Link Fittting
Link Fittting image
Get Latest Price Request a quote
Quick Details
Product Details
kV to 38 kV grounded systems with 100 or 200 A nominal currents.
Especially designed to protect transformers, capacitors, cables or lines.
It is robust construction, made of rigorously tested material, will interrupt all faults under the
most severe conditions, maintaining mechanical and electric characteristics.
The inserts, hardware and structural bolts and nuts are made from heavy galvanized steel.
The Fuse Cutout type OEI can be applied on all three-phase system rated at or below the maximum
operational rating of the cutout.
S/N | Description | Units | Schedule A | Schedule B | |
1 | Current ratings | A | 5 | ||
2 | Frequency | Hz | 50 | ||
3 | Rated Speed ratio | Type K as per IEC 60282 -2 |
|||
4 | Class of fuse link | Class B as per IEC 60282-2 |
|||
5 | Fuse element | Tin or Silver | |||
6 | Following Routine test results shall be provided on delivery of fuse links | Yes/No |
a) a static strength test; and | Yes | |
b) a resistance test, with the fuse-link under strain. |
Yes |
||||
7 | The following tests shall be performed on one fuse-link per batch and test results provided on delivery of fuse links: |
Yes/No |
a)confirmation of the time/current characteristics; and |
Yes |
|
b) a dynamic strength test. | Yes | ||||
8 | Drawing showing construction and dimensions as per figure 1 below to be provided with bid |
Yes/No | Yes | ||
9 | Previous type tests reports/certificate to be provided on bid. |
Yes/No |
Yes |
||
10 | Altitude above sea level | m | 1400 | ||
11 | Ambient operating | oC | -1 to 40 |
Performance Characteristic | |
Applied standard | IEEE C37.42-2009 |
Catalog number | |
Nominal system voltage kV | 22 |
Rated Frequency Hz | 50 |
Rated m aximum(design) voltage | 27 |
Rated Continuous current A-RMS | 100 |
Rated Interrupting current asymmetrical/symmetrical A-RMS | 12000/8000 |
BIL 1.2×50 µs kV-peak | 125 |
Minimum critical impulse flashover voltage(CFO)KV peak | 140 |
Dry withstand voltage kV-RMS | 42 |
Wet withstand voltage kV-RMS | 36 |
Creepage distance to group Min.mm | 320 |
Minimum creepage factor of insulator (Creepage Distance/arcing distance) | 2 |
Performance Characteristic | |
Applied standard | IEC60282-2 |
Catalog number | |
Nominal system voltage kV | 11 |
Rated Frequency Hz | 50 |
Rated m aximum(design) voltage | 12 |
Rated Continuous current A-RMS | 100 |
Rated Interrupting current asymmetrical/symmetrical A-RMS | 12000/8000 |
BIL 1.2×50 µs kV-peak | 125 |
Minimum critical impulse flashover voltage(CFO)KV peak | 140 |
Dry withstand voltage kV-RMS | 42 |
Wet withstand voltage kV-RMS | 36 |
Creepage distance to group Min.mm | 372 |
Minimum creepage factor of insulator (Creepage Distance/arcing distance) | N/A |
Performance Characteristic | |
Applied standard | IEEE C37.42-2009 |
Catalog number | |
Nominal system voltage kV | 33 |
Rated Frequency Hz | 50 |
Rated m aximum(design) voltage | 38 |
Rated Continuous current A-RMS | 100 |
Rated Interrupting current asymmetrical/symmetrical A-RMS | 8000/5000 |
BIL 1.2×50 µs kV-peak | 150 |
Minimum critical impulse flashover voltage(CFO)KV peak | 165 |
Dry withstand voltage kV-RMS | 70 |
Wet withstand voltage kV-RMS | 60 |
Creepage distance to group Min.mm | 650 |
Minimum creepage factor of insulator (Creepage Distance/arcing distance) | 2.3 |
DIMENSION(mm) | |||||
RATED CURRENT (A) |
A | B | C | D | L MN |
1 to 25 | 12.5+0.2 | 19.0+0.2 | 6.5 | 2.0 | 533,600,787 |
30 to 40 | 12.5+0.2 | 19.0+0.2 | 8.0 | 3.0 | 533,600,787 |
50 to 100 | 19.0+0.3 | not applicable | 9.0 | 5.0 | 533,600,787 |
140 to 200 | 19.0+0.3 | not applicable | 13.0 | 7.0 | 533,600,787 |
Recommended for You
Not exactly what you want?
Post Sourcing Request
Hot Searches
Voltage Fuse
Protection Fuse
Fuse Box
Low Voltage Fuse
Fast Fuse
We are China Link Fittting manufacture and supplier,You can get more details with Email,you will get cheap price or factory price.
Get Latest Price Request a quote
Popular Fuse Link Products
13G PU Glovespolyester/Nylon Black
10 Gauge Knitted Glovescotton/Polyesterunbleached/Bleached White 7-11
High Temperature-Resistant Gloves (Kevlar)
13G Latex Glovespolyester Linerblack 7-11
Popular High Voltage Fuse Products
T Connectors for Double Conductors Type Mg/Mr, Group B
1 0.5-Inch Split Pigskin Leather Palm, Striped Canvas Back, Starched Safety Cuff
Popular jgtrade1 Products
Yh10W-192, 192kv 10ka Surge Arrester
Seccionador Tripolar, Break Isolator, Substation
High -Voltage Isolate Switch 20kv
High Voltage 33kv Isolator Current 2000A with Earth Switch
Spike for Insulator Head Pole 18 ", Thread 1" of Nylon 18