D11 Single-Phase Oil-Immersed Transformer 11kv
D11 Single-Phase Oil-Immersed Transformer 11kv image
Get Latest Price Request a quote
Quick Details
Product Details
| Features of 11kV & 33kV oil-immersed distribution transformer |
1. The features of the product structure are:
Core of transformer are made by the high quality cold-rolled grain-oriented silicon steel sheet with laser notch, cutting by the
imported world first class cut-into-length production line to ensure less shear burrs, high precision lamination, also inclined by
45° full-seam construction, making the silicon steel sheet rolling direction same as the magnetic flux direction, it can reducing
the load loss, load current and noise level.
1.2 HV winding is made with polyvinyl acetal wire enamel wire, layer type, double-sided glue dots paper are used as the layer
insulation between layers, it will stick together after dry, so that the HV winding to solidify to a solid after dry. HV winding
ampere-turns arranged by our specific technology, it will reduce axial strength during short circuit happen.
1.3 Corrugated tank structure used in the transformer design. The imported corrugated tank production line can produce the
corrugated sheet and welding seam automatically, the weld the tank rim and bottom on the welding desk, it will be
performed the leakage test after welding process finished one tank by one tank, and a finally leakage test for whole
transformer to ensure the quality of sealing.
1.4 The oil will be filling in the transformer under vacuum condition, strictly and advanced technology greatly improved the
insulation strength of transformer.
1.5 Lastest invention technology are used on designing of transformer bushing, no pressure pin and plate on the outside, it
avoids oil leakage, steel rust and etc, the structure is reasonable and contour artistic.
1.6 Oil level gauge with magnetic plate structure, it can fully isolation the oil tank and air, can ensure the quality of
transformer oil not to effect by ultraviolet radiation.
1.7 Bar-type No Circuit Tap Changer used on the transformer design, it is easy to be operated. It can be automatically and
quickly switched, and have obviously feeling during switched by hand. Effectively solve the problems of switch as other
tap-changer. Client can also add a lock to prevent the non-normal random switching according their requirement.
2. Dyn11:
The comparison of the Dyn11 and Yyn0 vector group:Both Dyn11 and Yyn0 vector group distribution transformers are
three-phase three-column type, only the insulation requirements of high-voltage winding of Dyn11 transformer, insulation
strength slightly higher than Yyn0, others are all similar. However, still big difference between those two types of transformers.
2.1 Three-column core transformer, the third harmonic flux only can circulate through the tank wall and other parts. Thus,
walls and other components will be heated cause by the stray loss. Dyn11 will much better than Yyn0 in this issue.
2.2 Zero sequence impedance of Dyn11 is much smaller than Yyn0, it is conducive to shut off load in LV side when fault
grounding happened.
2.3 Dyn11 transformer can be running even the neutral current is equal or more than 75% of phase current. Therefore, the
ability to withstand unbalanced load, Dyn11 is greater than Yyn0.
2.4 When one phase fuses in HV side of Dyn11 transformer, the other two-phase load can still run, but Yyn0 can not. So
Dyn11 vector group, the neutral potential displacement of LV side will not be affected by the unbalanced load.
2.5 Whether single-phase short circuit in LV side, or three-phase short circuit, the current is no change with the neutral
grounding type of Dyn11 transformer.
2.6 Single-phase short circuit current of Dyn11 transformer is approximately equal to three-phase short-circuits current,
which is beneficial to fuses choosing. Zero sequence impedance of Yyn0 transformer is greater than the positive and
negative sequence impedance, so the single-phase short-circuit current is less than three-phase short-circuit current, it
will take some difficult in fuses choosing.
We are China D11 Single-Phase Oil-Immersed Transformer 11kv manufacture and supplier,You can get more details with Email,you will get cheap price or factory price.
Get Latest Price Request a quote
Popular Amorphous Transformer Products
Overhead Self Protected Single Phase Pole Mounted Distribution Transformer
33kv Dry-Type Transformer Dimensions with Protection Enclosure
11kv on Load Tap Changer Transformer
330kv Three Phase off Circuit Tap Changing Power Transformer
20kv 24kv 50-3150kVA Distribution Transformer
Type Sc (B) 11-24kv Dry-Type Transformer Dimensions with Protection Enclosure
Popular Oil Transformet Products
Amorphous Alloy Oil-Immersed Distribution Transformer
33kv Sz11 Type on-Load Tap Changer Transformers
11kv Three Phase Pad Mount Mobile Power Distribution Transformer
Intelligent Capacity Regulate and Tap Change Oil Immersed Transformer
D11 Single Phase Oil Immersed Transformer 11kv
Medium Voltage Dry Type Distribution Transformers
Popular Power Transformer Products
132kv Rectifier Special Transformer Factory
11kv S13-M Sealed Oild Immersed Transformer
High Quality Transmission and Distribution Aluminum Alloy Strain Clamp
Sz11 Type 33kv on-Load Tap Changing Transformers
Pad Mount Three Phase Dead Front ANSI Type Transformer Enclosure
High Voltage Power Transformer/Distribution Transformer 30kVA~150mva
Popular silverstone-electric Products
Zj118 12 11kv APG Cast Bushing Epoxy Resin Insulator IEC
Low Loss Oil-Immersed Power Transformer 132kv 126kv 110kv
Single Phase Overhead Self Protected Pole Mounted Distribution Transformer
Vintage White Brown Porcelain Electric Insulator ANSI
Manufacture 2500kVA 33kv Distribution Transformers
132kv 126kv Tap Changing Oltc Traction Transformer
Tags: Amorphous Transformer, Oil Transformet, Power Transformer, silverstone-electric