnect manufacture and supplier,You can get more details with Email,you will get cheap price or factory price.
Get Latest Price Request a quote
Popular Disconnector Switch Products
Factory Price 25kv High Voltage Electric Isolator
Outdoor High Voltage Disconnecting Switch/ Isolator Power
New Energy Vehicle Soft Connetion
33 Kv off-Load Isolator Without Earth Blade
33kv Isolator Current 2000A with Earth Switch Manufactory
Popular jgtrade1 Products
15g Sandy Nitrile Glovesnylonblack 7-11
T. J Imported Copper Bolt Connector
Fork with Guardacabo Pin, 5/8, Horquilla Con Guardacabo
Popular Rotary Switch Products
Chave Fusivel Porcelana 27kv Disconnector Switch
Top Selling High Power Electrical Product Fuse Cutout 24kv
Popular Switch Disconnector Products
15kv Indoor Low Voltage Disconnect Switch Disconnector
Best Selling High Voltage Dropout Fuse Cutout 24kv for Protection
Transmission Line 72.5kv Disconnector Switch
Tags: Disconnector Switch, jgtrade1, Rotary Switch, Switch Disconnector